Schneider Electric MicroLogic 2.2/5.2/6.2 Trip Units

ComPact NSX100-250 Series

Important Safety and Usage Notes

Please Note: Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. Schneider Electric assumes no responsibility for any consequences arising from the use of this material.

Remarque Importante: L'installation, l'utilisation, la réparation et la maintenance des équipements électriques doivent être assurées uniquement par du personnel qualifié. Schneider Electric décline toute responsabilité quant aux conséquences de l'utilisation de ce matériel.

Tenga en Cuenta: La instalación, manejo, puesta en servicio y mantenimiento de equipos eléctricos deberán ser realizados sólo por personal cualificado. Schneider Electric no se hace responsable de ninguna de las consecuencias del uso de este material.

请注意: 电气设备的安装、操作、维修和维护工作仅限于合格人员执行。Schneider Electric 不承担由于使用本资料所引起的任何后果。

Product Overview

This document provides installation and setting instructions for Schneider Electric MicroLogic 2.2, 5.2, and 6.2 trip units, designed for the ComPact NSX100-250 range of circuit breakers.

MicroLogic 2.2 Trip Unit:

The MicroLogic 2.2 trip unit is a thermal-magnetic trip unit for ComPact NSX circuit breakers. It offers adjustable long-time (Ir) and short-time (Isd) protection settings.

MicroLogic 5.2/6.2 Trip Units:

The MicroLogic 5.2 and 6.2 trip units are electronic trip units providing advanced protection functions, including adjustable long-time (Ir), short-time (Isd), instantaneous (Ii), and earth-fault (Ig) settings, depending on the model.

Model References: GHD16045AA-11, LV429451, LV429521 (25-100 A), LV430563 (150-250 A).

Installation Guide

Follow these steps for installing the MicroLogic trip units:

  1. Mounting the Trip Unit: Align the MicroLogic trip unit with the base unit. Push the trip unit downwards until it clicks into place. Ensure it is securely attached.
  2. Connecting Terminals: Connect the power and control circuits to the appropriate terminals on the trip unit. Refer to specific wiring diagrams for your configuration (e.g., 3P, 4P, 3P+N).
  3. Wiring Details: For specific connections, such as ENCT (Earth Neutral Trip), ensure the correct wire gauge (S: 0.4-1.5 mm², AWG 22-16) is used. Terminal connections like T2 and T1 are indicated for specific functions.
  4. Operation Check: After installation, the unit can be switched ON or OFF. The 'Tripped' state is indicated when the circuit breaker has operated due to a fault. A 'Push to trip' button is available for manual testing.

Example Installation Steps (MicroLogic 2.2):

Example Installation Steps (MicroLogic 5.2/6.2):

Parameter Setting Guide

The MicroLogic trip units allow for adjustment of various protection parameters. The following describes common settings:

MicroLogic 2.2 Settings (Ir, Isd)

The MicroLogic 2.2 unit allows adjustment of Long-Time Overcurrent (Ir) and Short-Time Overcurrent (Isd) protection.

Ir Adjustment:

The Ir setting is a percentage of the nominal current (In). For example, if In = 100 A, and Ir is set to 0.95, then Ir = 95 A.

Isd Adjustment:

The Isd setting is a multiple of Ir. For example, Isd = Ir x 4.

Example Calculation: If In = 100 A, Ir = 63 A (0.63 x In), then Isd = 63 A x 4 = 252 A.

3P-4P Configuration: The unit can be configured for 3-pole or 4-pole operation.

MicroLogic 5.2/6.2 Settings (Ir, Isd, tsd, li, Ig, tg)

These units offer more advanced settings:

Setting Procedure Example (MicroLogic 5.2E/6.2E):

The settings are adjusted using the buttons on the front panel (Mode, OK, Up/Down arrows). The display shows the current setting. Navigate through parameters (Ir, tr, Isd, tsd, li, Ig, tg) and adjust values using the arrow buttons. Press OK to confirm each setting.

Example: Setting Ir to 63 A:

  1. Press 'Mode' to cycle through parameters until 'Ir' is displayed.
  2. Press 'OK'.
  3. Use the arrow buttons to set the value to 63.
  4. Press 'OK' to confirm.

