MPP Solar MS, LV MPPT Inverter / Charger

User Manual

Power Factor 0.8 (for 110v/120v output & 220-240v output models)

Version: 2.3

About This Manual

Purpose

This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.

Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION -- To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. Fuses (3 pieces of 40A, 32VDC for 1KVA, 4 pieces of 40A, 32VDC for 2KVA and 6 pieces for 3KVA, 1 piece of 200A, 58VDC for 4KVA and 5KVA) are provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

Introduction

This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Features

  • Pure sine wave inverter
  • Built-in MPPT solar charge controller
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes the following devices to have a complete running system:

  • Generator or Utility.
  • PV modules (option)

Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.

Figure 1: Hybrid Power System Diagram (Text Description: A diagram showing a solar panel array connected to the inverter/charger, which is also connected to a utility/generator input and a battery bank. The inverter/charger then powers home appliances.)

Product Overview

Diagram Description: The front panel of the inverter shows an LCD display, status indicators (AC/INV, CHG, FAULT), and function keys (ESC, UP, DOWN, ENTER). Rear panel views are shown for different models (1-3KVA, 4KVA/5KVA single, 4KVA/5KVA parallel, 1K-12V 230Vac). Key components are numbered and listed: 1. LCD display, 2. Status indicator, 3. Charging indicator, 4. Fault indicator, 5. Function buttons, 6. Power on/off switch, 7. AC input, 8. AC output, 9. PV input, 10. Battery input, 11. Circuit breaker, 12. RS232 communication port, 13. Parallel communication cable (for parallel models), 14. Current sharing cable (for parallel models), 15. Dry contact, 16. USB communication port.

Installation

Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside the package:

  • The unit x 1
  • User manual x 1
  • Communication cable x 1
  • Software CD x 1

Preparation

Before connecting all wirings, please take off the bottom cover by removing two screws as shown below.

Diagram Description: Shows the bottom cover of the inverter being removed by unscrewing two screws.

Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the right diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

Diagram Description: Shows recommended clearances around the inverter for mounting: 50cm top/bottom, 20cm sides. A warning symbol ⚠️ indicates: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws. It's recommended to use M4 or M5 screws.

Diagram Description: Shows screw locations for mounting the inverter on the wall for 1KVA/3KVA/4KVA/5KVA 48V models and 2-3KVA 24V/48V Plus models.

Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

Recommended battery cable and terminal size:

Model Typical Amperage Battery Capacity Wire Size Ring Terminal Dimensions Torque Value
mm² D (mm) L (mm)
1KVA 48V 20A 100AH 1*14AWG 2 6.4 21.8 2~3 Nm
1KVA 24V, 2KVA 48V 33A 100AH 1*10AWG 5 6.4 22.5 2~3 Nm
3KVA 48V 50A 100AH 1*8AWG 8 6.4 23.8 2~3 Nm
1KVA 12V, 2KVA 24V 66A 100AH 1*6AWG 14 6.4 29.2 2~3 Nm
200AH 2*10AWG 8 6.4 23.8 2~3 Nm
3KVA 24V 100A 100AH 1*4AWG 22 6.4 33.2 2~3 Nm
200AH 2*8AWG 14 6.4 29.2 2~3 Nm
4KVA 120A 200AH 1*2AWG 38 6.4 39.2 2~3 Nm
2*6AWG 28 6.4 33.2 2~3 Nm
5KVA 120A 200AH 1*2AWG 38 6.4 39.2 2~3 Nm
2*6AWG 28 6.4 33.2 2~3 Nm

Diagram Description: Shows a ring terminal with dimensions labeled L and D.

Please follow below steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Connect all battery packs as units requires. It's suggested to connect at least 100Ah capacity battery for 1-3KVA model and at least 200Ah capacity battery for 4KVA/5KVA model.
  3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.

Diagram Description: Shows the DC input terminals on the inverter with labels PV+, PV-, POS+, NEG-. It also shows the battery connection terminals with POS+ and NEG- labels.

⚠️ WARNING: Shock Hazard

Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 10A for 1KVA, 20A for 2KVA, 32A for 3KVA, 40A for 4KVA and 50A for 5KVA.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires

Model Gauge Torque Value
1KVA 16 AWG 0.5~ 0.6 Nm
2KVA 230VAC 14 AWG 0.8~ 1.0 Nm
2KVA 120VAC 12 AWG 1.2~ 1.6 Nm
3KVA 10 AWG 1.4~ 1.6Nm
4KVA 10 AWG 1.4~ 1.6Nm
5KVA 8 AWG 1.4~ 1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor [ground symbol] first.
  4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor [ground symbol] first.

Diagram Description: Shows AC input and output terminal blocks with L, N, and PE (ground) connections. The PE connection is indicated by a ground symbol [ground symbol].

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

CAUTION: Important

Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Model Typical Amperage Cable Size Torque
1KVA 12V 40A 10 AWG 1.2~1.6 Nm
1KVA 24V / 2KVA 24V/
3KVA 24V
25A 12 AWG 1.2~1.6 Nm
1KVA 48V / 3KVA 48V 18A 14 AWG 1.2~1.6 Nm
2KVA 24V Plus
3KVA 24V Plus
2KVA 48V Plus
3KVA 48V Plus
60A 8 AWG 1.4~1.6 Nm
4KVA / 5KVA 80A 6 AWG 1.4~1.6 Nm

PV Module Selection

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.

