4KVA/5KVA Parallel Installation Guide

1. Introduction

This inverter can be used in parallel with two different operation modes:

  1. Parallel operation in single phase with up to 6 units. The supported maximum output power is 24KW/30KVA.
  2. Maximum six units work together to support three-phase equipment. Four units support one phase maximum. The supported maximum output power is 24KW/30KVA and one phase can be up to 16KW/20KVA.

NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following instruction from professional technical personnel in local dealer.

2. Package Contents

In parallel kit, you will find the following items in the package:

Diagram shows three items: a parallel board with connectors, a parallel communication cable, and a current sharing cable.

3. Parallel board installation

This installation steps are only applied to 4K/5K models.

  1. Step 1: Remove wire cover by unscrewing all screws ?.

    Diagram shows an inverter with screws being removed from its wire cover.

  2. Step 2: Remove communication board by unscrewing two screws ?.

    Diagram shows the rear of the inverter with screws being removed near the communication board.

  3. Step 3: Remove two screws ? and disconnect the 2-pin and 14-pin cables ?. Take out the board under the communication board.

    Diagram shows the communication board being removed, with 2-pin and 14-pin cables disconnected.

  4. Step 4: Remove two screws ? to take out the cover of the parallel communication.

    Diagram shows screws being removed from a parallel communication cover.

  5. Step 5: Install the new parallel board with 2 screws ? tightly.

    Diagram shows a new parallel board being installed with screws.

  6. Step 6: Re-connect the 2-pin and 14-pin cables ? to their original positions.

    Diagram shows the 2-pin and 14-pin cables being reconnected to the parallel board and communication board.

  7. Step 7: Put the communication board back to the unit.
  8. Step 8: Put the wire cover back to the unit. Now the inverter is providing parallel operation function.

4. Mounting the Unit

When installing multiple units, please follow the chart below:

Diagram shows four inverters arranged horizontally with arrows indicating spacing: approximately 20 cm clearance on the sides and 50 cm clearance above and below each unit.

NOTE: For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit. Be sure to install each unit on the same level.

5. Wiring Connection

The cable size of each inverter is shown below:

Recommended battery cable and terminal size for each inverter:

Model Wire Size Ring Terminal Cable mm² Dimensions Torque value
D (mm) L (mm)
4KVA 1*4AWG 22 6.4 33.2 2~3 Nm
2*8AWG 14 6.4 29.2
5KVA 1*4AWG 22 6.4 33.2 2~3 Nm
2*8AWG 14 6.4 29.2

Diagram illustrates a ring terminal with labels for diameter (D) and length (L).

WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery, causing parallel inverters not to work.

Recommended AC input and output cable size for each inverter:

Model AWG no. Torque
4KVA 10 AWG 1.4~1.6Nm
5KVA 8 AWG 1.4~1.6Nm

You need to connect the cables of each inverter together. Take the battery cables for example: You need to use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from the joint to the battery should be X times the cable size in the tables above, where “X” indicates the number of inverters connected in parallel. Regarding AC input and output, please also follow the same principle.

CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input. The recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.

Recommended breaker specification of battery for each inverter:

Model 1 unit*
4KVA 80A/60VDC
5KVA 100A/60VDC

*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times the current of 1 unit, where “X” indicates the number of inverters connected in parallel.

Recommended breaker specification of AC input with single phase:

Model 2 units 3 units 4 units 5 units 6 units
4KVA 80A/230VAC 120A/230VAC 160A/230VAC 200A/230VAC 240A/230VAC
5KVA 100A/230VAC 150A/230VAC 200A/23VAC 250A/23VAC 300A/23VAC

Note 1: Also, you can use a 40A breaker (50A for 5KVA) for only 1 unit, and each inverter has a breaker at its AC input.

Note 2: Regarding three-phase system, you can use a 4-pole breaker; the rating is up to the current of the phase which has the maximum units. Or you can follow the suggestion of note 1.

Recommended battery capacity

Inverter parallel numbers 2 3 4 5 6
Battery Capacity 400AH 600AH 800AH 1000AH 1200AH

WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.

5-1. Parallel Operation in Single phase

Two inverters in parallel:

Power Connection:

Diagram shows two inverters connected to BATTERY (red/black wires), Utility (blue/brown/dashed wires for L/N), and Load (blue/brown/dashed wires for L/N).

Communication Connection:

Diagram shows two inverters' communication ports (labeled 1 and 2) connected sequentially with green and red dotted lines.

Three inverters in parallel:

Power Connection:

Diagram shows three inverters connected to BATTERY, Utility, and Load, similar to the two-inverter setup but with an additional inverter.

Communication Connection:

Diagram shows three inverters' communication ports (labeled 1, 2, and 3) connected sequentially with green and red dotted lines.

