Bosch FLM-420-12 Interface Input Modules

Product Overview and Technical Specifications

Key Features

  • Line monitoring with end-of-line resistor
  • Dry contact monitoring
  • Voltage monitoring
  • Individual monitoring of two inputs
  • LSN ring fault tolerance with two internal isolators

System Overview

The FLM-420-12 interface input modules are designed to control up to two inputs. They function as 2-wire addressable LSN elements, connecting to the LSN security network and offering enhanced system parameters. These modules are crucial components in fire alarm systems, ensuring reliable detection and communication.

Diagram Description: The system overview diagram illustrates the FLM-420-12 module connected to a fire alarm system loop. It shows the module with its terminals for LSN connection (b1+, b2+), input connections (IN1+, IN1-, IN2+, IN2-), power supply, and shield. The LSN connection is depicted as a loop, highlighting the module's role within the network.

Technical Specifications

Electrical Characteristics

ParameterSpecification
LSN Voltage15 V to 33 V DC
Max. LSN Line Current10.4 mA
Inputs2, independent
End-of-line Resistance3.9 kΩ nominal
Line Resistance StatesNormal: 1500-6000 Ω
Break: > 12,000 Ω
Short Circuit: < 800 Ω
Dry Contact Monitoring Current8 mA
Voltage Monitoring Range0 V DC to 30 V DC
Input Resistance≥ 50 kΩ
Voltage Thresholds0.8 V, 3.3 V, 10.2 V, 21.2 V DC (± 0.3 V or ± 0.5 V)

Mechanical Characteristics

ParameterSpecification
ConnectionsTerminal blocks (14 for E/W, 7 for D)
Wire Cross-Section0.6 mm² to 2.0 mm² (E/W)
0.6 mm² to 3.3 mm² (D)
Address SettingDIP switches (E/W), Rotary switches (D)
Housing MaterialABS/PC (E/W), PPO (D)
ColorWhite, RAL 9003 (E/W)
White, similar to RAL 9002 (D)

Dimensions

ModelDimensions (approx.)
FLM-420-12-E50 mm x 22 mm (Ø x H)
FLM-420-12-W76 mm x 30 mm (Ø x H)
FLM-420-12-D110 mm x 110 mm x 48 mm (W x H x D)

Weight

ModelWeight (with/without packaging)
FLM-420-12-E35 g / 130 g
FLM-420-12-W55 g / 155 g
FLM-420-12-D150 g / 235 g

Environmental Conditions

ParameterSpecification
Operating Temperature-20 °C to +65 °C
Storage Temperature-25 °C to +80 °C
Relative Humidity< 96% (non-condensing)
Equipment Class (IEC 60950)Class III
Protection Class (IEC 60529)IP 30

System Limits

ParameterSpecification
Max. Cable Length per Input3 m

Product Variants

The FLM-420-12 series is available in three main variants:

  • FLM-420-12-E: Flush-mount interface input module with 2 monitored inputs, suitable for standard enclosures (e.g., switch programs). Requires an enclosure depth of at least 60 mm.
  • FLM-420-12-W: Wall-mount interface input module with 2 monitored inputs, designed for surface mounting, either directly or using the FLM-IFB126-S enclosure.
  • FLM-420-12-D: DIN-rail mount interface input module with 2 monitored inputs, designed for installation on standard DIN rails (EN 60715) or within the FLM-IFB126-S enclosure.

Models -E and -W also support loop-through connection for additional LSN power supply.

Certifications and Compliance

The FLM-420-12 modules comply with the following standards and have received relevant certifications:

  • EN 54-17:2005
  • EN 54-18:2005
  • VdS (e.g., G 207076)
  • CE
  • CPD (e.g., 0786-CPD-20288)
  • MOE (e.g., UA1.016-0070269-11)

Installation and Configuration Notes

  • Modules can be connected to Bosch fire alarm panels such as FPA-5000 and FPA-1200.
  • Address setting is performed using DIP switches (for -E/-W models) or rotary switches (for -D models), or via panel software.
  • The LSN improved technology supports flexible network architectures, including T-type branches, without additional components.
  • The maximum cable length for each input is 3 meters.

Ordering Information

Product CodeDescription
FLM-420-12-EInterface input module, flush-mount
FLM-420-12-WInterface input module, wall-mount (with cover and accessories)
FLM-420-12-DInterface input module, DIN-rail mount (with adapter and fiber optic)

Accessories

  • FLM-IFB126-S: Enclosure for surface mounting, for use as a holder for the 420 series interface modules for DIN-rail mounting (-D) or surface mounting (-S).
  • FMX-IFB55-S: Surface mount enclosure for wall-mount 420 series interface modules.

Contact Information

For inquiries in Russia:

Robert Bosch OOO Security Systems
13/5, Akad. Korolyova str.
129515 Moscow, Russia
Phone: +7 495 937 5361
Fax: +7 495 937 5363
Email: Info.bss@ru.bosch.com, ru.securitysystems@bosch.com
Website: www.bosch.ru

PDF preview unavailable. Download the PDF instead.

FLM 420 I2 Data sheet ruRU 1297323915 AH Formatter V5.0 MR2a (5,0,2009,0623) for Windows Antenna House PDF Output Library 2.6.0 (Windows)

Related Documents

Preview Bosch FLM-420-12-W Input Interface Module Wall-mount Installation Guide and Technical Specifications
Comprehensive guide for the Bosch FLM-420-12-W Input Interface ModuleType Wall-mount, covering installation, safety, functional descriptions, address setting, connections, and detailed technical specifications.
Preview Bosch FLM-420-NAC Signaling Device Interface Module Installation and Technical Guide
Comprehensive guide for installing and configuring Bosch FLM-420-NAC-S and FLM-420-NAC-D Signaling Device Interface Modules. Covers functional description, address setting, connections, technical specifications, and safety precautions for LSN fire alarm systems.
Preview Bosch FPA-5000 Modular Fire Panel System Information and Installation Guide
Comprehensive technical guide for the Bosch FPA-5000 Modular Fire Panel system, covering installation, configuration, components, and technical specifications for advanced fire detection and alarm management.
Preview Manual de funcionamiento AVENAR detector 4000
Manual de funcionamiento para el AVENAR detector 4000 de Bosch, incluyendo información sobre sus características, descripción del sistema, sensores, accesorios y compatibilidad.
Preview Bosch Base Sounder Indoor FNM-420-A-BS Installation Manual
Installation manual for the Bosch Base Sounder Indoor (FNM-420-A-BS-RD, FNM-420-A-BS-WH). Includes safety instructions, functional description, and technical specifications.
Preview Détecteurs automatiques version LSN improved - Guide d'utilisation Bosch
Guide d'utilisation détaillé pour les détecteurs automatiques LSN improved de Bosch, incluant les modèles FAP-O 520, FAP-O 520-P, FAP-OC 520 et FAP-OC 520-P. Couvre la description du produit, l'installation, la programmation, la maintenance et les spécifications techniques.
Preview Bosch FAP-520 Automatic Fire Detectors Operation Manual
This document provides comprehensive operational instructions for the Bosch FAP-520 series automatic fire detectors, including installation, programming, maintenance, and technical specifications. It covers both optical (FAP-O 520) and multisensor (FAP-OC 520) models designed for LSN improved systems.
Preview Bosch Automatische Brandmelder, LSN improved version FAP-520 Serie Bedienungsanleitung
Bedienungsanleitung für die Bosch Automatische Brandmelder, LSN improved version, FAP-520 Serie. Enthält Informationen zu Produktbeschreibung, Projektierungshinweisen, Installation, Programmierung, Wartung und Service, sowie technische Daten.