Aldes 11057261 Parking Hab 2 Ventilators Smoke Extraction Control Box
Product Overview: Smoke Extraction Habitat
Accessory: Helical Fan Ventilator
Model: 11057261
Product Name: COFFRET PARKING HAB 2 VENTILATEURS (Parking Hab 2 Ventilators Control Box)
The Aldes parking habitat smoke extraction control boxes are designed to operate two-speed helical fans for ventilation and smoke extraction purposes in parking facilities.
Key Product Feature: Programmable timer to meet ventilation needs while saving energy.
The control box, with its integrated timer, allows for the programming of fan operation (Low Speed / High Speed / Stop) in anticipation of parking traffic. This system is particularly suitable for collective housing parking facilities. It manages manual smoke extraction activation and smoke extraction shutdown upon request from fire services.
Application Areas
Collective residential housing, new construction, renovation, tertiary premises.
Installation
- Fix the smoke extraction control box to the wall.
Main Features
- Plastic enclosure with IP 55 rating.
- Dimensions for models 4 to 32A: Length x Height x Depth = 375 x 375 x 180 mm.
- Dimensions for models 40 to 57A: Length x Height x Depth = 375 x 500 x 230 mm.
- Dimensions for 2-ventilator model: Length x Height x Depth = 375 x 750 x 230 mm.
- Secured weekly programming timer.
- Motor protection for High Speed (GV) and Low Speed (PV) via magnetic-thermal circuit breakers, with current rating to be selected based on the motors used.
- Range for 2-speed Dahlander motors, 3-phase 400V.
- Input/output terminals for manual smoke extraction triggers (normally closed contact).
- Optional connection for key-operated fire service shutdown (normally closed contact).
- Manual and wiring diagrams are available from your local Aldes agency.
Dimensional Data
References | H (mm) | L (mm) | P (mm) |
---|---|---|---|
11057261 | 750 | 375 | 230 |
Diagram showing dimensions: Height (H), Length (L), and Depth (P) with labels.
Principle of Operation
Power Supply: 3X400V-50Hz
Diagram:
The diagram illustrates the wiring connections for the smoke extraction control box. It shows inputs for:
- Fire service stop (Arrêt pompier) - connected to a normally closed contact.
- Smoke extraction trigger (Déclencheur(s) manuel(s)) - connected to a normally closed contact.
- Timer (Horloge) - controlling fan speeds.
- Motor protection (IPVGV) - magnetic-thermal circuit breakers.
- Proximity switch (Interrupteur de proximité 2V) - for 2-speed operation.
Outputs are shown for connecting to the motor terminals (U1, V1, W1 for low speed; U2, V2, W2 for high speed) and a common terminal (XM).
Motor Type: 2-speed Dahlander, 3-phase.
Wiring Principle: Illustrates the connection of the control box to the motor and various control inputs.
For more information, contact your Aldes advisor.
Visit: www.aldes.com