Greenheck Heat-Cool Only Controls for Dedicated Outdoor Air System

Supplement Microprocessor Controller

Document 486987

Technical Support: Call: 1-866-478-2574 | Email: doas@greenheck.com

Overview

This document is a supplement to the Microprocessor Controller for Dedicated Outdoor Air System Installation, Operation and Maintenance Manual (IOM). All safety information from the IOM also pertains to Heat-Cool Only controls.

Heat-Cool Only Overview

The Heat-Cool Only system is designed to enable third-party control of a packaged DX or Heat Pump unit while preserving the safeties of the refrigeration and heating systems. The Heat-Cool Only controller is factory installed and commissioned, managing the unit's refrigeration and heating components. Refrigeration system safety is maintained through monitoring pressures and temperatures within the circuit. The third party is responsible for controlling:

A field-supplied and installed third-party device provides occupancy, temperature, and airflow monitoring. This device interfaces with the Heat-Cool Only controller via a terminal strip in the control cabinet.

END DEVICES: End devices for Heat-Cool Only operation are factory-provided for the heat/cooling control system. Sensors for third-party controller operation must be provided and installed by the third party. Additional end devices not provided by the factory may be used by the third-party control system. Refer to unit submittal information for specific unit configuration and factory-provided end devices.

WARNING: Powering the third-party controller is the third party's responsibility. A transformer supplied and installed by the third party must power their controller. This power cannot be sourced from the control panel. The third-party device must not be mounted within the unit's electrical control panel.

System Diagram: A block diagram illustrates the system architecture. It shows a "Third Party Controller" communicating via a "Terminal Strip" with the "Heat-Cool Only Controller". The "Heat-Cool Only Controller" manages "Refrigeration & Heating Components" and "Non-tempering Components". Arrows indicate bidirectional communication between the controller and the terminal strip, and between the terminal strip and the Heat-Cool Only Controller.

Third Party Responsibilities

Occupancy, temperature, airflow, and third-party device power for Heat-Cool Only systems are the responsibility of the third party via a dedicated device. This includes timing of occupied modes and logic for enabling/modulating all non-refrigeration or heating components.

Occupancy

Scheduling and occupancy mode control are the responsibility of the third party.

Airflow

Maintaining proper airflow by enabling and modulating fans and dampers is the responsibility of the third-party controller. During normal operation, airflow should continue over the unit's heat exchangers after the remote start command to the Heat-Cool Only controller is removed. For units with variable speed compressors, compressors may take up to two minutes to stop completely. In heating mode, supply airflow should continue until supply air temperatures drop below 80°F to dissipate residual heat and prevent excessive component temperatures.

Damper Positioning

Dampers require power and a position signal for modulation. Before starting fans, the third party must ensure an open airflow path by confirming the damper end switch is closed (if installed).

Fan Modulation

The third-party controller is responsible for enable and modulation signals.

WARNING: When modulating gas furnace heating capacity, maintain a maximum temperature rise and minimum airflow to prevent improper combustion and unit damage. Refer to Appendix B for specific minimum airflow requirements.

Gas Furnace Heat: Limit turndown to the minimum airflow based on unit size or 50.0% of design airflow, whichever is greater. Refer to unit submittal information for exact gas furnace performance data.

Energy Recovery

Control of energy recovery equipment (heat wheel with/without VFD, core with face/bypass dampers, or bypass-only damper) is the third party's responsibility, controlled via a third-party provided sensor.

Energy Recovery Defrost

Both forms of energy recovery require a defrost sequence provided by the third-party controller.

Temperature

Heat-Cool Only Control requires the third party to make decisions for heating, cooling, dehumidifying, or economizing based on operating conditions and setpoints. Setpoints are communicated via hard-wired 2-10 VDC signals:

The third-party controller must manage economizer and energy recovery capacity to meet current requirements. Analog output signals are sent via the terminal strip or directly to end devices. Refer to Appendix A for wiring schematics and terminal strip information.

Digital Status

The Heat-Cool Only terminal strip provides digital status information from installed devices:

Digital Commands

FILTER PRESSURE SWITCH

Indicates dirty filters when installed.