Four inverters in parallel:

Power Connection:

Diagram shows four inverters connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows four inverters' communication ports (labeled 1, 2, 3, and 4) connected sequentially with green and red dotted lines.

Five inverters in parallel:

Power Connection:

Diagram shows five inverters connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows five inverters' communication ports (labeled 1, 2, 3, 4, and 5) connected sequentially with green and red dotted lines.

Six inverters in parallel:

Power Connection:

Diagram shows six inverters connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows six inverters' communication ports (labeled 1, 2, 3, 4, 5, and 6) connected sequentially with green and red dotted lines.

5-2. Support 3-phase equipment

Two inverters in each phase:

Power Connection:

Diagram shows three sets of inverters (P1, P2, P3 representing phases L1, L2, L3) connected to BATTERY, Utility (L1, L2, L3, N), and Load (L1, L2, L3, N).

Communication Connection:

Diagram shows communication ports of inverters across three phases connected sequentially.

Four inverters in one phase and one inverter for the other two phases:

Power Connection:

Diagram shows a configuration with four inverters on one phase (e.g., P1) and one inverter on each of the other two phases (P2, P3), connected to BATTERY, Utility (L1, L2, L3, N), and Load (L1, L2, L3, N).

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

Note: It's up to customer's demand to pick 4 inverters on any phase. P1: L1-phase, P2: L2-phase, P3: L3-phase.

Three inverters in one phase, two inverters in second phase and one inverter for the third phase:

Power Connection:

Diagram shows a three-phase configuration with three inverters on P1, two on P2, and one on P3, connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

Three inverters in one phase and only one inverter for the remaining two phases:

Power Connection:

Diagram shows a three-phase configuration with three inverters on P1, one on P2, and one on P3, connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

Two inverters in two phases and only one inverter for the remaining phase:

Power Connection:

Diagram shows a three-phase configuration with two inverters on P1, two on P2, and one on P3, connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

Two inverters in one phase and only one inverter for the remaining phases:

Power Connection:

Diagram shows a three-phase configuration with two inverters on P1, one on P2, and one on P3, connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

One inverter in each phase:

Power Connection:

Diagram shows a three-phase configuration with one inverter on P1, one on P2, and one on P3, connected to BATTERY, Utility, and Load.

Communication Connection:

Diagram shows communication ports connected across the different phase groups.

WARNING: Do not connect the current sharing cable between the inverters which are in different phases. Otherwise, it may damage the inverters.

6. PV Connection

Please refer to the user manual of a single unit for PV Connection.

CAUTION: Each inverter should connect to PV modules separately.

7. LCD Setting and Display

Setting Program:

Program Description Selectable option
28 AC output mode
*This setting is only available when the inverter is in standby mode (Switch off).
Single:
28 510 (OUTPUT)
Parallel:
28 PAL (OUTPUT)
L1 phase:
28 3P1 (OUTPUT)
L2 phase:
28 3P2 (OUTPUT)
L3 phase:
28 3P3 (OUTPUT)
30 PV judge condition
(Only apply for setting "Solar first" in program 1: Output source priority)
One Inverter (Default):
30 ONE
All of Inverters:
30 ALL

Program 28 Description:

Program 30 Description:

Fault code display:

Fault Code Fault Event Icon on
60 Power feedback protection 60
71 Firmware version inconsistent 71
72 Current sharing fault 72
80 CAN fault 80
81 Host loss 81
82 Synchronization loss 82
83 Battery voltage detected different 83
84 AC input voltage and frequency detected different 84
85 AC output current unbalance 85
86 AC output mode setting is different 86

8. Commissioning

Parallel in single phase

Step 1: Check the following requirements before commissioning:

Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each unit. And then shut down all units.

NOET: It's necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.

Step 3: Turn on each unit.

LCD display in Master unit:

Diagram shows a simplified LCD screen with 'INPUT AC 0 V' and 'OUTPUT 85, 230 V'. Icons for AC input (lightning bolt), battery (battery symbol), and load (house symbol) are shown.

LCD display in Slave unit:

Diagram shows a simplified LCD screen with 'INPUT AC 0 V' and 'OUTPUT 54, 230 V'. Icons for AC input, battery, and load are shown.

NOTE: Master and slave units are randomly defined.

Step 4: Switch on all AC breakers of Line wires in AC input. It's better to have all inverters connect to utility at the same time. If not, it will display fault 82 in following-order inverters. However, these inverters will automatically restart. If detecting AC connection, they will work normally.

Diagram shows simplified LCD screens for Master and Slave units displaying 'INPUT AC 230 V' and 'OUTPUT 85, 230 V' (Master) or 'OUTPUT 54, 230 V' (Slave), with BYPASS and CHARGING indicators.

Step 5: If there is no more fault alarm, the parallel system is completely installed.

Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.

