Goodman CPLE Series 10 SEER Split System Heat Pump
Product Specifications
Product Overview
The Goodman CPLE split system heat pump is designed for ground-level or rooftop mount applications. It offers capacities ranging from 1½ to 5 Ton and features a 10 SEER (Seasonal Energy Efficiency Ratio) rating.
[Image: A Goodman outdoor unit for a split system heat pump, featuring the Goodman logo and 'Air Conditioning & Heating' text. It shows a vertical louvered cabinet with a fan grille on top. The unit is labeled with '5-YEAR COMPRESSOR LIMITED WARRANTY' and '5-YEAR PARTS LIMITED WARRANTY' seals, along with ETL and ARI certification marks.]
Standard Features
- Energy-efficient compressor with internal high-pressure relief
- Louvered guard protects coil from damage and adds strength to unit
- Bottom pan rails elevate unit above slab
- Quiet operating top discharge
- Totally enclosed and permanently lubricated condenser motor
- Copper tube, aluminum fin coil
- Brass liquid and suction service valves with sweat connections
- Fully charged for 15' of tubing length
- Factory-installed bi-flow liquid line filter drier
- Discharge line muffler
- Suction line accumulator
- Check-flowrater expansion device
- Time initiated, temperature-terminate defrost
- Low-pressure control for loss of charge protection
- Crankcase heater (where indicated)
Cabinet Construction
- Polyester powder paint provides premium durability and improved UV protection
- Heavy gauge, zinc-clad, G90 galvanized steel
- When properly anchored, meets the 2001 Florida Building Code unit integrity requirements for hurricane-type winds
Air Handler and Coil Compatibilities
- ARUF, ARPT and AEPT multi-position electric heat air handlers
- ARPF dedicated downflow electric heat air handler
- AWB vertical wall-mounted electric heat air handler
- AH vertical wall-mounted hydronic heat air handler
- AC ceiling-mounted electric heat air handler
- ACHP ceiling-mounted hydronic heat air handler
- MBR/MBE modular blower
- CA, CH and H indoor coils
Accessories
- Standard Room Thermostat with 1-stage cool/2-stage heat (HPT18-60)
- Digital Room Thermostat with 1-stage cool/2-stage heat (CHTP18-60HD)
- Outdoor Lockout Thermostat/Emergency Heat Relay Kit for staging electric heat (OT/EHR18-60)
- Outdoor Thermostat (OT18-60); required for all heat pumps if outdoor ambient temperature is 0°F with 50% or higher relative humidity
Specifications
Service Valve and Shipping Weight
Model | Liquid | Suction | Type | Approximate Shipping Weight (pounds) |
---|---|---|---|---|
CPLE18-1B/-1C | 3/8" | 3/4" | Sweat | 127 |
CPLE24-1B/-1C | 3/8" | 3/4" | Sweat | 137 |
CPLE30-1A/-1C | 3/8" | 3/4" | Sweat | 140 |
CPLE36-1A/-1C | 3/8" | 3/4" | Sweat | 152 |
CPLE42-1B/-1C | 3/8" | 7/8" | Sweat | 162 |
CPLE48-1A/-1C | 3/8" | 7/8" | Sweat | 178 |
CPLE48-3A/-3C | 3/8" | 7/8" | Sweat | 178 |
CPLE60-1/-1C | 3/8" | 7/8" | Sweat | 210 |
CPLE60-3/-3C | 3/8" | 7/8" | Sweat | 210 |
Electrical Data
Model | Volts | Ph | Hz | Minimum Circuit Amps¹ | Maximum Overcurrent Protection² | Minimum Volts | Maximum Volts | Compressor RLA | Compressor LRA | Condenser Fan FLA | Condenser Fan HP |
---|---|---|---|---|---|---|---|---|---|---|---|
*CPLE18-1B/-1C | 208/230 | 1 | 60 | 13.1 | 20 | 197 | 253 | 9.4 | 49 | 1.3 | 1/6 |