GLOBAL ALARM OUTPUT

Indicates an alarm condition in the Heat-Cool Only controller.

A2L SYSTEM RESPONSE

A standard hardwired system monitoring for refrigerant leaks, responding in two ways:

  1. Air Tunnel Leak: Unit overrides supply fan and damper operation to move stagnant refrigerant for dilution. Ignition sources are disabled, and compressor operation is stopped. The supply fan operates at the higher of minimum heat operation CFM or UL-required minimum airflow for dilution. Recirculation dampers force 100% recirculation. 100% outdoor air units force 100% outdoor air. Heat operation (electric post heat, indirect gas heat) is allowed. The building is responsible for energy wheel speed, frost control, and exhaust fans.
  2. Compressor Section Leak: Unit disables compressor operation and indirect gas heat. The airstream fan is not forced on, and heat operation is not allowed. If no indirect gas heater is present, no refrigerant sensor is in the compressor section.

Alarm outputs are available for monitoring and external actions like opening zone dampers, disabling duct-mounted electric resistance heaters, or enabling mechanical ventilation. These can be accessed via the building management system or hardwire mitigation system contacts.

Mitigation system response verification requires removing the A2L mitigation test jumper at start-up. Additional testing may be required by local code.

Refrigerant sensors initiate a safety sequence upon leak detection. Maintain sensors free of dust. Alarm status is available as an electronic signal and a relay dry contact. End-of-life results in a leak detected indication. Refer to the sensor's blink code for status (Solid green: power-up/self-test; Blinking green: normal operation; Solid red: alarm/gas detected; Blinking red: sensor fault/replace).

Operation of Unit

All Modes

The following conditions are required for the third party to enable unit operation in any mode:

NOTE: These safety checks are the responsibility of the third-party controller and are not input to the controller.

Cooling

The following conditions are required for the third party to enable the unit and start compressors in cooling mode:

Dehumidifying

NOTE: Hot Gas Reheat must be installed in the unit to utilize this functionality.

The following conditions are required for the controller to enable a unit in dehumidification mode:

Heating

The following conditions are required for the controller to enable a unit in heating mode:

Heating - Heat Pump

The following conditions are required for the controller to enable a unit and start compressors in heating mode:

Appendices

Appendix A: Terminal Strip Wiring

The following table details the terminal strip wiring for Heat-Cool Only operation, serving as the wiring point for the third-party control device. Refer to unit schematics for additional information.

TerminalTerminal TypeDescription/DeviceThird Party IO Type
50C (2)CommonCommon
5010.0-10.0 VDCSupply Fan Speed InputAnalog Command
5020.0-10.0 VDCExhaust Fan Speed InputAnalog Command
5030.0-10.0 VDC *Energy Recovery Capacity Input *Analog Command
51CCommon from ControllerCommon
5112.0-10.0 VDCCooling Coil Temperature Setpoint InputAnalog Command
5122.0-10.0 VDCSupply Air Temperature Setpoint InputAnalog Command
60C (2)CommonCommon
6012.0-10.0 VDCOutside/Recirc Air Damper SignalAnalog Command
60224 VACOutside/Recirc Air Damper Actuator PowerDigital Command
60324 VACSupply Fan StartDigital Command
60424 VACExhaust Fan StartDigital Command
60524 VACEnergy Recovery Wheel StartDigital Command
60624 VACPre-Heater EnableDigital Command
60724 VACReturn/Exhaust Damper Actuator PowerDigital Command
70P (2)24 VAC power or 24 VAC common from unitDigital Command
701Building Fire AlarmDigital Command
702See Wiring DiagramRemote Start InputDigital Command
703Cooling(0)/Dehumidification(1) Control ModeDigital Command
704Cooling(0)/Heating (1) Control ModeDigital Command
80C (3)CommonCommon
801Global Alarm Output (Heat/Cool Alarms Only)Digital Status
802Outside Air Damper End Switch (100% OA Units)Digital Status
803Condensate Overflow SwitchDigital Status
804Energy Recovery StatusDigital Status
805Filter Pressure SwitchDigital Status
806Return/Exhaust Damper End SwitchDigital Status
90C (2)CommonCommon
901 (2)24 VACAFMS Power24 VAC
9020.0-10.0 VDCSupply Airflow Measuring StationAnalog Feedback
9030.0-10.0 VDCExhaust Airflow Measuring StationAnalog Feedback
9040.0-10.0 VDCOutdoor Airflow Measuring StationAnalog Feedback
71R21 NCAirstream Mitigation sequence activeStatus - Alarm/off state is normal state
72R21 CommonAirstream Mitigation sequence activeCommon
73R21 NOAirstream Mitigation sequence activeStatus - Alarm/off state is normal state
74R23 NCIndirect Gas Furnace lockout activeStatus - Alarm/off state is normal state
74R23 CommonIndirect Gas Furnace lockout activeCommon
76R23 NOIndirect Gas Furnace lockout activeStatus - Alarm/off state is normal state

