ComPacT™ NSX400-630 MicroLogic Trip Units
This document provides installation, adjustment, and operational guidance for Schneider Electric ComPacT™ NSX400-630 circuit breakers equipped with MicroLogic 1.3/2.3 and 5.3/6.3 trip units.
For the latest documentation and support, visit www.se.com/support.
Important Safety Information
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. Schneider Electric assumes no responsibility for consequences arising from the use of this material. All pertinent state, regional, and local safety regulations must be observed when installing and using this product.
Failure to follow these instructions will result in death or serious injury.
Product Overview
The ComPacT™ NSX400-630 series offers advanced circuit protection solutions. This guide focuses on the installation and configuration of MicroLogic trip units, specifically models 1.3/2.3 and 5.3/6.3.
Associated documentation:
- ComPacT NSX100-630 User Guide (DOCA0187EN, DOCA0187FR, DOCA0187ES, DOCA0187ZH)
- ComPacT NSX MicroLogic 5/6/7 User Guide (DOCA0188EN, DOCA0188FR, DOCA0188ES, DOCA0188ZH)
1. Required for Installation
Ensure you have the necessary tools and materials before proceeding with installation:
- Screwdriver (PZ2)
- Screwdriver (T25)
- Snap-off screws (LV432513)
- Voltage sensing device
2. Before Working on Equipment
Follow these critical steps before performing any work on the equipment:
- Turn off all power supplying the equipment before working on or inside it.
- Use the push-to-trip button to trip the device.
- Use a properly rated voltage sensing device to confirm power is off.
3. Installation
WARNING: HAZARD OF FIRE
When installing the MicroLogic trip unit, ensure that the snap-off screws (A) break when tightened. It is mandatory to use snap-off screws LV432513 for installation. If replacing a trip unit with one of a different rating, you must redefine trip unit settings and adapt connection characteristics.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
3.1 MicroLogic 1.3/2.3 Installation
- Loosen and remove screws from the front cover or accessories as indicated in the instruction sheet shipped with the device.
- Install the trip unit into its compartment.
3.2 MicroLogic 5.3/6.3 Installation
3.2.1 MicroLogic 3P 5.3/6.3
- Connect the trip unit supply wires to terminals T1 and T2. Use wires with a cross-section of 0.4-1.5 mm² (22-16 AWG) and torque to 0.2 N.m (2 lb-in).
3.2.2 MicroLogic 3P 5.3E/6.3E + ENVT
- Connect the trip unit supply wires.
- Ensure the device trips with a 'Click!' sound when the push-to-trip button is activated.
3.2.3 MicroLogic 3P 5.3/6.3 + ZSI
- Connect ZSI (IN) and ZSI (OUT) terminals using wires with a cross-section of 0.4-1.5 mm² (22-16 AWG).
- Torque connections to 0.2 N.m (2 lb-in).
4. Reinstall Front Cover
NOTICE: HAZARD OF EQUIPMENT DAMAGE
Be careful not to pinch wires when installing the front cover. Tighten all front cover screws to the specified torque. Do not overtighten screws, and do not use power equipment for torquing.
Failure to follow these instructions can result in equipment damage.
- Put back the front cover and accessories as indicated in the instruction sheet shipped with the device.
- The device is now ready to be placed in service.
5. Tripping Test
Perform a tripping test to verify the functionality of the trip unit.
- Ensure the device is ON.
- Press the push-to-trip button.
- The device should indicate 'Tripped' after activation.
6. MicroLogic 1.3/2.3 Trip Unit Adjustment
Adjust the trip unit settings (Ir, Isd) according to the required protection levels.
For 3P/4P units:
- In: Set the nominal current rating.
- Io: Adjust the short-circuit threshold.
- Ir: Set the long-time pickup current. Example: Ir = 400 A x 0.95 = 380 A.
- Isd: Set the short-time pickup current. Example: Isd = 380 A x 5 = 1900 A.
For 4P units:
Settings include Ir, Io, Isd, and potentially Ig (for specific configurations like 3D+N/2 or 4D).
7. MicroLogic 5.3/6.3 Trip Unit Adjustment
7.1 Trip Unit Supply
Ensure the trip unit receives proper power supply.
7.2 Settings with Rotary Dial
Adjust trip unit settings using the rotary dial and buttons.
MicroLogic 5.3:
- Set Ir (Long-time pickup current) and Isd (Short-time pickup current).
- Example settings shown for Ir = 400 A and Isd = 5.0 x Ir.
MicroLogic 6.3:
- Set Ir (Long-time pickup current) and Ig (Ground fault pickup current).
- Example settings shown for Ir = 400 A and Ig = 0.60 x In.
7.3 Settings on HMI
Configure trip unit parameters via the Human-Machine Interface (HMI).
For MicroLogic 5.3: Adjust Ir, tr, Isd, tsd, li.
For MicroLogic 6.3: Adjust Ir, tr, Isd, tsd, li, lg, tg.
The HMI interface allows detailed setting adjustments for various protection functions. Steps involve navigating menus, selecting parameters, and confirming values.
8. Sealing
Instructions for installing a sealing accessory to secure trip unit settings.
9. Manufacturing Date
The product's manufacture date is coded as PP-YYYY-Www-D:
- PP: Plant code
- YYYY: Year of manufacture
- Www: Week of manufacture
- D: Weekday of manufacture (Monday = 1)
Example: 7Q-2019-W20-3 indicates a product manufactured at plant 7Q on Wednesday, May 15, 2019.
Additional Information and Warnings
California Proposition 65 Warning:
This product can expose you to chemicals including lead and lead compounds, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.