*CPLE24-1B/-1C | 208/230 | 1 | 60 | 17.6 | 30 | 197 | 253 | 13.0 | 56 | 1.3 | 1/6 |
*CPLE30-1A/-1C | 208/230 | 1 | 60 | 18.4 | 30 | 197 | 253 | 13.7 | 75 | 1.3 | 1/6 |
*CPLE36-1A/-1C | 208/230 | 1 | 60 | 22.1 | 30 | 197 | 253 | 16.2 | 96 | 1.8 | 1/4 |
*CPLE42-1B/-1C | 208/230 | 1 | 60 | 23.2 | 40 | 197 | 253 | 17.1 | 105 | 1.8 | 1/4 |
*CPLE48-1A/-1C | 208/230 | 1 | 60 | 24.6 | 40 | 197 | 253 | 18.3 | 102 | 1.8 | 1/4 |
*CPLE48-3A/-3C | 208/230 | 3 | 60 | 17.6 | 30 | 197 | 253 | 12.6 | 91 | 1.8 | 1/4 |
**CPLE60-1/-1C | 208/230 | 1 | 60 | 33.1 | 50 | 197 | 253 | 25.0 | 150 | 1.8 | 1/4 |
**CPLE60-3/-3C | 208/230 | 3 | 60 | 21.1 | 30 | 197 | 253 | 15.4 | 124 | 1.8 | 1/4 |
Notes:
- ¹ Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
- ² May use fuses or HACR type Circuit Breakers of the same size as noted.
- ³ The -*C models are painted Architectural Gray. All other models are painted Bahama Beige.
- * With Crankcase Heat
- ** Uses Scroll Compressor
Dimensions
[Diagram: Shows the dimensions of the Goodman CPLE Series outdoor units. It specifies chassis sizes: 'SMALL CHASSIS = 23"' and 'LARGE CHASSIS = 29"'. Detailed model dimensions are provided: CPLE18 = 22.5", CPLE24 and CPLE30 = 30", CPLE36 = 25", CPLE42 = 30", CPLE48 and CPLE60 = 32.5". Connection points are clearly marked: 'LIQUID CONN.', 'SUCTION CONN.', '1-1/8" DIA. POWER', and '7/8" DIA. CONTROL'. An 'ADDITIONAL 1-1/2" ELEVATED CHANNEL' is also depicted.]
Performance Ratings
Cooling Performance
Model Outdoor Section | Model Indoor Section | Total Cooling BTUH (1) | Sensible Cooling BTUH | (2) BTUH @ 75 °F / 63 °F-95 °F | Total Sens | Cooling SEER | Cooling EER (3) |
---|---|---|---|---|---|---|---|
CPLE18-1B/-1C | AH18 AC18-XX AWB18-XX ARUF018 HT1830/U18/UC18+EEP | 16,200 | 11,400 | 15,700 | 10,800 | 10.00 | 9.00 |
AWB24-XX AH24/ARUF024/ARPT024 ARPF024 HT3236/H36F+EEP UC29/U29+EEP CA*F018*2A+EEP CA*F024*2A+EEP CHPF024A2A+EEP CHPF030A2A+EEP | 17,000 | 11,700 | 15,700 | 10,800 | 10.00 | 9.00 | |
CPLE24-1B/-1C | AH24 AC24-XX AWB24-XX ARUF024/ARPT024 ARPF024 HT1830/U29/UC29+EEP AH30/AWB30-XX/ARUF030 U30+EEP AWB36-XX/ARUF032/ARPT032 AC30-XX U31/U32/UC32+EEP HT3236/H36F+EEP CA*F024*2A+EEP CA*F030*2A+EEP CHPF024A2A+EEP CHPF030A2A+EEP | 21,800 | 16,000 | 22,500 | 15,500 | 10.00 | 9.00 |
CPLE30-1A/-1C | AC30-XX HT3236/U29/UC29+EEP AWB30-XX ARUF030 U30+EEP H36F+EEP AWB36-XX/ARUF032/ARPT032 ARPF036 HT4248/U31/H48F+EEP U32/UC32+EEP CA*F024*2A+EEP CA*F030*2A+EEP CHPF030A2A+EEP CHPF042B2A+EEP | 27,000 | 19,000 | 26,800 | 18,000 | 10.00 | 9.00 |
CPLE36-1A/-1C | HT36/U35/UC35+EEP AC36-XX/ARPF036 AWB36-XX/ARUF036/ARPT036 HT3236/U36/UC36+EEP HT4248+EEP ARUF042/ARPT042 U42/UC42/H49F+EEP CA*F036*2A+EEP CA*F042*2A+EEP CHPF030A2A+EEP CHPF036B2A+EEP CHPF042B2A+EEP | 32,000 | 22,500 | 30,600 | 23,000 | 10.00 | 9.00 |
Heating Performance Expanded Ratings @ 70 °F Indoor Ambient
[Graphs: Illustrate Heating Performance Expanded Ratings at 70°F Indoor Ambient. Each graph shows the relationship between Outside Temperature (in degrees Fahrenheit) on the x-axis and Heating BTUH (British Thermal Units per Hour) and COP (Coefficient of Performance) on the y-axes. The solid line represents Heating BTUH, and the dashed line represents COP.]