* This terminal position is for any energy recovery device, heat wheel, core with face/bypass dampers, or core with bypass only damper. The voltage for either core option is 2.0-10.0VDC.

Appendix B: Gas Furnace Limitations

Supply fan modulation must be limited to the minimum airflow based on unit size or 50% of design airflow, whichever is greater. When modulating gas furnace heating capacity, maintain a maximum temperature rise and minimum airflow for all units.

WARNING: Criteria must be met when controlling gas furnace staging and modulation to prevent improper combustion and unit damage. Airflow reduction is allowed only if supply air temperature does not exceed the max temp rise. Supply air temp must be monitored, and the furnace modulated to prevent over-firing at low airflows.

  1. Locate unit casing size, furnace MBH, and airflow supply direction for minimum airflow in CFM in the table below.
  2. Limit all gas furnaces to the greater of: minimum airflow in CFM, OR 50% of design airflow.
  3. Third-party controls will send a 2-10VDC signal for a supply air temperature setpoint between 50.0°F (10.0°C) and 95.0°F (35.0°C) in all modes.
  4. Third-party controls must have a high supply temperature limit of 120.0°F (48.8°C) to shut down all heating sources when supply air temperature is greater than or equal to this limit.
  5. Minimum Temp Rise of 20.0°F for all furnaces.
Unit Casing SizeFurnace MBHBottom DischargeSide Discharge
Max Temp RiseMin Airflow CFMMax Temp RiseMin Airflow CFM
RV-2075100.0°F556100.0°F556
RVE-20100100.0°F741100.0°F741
150100.0°F1,111100.0°F1,111
200100.0°F1,481100.0°F1,481
RV-40100100.0°F741100.0°F741
RVE-40200100.0°F1,481100.0°F1,481
RVC-40300100.0°F2,222100.0°F2,222
RV-85300100.0°F2,222100.0°F2,222
RVE-85400100.0°F2,963100.0°F2,963
RVC-85600100.0°F3,704100.0°F3,704
RV-150600100.0°F4,444100.0°F4,444
RVE-150800100.0°F5,926100.0°F5,926
1000100.0°F7,407100.0°F7,407
1200100.0°F8,889100.0°F8,889
RV-220800100.0°F5,926100.0°F5,926
1200100.0°F8,889100.0°F8,889
1600100.0°F11,852100.0°F11,852
2000100.0°F14,814100.0°F14,814

Appendix C: Supply and Exhaust Airflow Calculations

If airflow monitoring for the outside air damper is installed, it can be one of two types of airflow, each with its own calculations and setup.

Supply and Exhaust Fan Models

The following table shows available supply and exhaust fan blade models and their corresponding K Factor. The third party needs to know the fan model number, quantity, and whether an airflow monitoring station was purchased.

ManufacturerModel NumberFan Blade MaterialFan Blade DiameterK Factor
GreenheckPRM-450Aluminum450mm/18"1899
GreenheckPRM-560Aluminum560mm/22"2975
GreenheckPDL-355Aluminum355mm/14"1160

Supply and Exhaust Fan Airflow Measurement

The third-party controller can use transducer signals from the supply and/or exhaust fan and the airflow formula to determine current airflow.

FORMULA: CFM = k * √ (△P)

Where:

NOTE: Supply and exhaust airflow are calculated separately. Only include fans of the same type in the calculation.

