Quick Guide - Access Software 4.0-1-04 to 4.1-1-00

Document translated from English

1 General

The NaviPad is Systemair's control panel featuring a 7" capacitive touchscreen. It provides operational information for connected units and allows control of all functions. Navigation is done by touching the screen to activate a function, change a setting, or read real-time values.

After 5 minutes of inactivity, the screen enters sleep mode. Touch the screen to return to the previous screen. After another 10 minutes of inactivity, you will be returned to the system overview (Figure 3) and will need to log in again.

Editable texts and values are displayed in blue and vary depending on the user level.

As the unit's control panel consists of a web server with web pages, it is possible to use a computer to browse the control panel. Identify the unit's IP address using the NaviPad (see Example 4) and enter it into the address bar of a web browser.

Important

  • The unit and NaviPad, along with any computer used, must be connected to a local network with the same IP subnet.
  • The Chrome browser is supported for navigating the unit's web pages from a computer.

Figure 1: (1) Start/Home button, (2) USB connection, reset button, (3) Power supply and communication.

Figure 2: NaviPad Holder, (1) Mounting points, (2) Cable hook. Attach the holder to the unit using the provided screws (wall mounting is also possible; use mounting hardware suitable for the wall construction).

1.1 Startup Wizard

During the first startup of the NaviPad, you must calibrate the screen by lightly touching the crosshairs.

You will then be prompted to enter the following information:

  • Language
  • Date and Time

Available units will be displayed in the overview list. Select the unit you wish to pair with the NaviPad. Use the serial number of the regulator in the unit to ensure you pair the correct unit with the NaviPad.

If the startup wizard is interrupted, it will restart upon the next startup of the NaviPad. This will continue until the startup wizard is completed.

Version: PR1.2 (1.1.0.128) and later

Startup Wizard Flow:

Step 1: Startup wizard starts.

Step 2: Scan for units.

Step 3: If 1 or more units are discovered, select a unit.

Step 4: Select language.

Step 5: Set date and time.

Step 6: System overview is displayed.

After the startup wizard is completed, the system overview is shown. Touch the unit's image to select it.

Figure 3: System Overview showing Unit Name and Normal Operation status.

1.2 Keyboard

When a name, value, or password needs to be changed or entered, a keyboard will appear at the bottom of the touchscreen.

1.3 Symbol Description

  • Home [?]: Navigate to system overview.
  • Data and Settings [⚙️]: View operational information and settings.
  • Flow Diagram [?]: Schematic overview of the unit.
  • Language [?]: Change language.
  • Date and Time [⏰]: Set date, time, and weekly programs.
  • Settings [?]: Alarm and function settings, I/O mapping.
  • Alarm Symbol [?]: Indicates active alarms; pressing the symbol leads to the alarm list.

1.4 User Levels

User LevelAccess RightsActions
End User (Not logged in)Read-only - Start Page (Fig. 1)Possible actions include stopping the unit for maintenance (e.g., filter change), changing extended run time, and adjusting temperature setpoints. Flow diagrams and active alarms in the alarm list are visible.
Operator Mode (Login: 1111)Read/write rights (excluding Configuration)Acknowledge/block/unblock alarms and view alarm history.
Service Mode (Login: 0612)Full read and write rightsFull read and write access.

2 Alarms

The LED light on the start button (Figure 1, (1)) indicates the unit's status:

  • Solid Green: Status OK (no active alarms).
  • Flashing Red: Active/returned alarms in one or more units.
  • Solid Red: Confirmed/blocked alarms in one or more units; alarms have not been reset.

Different Alarm Levels

  • Class A Alarm: Must be acknowledged.
  • Class B Alarm: Must be acknowledged.
  • Class C Alarm: Disappears when the cause of the alarm is removed.

2.1 Alarm List

Navigation: Data and Settings > Alarm List

ActionStatus
Acknowledge allNo
Name: Filter 1Level: [Class B]
View all alarmsStatus: New alarm
Alarm history[Available when pressing the alarm symbol]

Alarm Status: Activated, Acknowledged, Blocked, Returned.

3 Regulator Settings

Menus and functions may vary depending on the actual configuration and/or application version of the unit.

3.1 Data and Settings

  • 3.1.1 Operation Overview: Displays active signals, I/O signals, and operating modes. Includes parameters like Temperature, Airflow/Pressure, CO2, RH, Heating, Heat Exchanger, Cooling Coil, and Recirculation.
  • 3.1.2 Input/Output Status: Provides an overview of sensors, I/O, fan regulation, temperature sequencing, and operating modes. All can be controlled in manual mode. Options include manual sensor setting, fan locking during adjustment, manual I/O testing of external functions, and raw values.