Support three-phase equipment

Step 1: Check the following requirements before commissioning:

Step 2: Turn on all units and configure LCD program 28 as P1, P2 and P3 sequentially. And then shut down all units.

NOET: It's necessary to turn off switch when setting LCD program. Otherwise, the setting can not be programmed.

Step 3: Turn on all units sequentially.

LCD display in L1-phase unit:

Diagram shows LCD screen: 'INPUT AC 0 V', 'OUTPUT 0 P1, 230 V'.

LCD display in L2-phase unit:

Diagram shows LCD screen: 'INPUT AC 0 V', 'OUTPUT 0 P2, 230 V'.

LCD display in L3-phase unit:

Diagram shows LCD screen: 'INPUT AC 0 V', 'OUTPUT 0 P3, 230 V'.

Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work in line mode.

Diagram shows LCD screens for L1, L2, L3 phase units displaying 'INPUT AC 230 V' and 'OUTPUT 230 P1, 230 V' (or P2, P3), with BYPASS and CHARGING indicators.

Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.

Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the load.

Note 1: To avoid overload occurring, before turning on breakers in load side, it's better to have whole system in operation first.

Note 2: Transfer time for this operation exists. Power interruption may happen to critical devices, which cannot bear transfer time.

9. Trouble shooting

Fault Code Fault Event Solution
60 Current feedback into the inverter is detected. 1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the sharing are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases.
4. If the problem remains, please contact your installer.
71 The firmware version of each inverter is not the same. 1. Update all inverter firmware to the same version.
2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your installer to provide the firmware to update.
3. After updating, if the problem still remains, please contact your installer.
72 The output current of each inverter is different. 1. Check if sharing cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
80 CAN data loss 1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
81 Host data loss 1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
82 Synchronization data loss 1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, please contact your installer.
83 The battery voltage of each inverter is not the same. 1. Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, please check if all battery cables are the same length and same material type. Otherwise, please contact your installer to provide SOP to calibrate battery voltage of each inverter.
3. If the problem still remains, please contact your installer.
84 AC input voltage and frequency are detected different. 1. Check the utility wiring connection and restart the inverter.
2. Make sure utility starts up at same time. If there are breakers installed between utility and inverters, please be sure all breakers can be turned on AC input at same time.
3. If the problem remains, please contact your installer.
85 AC output current unbalance 1. Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type.
3. If the problem remains, please contact your installer.
86 AC output mode setting is different. 1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on #28. For supporting three-phase system, make sure no “PAL” is set on #28.
3. If the problem remains, please contact your installer.

PDF preview unavailable. Download the PDF instead.

PIP-HS MS Parallel Guide Microsoft Word 2013 Microsoft Word 2013

Related Documents

Preview MPP Solar 1KVA-5KVA (PF1) Inverter/Charger User Manual
User manual for MPP Solar's 1KVA-5KVA (PF1) Inverter/Charger. Covers installation, operation, safety, specifications, and troubleshooting for reliable solar power systems.
Preview PIP-LC Series Inverter Service Manual: 1.2K to 8.0KVA
Comprehensive service manual for MPP Solar PIP-LC series inverters, covering models from 1.2KVA to 8.0KVA. Includes detailed specifications, troubleshooting guides, maintenance procedures, reference data, and circuit diagrams.
Preview MPP Solar MS, LV MPPT Inverter/Charger User Manual
Comprehensive user manual for MPP Solar MS, LV MPPT Inverter/Charger models (1KVA to 5KVA), covering installation, operation, specifications, and troubleshooting.
Preview MPP Solar PIP8048MAX Solar Inverter/Charger User Manual and Installation Guide
Comprehensive user manual for the MPP Solar PIP8048MAX solar inverter and charger, covering installation, operation, specifications, troubleshooting, parallel function, and Wi-Fi monitoring.
Preview MPP Solar LVX6048 WP PV Inverter User Manual
Comprehensive user manual for the MPP Solar LVX6048 WP PV Inverter, detailing installation, operation, safety warnings, specifications, and troubleshooting for hybrid solar power systems.
Preview MPP Solar Wi-Fi Module and SolarPower App User Manual
Comprehensive user manual for the MPP Solar Wi-Fi Module and SolarPower App, detailing installation, setup, operation, monitoring, and parameter settings for hybrid inverters.
Preview PIP-GE Series 3KVA, 5KVA Inverter/Charger User Manual - MPP Solar
Comprehensive user manual for the MPP Solar PIP-GE Series 3KVA and 5KVA Inverter/Charger, covering installation, operation, specifications, and troubleshooting for this high PV input model.
Preview MPP Solar Hybrid 10KW PV Inverter User Manual: Installation and Operation Guide
Comprehensive user manual for the MPP Solar Hybrid 10KW PV Inverter, covering installation, safety warnings, operation modes, maintenance, troubleshooting, and technical specifications. Essential guide for users and installers.