Appendix D: GreenTrol Airflow Calculations

GreenTrol Airflow Monitoring

The GreenTrol® airflow monitoring station uses advanced thermal dispersion technology. An integral LCD displays airflow measurement and device configuration. It accepts up to two airflow probes for averaging.

GreenTrol Airflow Monitor functions:
ANALOG OUTPUTS:

The airflow monitoring controller has two configurable analog outputs for transmitting airflow, temperature, or PID control. Outputs can be configured for 0-10VDC, 0-5VDC, or 2-10VDC. The controller is factory configured to use analog output 1 for outdoor airflow rate and analog output 2 for outdoor air temperature. The airflow monitoring output is wired to the customer terminal strip for Heat-Cool Only controls. Refer to the airflow controller's technical manual for configuration instructions and the Field Calibration Wizard.

FORMULA: Calculating airflow based on the analog output signal:

Airflow = (Signal Voltage - Minimum Voltage) / (Maximum Voltage - Minimum Voltage) * Full Scale Airflow

Our Commitment

As part of its commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are available on greenheck.com under product area tabs and in the Library under Warranties.

AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information and can be obtained from AMCA International, Inc. at www.amca.org.

[Greenheck Logo] Building Value in Air.

Contact Information:

Document 486987 • Heat-Cool Only Controls for DOAS, Rev. 3 August 2025

Copyright 2025 © Greenheck Fan Corporation

PDF preview unavailable. Download the PDF instead.

486987 HeatCoolOnly iom Adobe PDF Library 17.0

Related Documents

Preview Greenheck Microprocessor Controller for Dedicated Outdoor Air Systems - Reference Guide
This reference guide provides detailed information on the Greenheck Microprocessor Controller for Dedicated Outdoor Air Systems (DOAS), covering its program features, operation modes, setpoint controls, and advanced functions. Learn about BMS communication, occupancy settings, and various operational sequences for optimal performance.
Preview GREENHECK DG, DGX, TSU, VSU Direct Gas Make-Up Air & Industrial Space Heat Installation, Operation, and Maintenance Manual
Official Installation, Operation, and Maintenance Manual for GREENHECK Direct Gas Make-Up Air and Industrial Space Heat units (Models DG, DGX, TSU, VSU). Covers safety, installation, operation, maintenance, and troubleshooting for industrial and commercial HVAC applications.
Preview Greenheck Vari-Green Control Indoor Air Quality Temperature and Humidity Controller Installation, Operation, and Maintenance Manual
Comprehensive manual for the Greenheck Vari-Green Control Indoor Air Quality Temperature and Humidity Controller (PN 387127). Covers installation, operation, maintenance, wiring, programming, troubleshooting, and safety guidelines for HVAC systems.
Preview Greenheck Grease Trapper ESP™ Kitchen Exhaust Pollution Control System Manual
Comprehensive installation, operation, and maintenance manual for the Greenheck Grease Trapper ESP™ Kitchen Exhaust Pollution Control System, detailing setup, troubleshooting, and maintenance procedures.
Preview Greenheck Vari-Green Motor and Controls Installation, Operation, and Maintenance Manual
This manual provides comprehensive instructions for the installation, operation, and maintenance of Greenheck's Vari-Green Motor and Controls. It covers features, troubleshooting, wiring diagrams, and specifications for various motor models.
Preview Greenheck Vari-Green Drive (VGD-100/100+) Installation, Operation, and Maintenance Manual
Comprehensive guide for the Greenheck Vari-Green Drive (VGD), covering installation, operation, maintenance, and troubleshooting for models VGD-100 and VGD-100+. Details features, wiring, safety instructions, and communication protocols like Modbus and BACnet.
Preview Greenheck Packaged DX Module Installation, Operation, and Maintenance Manual
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Greenheck Packaged DX Module. It covers safety precautions, component descriptions, installation procedures, start-up checklists, troubleshooting, and routine maintenance.
Preview Greenheck HOA Controller Installation, Operation, and Maintenance Manual
This manual provides comprehensive installation, operation, and maintenance instructions for the Greenheck 100-277Vac HOA Controller. It includes safety precautions, component descriptions, wiring diagrams, troubleshooting guides, and product specifications.