3.1.3 Temperature Regulation

Settings for temperature, including limit values, setpoints for current regulation types, min/max limitations, and outdoor temperature values.

Example 1: Setpoint for current regulation type

Navigation: Data and Settings > Temperature Regulation > Supply Air

ParameterValue
Supply Air Temperature10.4 °C
Setpoint Adjustment0 °C
Setpoint Adjustment Low Speed0 °C
Setpoint Adjustment High Speed0 °C
Supply Air Setpoint18 °C

This example shows temperature regulation set to supply air. To change a setpoint, touch the current value and select the desired setting from the pop-up menu. Confirm with OK. (Editable text and values are shown in blue on the NaviPad.)

3.1.4 Fan Regulation

Settings for fan regulation, including setpoints for different fan speeds, fan compensation (e.g., outdoor compensated fan curves), fan/damper start delay, SFP menu, and external fans.

3.1.5 Demand Control

Settings for CO2, Recirculation, Pressure Regulation, and Free Cooling.

3.1.6 Fire/Smoke

Settings for Fire Damper, Smoke Detector Status, and Fire Damper Test.

3.1.7 Humidity Control

Setpoints and settings for dehumidification and humidification.

3.2 Flow Diagram

Flow Diagram Description: A dynamic flow diagram displays the configured unit, showing active sensors and components with real-time values. Touching blue-highlighted values or elements navigates to related settings or overview pages.

3.3 Language

Language Settings: To synchronize the NaviPad with all connected units, go to the system overview by pressing the Home button (Figure 1, (1)) and select the language. Using the language icon on individual unit start screens via NaviPad or computer will only change the language for that specific unit.

3.4 Time Settings

This menu allows you to change the date and time, as well as other system settings.

Settings include: Date and Time, Operating Periods (Examples 2 & 3), Holidays, and Extra time groups.

Each day can have up to two individual operating periods; set the desired start and stop times. For holidays, enter dates under Time Settings > Operating Period > Holiday Calendar and times under Time Settings > Schedule > Low Fan Speed / Normal Fan Speed / High Fan Speed.

Example 2: Operating Period for Normal Fan Speed

DayStart (12-hour)Stop (12-hour)Start (24-hour)Stop (24-hour)
Monday5:00 AM18:00 AM00:00 AM00:00 AM
Monday5:00 AM18:00 AM00:00 AM00:00 AM

This example shows the unit starting at normal fan speed at 5:00 AM and stopping at 6:00 PM (18:00). The second operating period is deactivated.

Example 3: Operating Period for Low Fan Speed

DayStart (12-hour)Stop (12-hour)Start (24-hour)Stop (24-hour)
Monday18:00 AM00:00 AM00:00 AM5:00 AM
Monday18:00 AM24:0000:00 AM5:00 AM

This example shows the unit starting at low fan speed at 6:00 AM and stopping at 12:00 AM (midnight). The second low fan speed period is between 12:00 AM (00:00) and 5:00 AM.

3.5 Settings

  • System Settings
  • Settings Wizard (Example 4)
  • Function Settings (Example 5)
  • I/O Mapping
  • Alarm Settings (Example 6)
  • PID Controllers

The Settings Wizard is a menu that simplifies the procedure for activating and setting up common accessories and functions, and assigning inputs and outputs. The wizard automatically performs necessary settings and guides the user through limited options.

Example 4: Settings Wizard

Navigation: Settings > Settings Wizard

  • Configure pressure regulation
  • Configure cooler
  • Configure changeover
  • Return to Settings menu

If the settings wizard does not cover the desired accessory or function, it can still be set via the settings menu.

Example 5: Function Settings

Navigation: Settings > Functions > Function Activation

FunctionStatus
Fan CompensationYes
Standby OperationNo
CO2 RegulationNo

To activate a function, go to Function Activation. Select the function you want to activate and choose 'Yes' in the subsequent pop-up menu. Values for the activated function will now be visible and can be adjusted under Data Settings. If necessary, inputs and outputs are assigned in I/O Mapping.

4 Advanced HMI Settings

To return to the system overview dashboard, press the Home button (Figure 1, (1)). Navigate to Advanced HMI Settings. Login is required (1111).