Example: Setting Isd to 0.5 x In:

  1. Press 'Mode' to cycle through parameters until 'Isd' is displayed.
  2. Press 'OK'.
  3. Use the arrow buttons to set the value to 0.5.
  4. Press 'OK' to confirm.

Example: Setting li to 2.0 x In:

  1. Press 'Mode' to cycle through parameters until 'li' is displayed.
  2. Press 'OK'.
  3. Use the arrow buttons to set the value to 2.0.
  4. Press 'OK' to confirm.

User Guide Reference: For detailed information, refer to the MicroLogic User Guide (DOCA0141EN, DOCA0141FR, DOCA0141ES, DOCA0141ZH).

Technical Specifications & Configuration

ComPact NSX100-250 Series: Designed for high-performance electrical distribution.

MicroLogic 2.2: Thermal-magnetic trip unit.

MicroLogic 5.2/6.2: Electronic trip units with advanced protection features.

Configuration Options:

Torque Values:

Wire Gauge: S: 0.4-1.5 mm² (AWG 22-16) for specific connections.

Models: ComPact NSX100-250, Circuit Breaker, ComPact NSX100-250 Circuit Breaker, Breaker, GHD16045AA-11

File Info : application/pdf, 4 Pages, 3.51MB

PDF preview unavailable. Download the PDF instead.

files?p enDocType=Instruction sheet&p File Name=GHD1604501-11 &p Doc Ref=GHD16045AA

References

Adobe PDF library 16.03

Related Documents

Preview ComPacT NSX MicroLogic Trip Units: Installation, Adjustment, and Safety Guide
This guide provides essential information for installing, adjusting, and testing Schneider Electric's ComPacT NSX MicroLogic 2.2, 5.2, and 6.2 trip units. It covers safety warnings, operational procedures, configuration settings, and manufacturing date information, ensuring proper and safe use of the equipment.
Preview Schneider Electric ComPacT NSX100-250 MicroLogic 4.2 Trip Units Installation and Operation Manual
This document provides comprehensive instructions for the installation, adjustment, testing, and operation of Schneider Electric ComPacT NSX100-250 MicroLogic 4.2 and 4.2AL trip units. It includes critical safety warnings, detailed procedures, and technical specifications to ensure safe and effective use of the equipment.
Preview MasterPact MTZ - MicroLogic X Control Unit User Guide
Comprehensive user guide for Schneider Electric's MasterPact MTZ circuit breakers featuring the MicroLogic X control unit. Details protection functions, metering capabilities, maintenance procedures, and cybersecurity recommendations for electrical distribution systems.
Preview Masterpact MTZ Micrologic X Control Unit User Guide - Schneider Electric
This user guide from Schneider Electric details the Masterpact MTZ circuit breakers and their integrated Micrologic X control units, covering advanced protection, metering, communication, and diagnostic functions essential for modern electrical installations.
Preview Schneider Electric MicroLogic Trip Units: Installation, Settings, and Operation Guide
A comprehensive guide for installing and configuring Schneider Electric MicroLogic 1.3, 2.3, 5.3, and 6.3 trip units for ComPact NSX400-630 circuit breakers. Covers safety precautions, parameter settings (Ir, Isd, Ig, etc.), and Zone Selective Interlocking (ZSI).
Preview Preventative Maintenance Guide for Schneider Electric PowerPacT Circuit Breakers with MicroLogic 5/6 Trip Units
Comprehensive instruction bulletin detailing preventative maintenance, alarm management, communication, and software configuration for Schneider Electric PowerPacT H-, J-, and L-Frame Circuit Breakers featuring MicroLogic 5 and 6 Trip Units. Essential for ensuring system reliability and performance.
Preview Schneider Electric ComPacT NSX400-630 MicroLogic Trip Units: Installation and Adjustment Guide
Comprehensive guide for installing, adjusting, and testing Schneider Electric ComPacT NSX400-630 circuit breakers with MicroLogic 1.3/2.3 and 5.3/6.3 trip units. Includes safety warnings, setup procedures, and setting configurations.
Preview MasterPact MTZ IEC Devices: Basic and Standard End-User Maintenance Procedures Guide
Schneider Electric's MasterPact MTZ IEC Devices Maintenance Guide offers essential procedures for basic and standard end-user maintenance, ensuring optimal performance and safety of circuit breakers and switch-disconnectors.