Model Outdoor Section | Model Indoor Section | Heating BTUH 47 °F | Heating COP 47 °F | Heating BTUH 17°F | Heating COP 17 °F | Heating HSPF | Decibels |
---|---|---|---|---|---|---|---|
CPLE18-1B/-1C | AH18 AC18-XX AWB18-XX ARUF018 HT1830/U18/UC18+EEP | 16,000 | 3.00 | 10,200 | 2.20 | 6.80 | 77 |
AWB24-XX AH24/ARUF024/ARPT024 ARPF024 HT3236/H36F+EEP UC29/U29+EEP CA*F018*2A+EEP CA*F024*2A+EEP CHPF024A2A+EEP CHPF030A2A+EEP | 17,400 | 3.00 | 10,600 | 2.20 | 6.80 | 77 | |
CPLE24-1B/-1C | AH24 AC24-XX AWB24-XX ARUF024/ARPT024 ARPF024 HT1830/U29/UC29+EEP AH30/AWB30-XX/ARUF030 U30+EEP AWB36-XX/ARUF032/ARPT032 AC30-XX U31/U32/UC32+EEP HT3236/H36F+EEP CA*F024*2A+EEP CA*F030*2A+EEP CHPF024A2A+EEP CHPF030A2A+EEP | 21,400 | 3.00 | 12,400 | 2.00 | 7.00 | |
CPLE30-1A/-1C | AC30-XX HT3236/U29/UC29+EEP AWB30-XX ARUF030 U30+EEP H36F+EEP AWB36-XX/ARUF032/ARPT032 ARPF036 HT4248/U31/H48F+EEP U32/UC32+EEP CA*F024*2A+EEP CA*F030*2A+EEP CHPF030A2A+EEP CHPF042B2A+EEP | 26,000 | 3.00 | 15,000 | 2.00 | 6.80 | 77 |
CPLE36-1A/-1C | HT36/U35/UC35+EEP AC36-XX/ARPF036 AWB36-XX/ARUF036/ARPT036 HT3236/U36/UC36+EEP HT4248+EEP ARUF042/ARPT042 U42/UC42/H49F+EEP CA*F036*2A+EEP CA*F042*2A+EEP CHPF030A2A+EEP CHPF036B2A+EEP CHPF042B2A+EEP | 33,000 | 3.10 | 18,600 | 2.10 | 7.30 | 80 |
Notes:
- ¹ Certified per ARI 240 @ 80 °F/67 °F/95 °F
- ² TVA Rating
- ³ Seasonal Energy Efficiency Ratio
- ⁴ Energy Efficiency Ratio @ 80 °F/67 °F/95 °F
- ⁵ HSPF = Heating Seasonal Performance Factor
- ⁶ Order the EEP from the Service Department using Part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not interchangeable with B13707-35S.
- When mix-matching outdoor and indoor units, the indoor unit check-flowrator must match the outdoor unit size.
- See the AR series air handler for coil instructions.