Settings:

  • NaviPad Settings
  • Home
  • Language
  • Time and Date Settings
  • Advanced HMI Settings
  • Restart NaviPad

Available Units (Aggregates) (Example 7)

Change Password

Ethernet Settings: The IP address can be configured to either obtain an IP address from a DHCP server (dynamic) or be manually set as a static IP address. [Further support on setting a static IP address can be found in the manual for Manual Access Communication.]

Restore NaviPad Factory Settings (Example 8)

Software Update

Example 6: Alarm Configuration

Navigation: Settings > Alarms

Alarm TypeValue
Supply air filter alarm53
Extract air filter alarm54
Low airflow alarm55
Freeze protection56
Heat exchanger defrost protection57
Fire alarm58
Smoke alarm59

Navigation: Settings > ... > Supply air filter alarm

ParameterValue
ActionNo action
LevelClass B
Delay300 s
No.53
NameSupply air filter alarm
Original TextSupply air filter alarm
Limit X10 m³/h
Limit X22000 m³/h
Limit Y110 Pa
Limit Y2150 Pa

Example 7: Available Units (Aggregates)

Navigation: Home > Advanced HMI Settings > Available Units

Unit displayed: 192.168.41.38 Select Unit

Serial NumberIP AddressName
012345678910192.168.41.116Unit Name
058345678919192.168.41.49Unit Name

The air unit is displayed; touch the button to select the unit for pairing with NaviPad. If multiple units are on the same IP subnet, a list of available units will be shown. The IP address of the NaviPad itself is displayed above the 'Select Unit' heading.

Example 8: Restore NaviPad Factory Settings

You will be prompted to confirm the action. All settings, including passwords, will be reset, and the startup wizard will run again.

5 No Communication

Navigation: Home > Available Units

Unit Name: No Communication

If the symbol above is displayed, communication with the selected unit is lost. This can happen if the IP number has changed. Go back to Available Units (Aggregates), Figure 4, deactivate all units first, and then activate them again.

PDF preview unavailable. Download the PDF instead.

QUICKGUIDE ACCESS SW 4 0-1-06 TO 4 1-1-00 1516714 A005 NO PDFlib PDI 9.1.2p4 (C /Win64) Arbortext Publishing Engine

Related Documents

Preview Systemair Topvex SoftCooler SR09/SR11 Operation and Maintenance Instructions
This document provides comprehensive operation and maintenance instructions for the Systemair Topvex SoftCooler SR09 and SR11 access control systems. It covers product description, installation, function descriptions, cooling flow charts, maintenance procedures, and alarm management.
Preview Systemair Topvex SR60-R-EL7,1 M0 ODK: Compact Air Handling Unit
Detailed product information for the Systemair Topvex SR60-R-EL7,1 M0 ODK, a side-connected model of compact air handling units for outdoor applications, featuring high-efficiency rotary heat exchanger and Systemair Access control.
Preview STS 2.0 Smart Touch Screen Control Installation Guide
Installation instructions for the Systemair STS 2.0 Smart Touch Screen Control, covering safety precautions, best practices, step-by-step installation, and troubleshooting.
Preview Systemair Topvex SoftCooler SR09, SR11: Operation and Maintenance Manual
This manual provides detailed information on the operation, installation, and maintenance of the Systemair Topvex SoftCooler SR09 and SR11 access control systems. It covers system components, functions, technical specifications, and troubleshooting.
Preview Systemair SAVE VTR 500 User Manual
User manual for the Systemair SAVE VTR 500 heat recovery ventilation unit, covering its features, configuration, operation, maintenance, and troubleshooting.
Preview Systemair Topvex Suspended Air Handling Units: Compact, Efficient Ventilation
Explore the Systemair Topvex series of suspended air handling units, designed for compact installation and energy efficiency. Ideal for various building types, featuring advanced Access control system for easy operation and monitoring.
Preview Systemair CB 250-3,0 230V/1 Duct Heater: Features, Specs, and Wiring
Detailed overview of the Systemair CB 250-3,0 230V/1 electrical duct heater, highlighting its compact design, flexible installation, robust construction, and double overheating protection. Includes technical specifications, performance data, dimensions, wiring diagram, and accessories.
Preview Systemair SAVE VTR 150/B Installation Manual
Comprehensive installation manual for the Systemair SAVE VTR 150/B heat recovery ventilation unit. Covers general information, technical specifications, dimensions, mounting procedures for various kitchen hoods, electrical connections, system checks, commissioning, and disposal guidelines.