Solar Charging Mode

INVERTER MODEL 1KVA 12V 1KVA 24V
2KVA 24V
3KVA 24V
2KVA 24V Plus
3KVA 24V Plus
1KVA 48V
3KVA 48V
2KVA 48V Plus
3KVA 48V Plus
4KVA/5KVA
Max. PV Array Open Circuit Voltage 102Vdc max 75Vdc max 102Vdc max 145Vdc 145Vdc 145Vdc
PV Array MPPT Voltage Range 15~80Vdc 30~66Vdc 60~88Vdc 30~115Vdc 60~115Vdc 60~115Vdc
Min. battery voltage for PV charge 8.5Vdc 17Vdc 34Vdc 17Vdc 34Vdc 34Vdc

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  3. Make sure the wires are securely connected.

Diagram Description: Shows PV input terminals on the inverter with POS+ and NEG- labels, and connection cables with '+' and '-' polarity markings.

Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws as shown below.

Diagram Description: Shows the back view of the inverter models (1KVA/2KVA/3KVA/4KVA/5KVA and 2KVA Plus/3KVA Plus) with the bottom cover being reattached.

Communication Connection

Please use the supplied communication cable to connect to the inverter and PC. Insert the bundled CD into a computer and follow on-screen instructions to install the monitoring software. For detailed software operation, please check the user manual of the software inside the CD.

Dry Contact Signal

There is one dry contact (3A/250VAC) available on the rear panel. When program 38 is set as "disable", it could be used to deliver a signal to an external device when the battery voltage reaches a warning level. When program 38 is set as "enable" and the unit is working in battery mode, it could be used to trigger the grounding box to connect neutral and grounding of AC output together.

When program 38 is set as "disable" (default setting):

Unit Status Condition Dry contact port: NC C NO
NC & C NO & C
Power Off Unit is off and no output is powered. Close Open
Power On Output is powered from Utility. Close Open
Output Program 01 set as Utility Open Close
Battery voltage < Low DC warning voltage
is powered from Battery or Solar. Battery voltage > Setting value in Program 13 or battery charging reaches floating stage Close Open
Program 01 set as SBU or Solar first Open Close
Battery voltage < Setting value in Program 12
Battery voltage > Setting value in Program 13 or battery charging reaches floating stage Close Open

When program 38 is set as “enable":

Unit Status Condition Dry contact port: NC C NO
NC & C NO & C
Power Off Unit is off. Close Open
Power On Output is powered from Battery or Solar Open Close

Operation

Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

Operation and Display Panel

The operation and display panel, shown in the below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Diagram Description: Shows the front panel of the inverter with the LCD display, LED indicators (AC/INV, CHG, FAULT), and function keys (ESC, UP, DOWN, ENTER).

LED Indicator LED Indicator Messages
AC/INV Green Solid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHG Green Solid On: Battery is fully charged.
Flashing: Battery is charging.
FAULT Red Solid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

LCD Display Icons

Diagram Description: Shows the LCD display with various icons and their meanings.

Icon Function description
AC Indicates the AC input.
PV Indicates the PV input.
INPUTBATT
kW VA % Hz
Indicate input voltage, input frequency, PV voltage, battery voltage, and charger current.
88 Indicates the setting programs.
Warning: 8.8 flashing with warning code.
Fault: 8.8 lighting with fault code
Indicates the warning and fault codes.
OUTPUTBATTLOAD
kW VA % Hz
Indicate output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
CHARGING Indicates battery level by 0-24%, 25-49%, 50-74%, and 75-100% in battery mode and charging status in line mode. In AC mode, it will present battery charging status.

Battery Information

Status Battery voltage LCD Display
<2V/cell 4 bars will flash in turns.
Constant Current mode / Constant Voltage mode 2 ~ 2.083V/cell Bottom bar will be on and the other three bars will flash in turns.
2.083 ~ 2.167V/cell Bottom two bars will be on and the other two bars will flash in turns.
> 2.167 V/cell Bottom three bars will be on and the top bar will flash.
Floating mode. Batteries are fully charged. 4 bars will be on.

In battery mode, it will present battery capacity.

Load Percentage Battery Voltage LCD Display
Load >50% < 1.717V/cell Diagram Description: LCD showing 1 bar.
1.717V/cell ~ 1.8V/cell Diagram Description: LCD showing 2 bars.
1.8 ~ 1.883V/cell Diagram Description: LCD showing 3 bars.
> 1.883 V/cell Diagram Description: LCD showing 4 bars.
50%> Load > 20% < 1.817V/cell Diagram Description: LCD showing 1 bar.
1.817V/cell ~ 1.9V/cell Diagram Description: LCD showing 2 bars.
1.9 ~ 1.983V/cell Diagram Description: LCD showing 3 bars.
> 1.983 Diagram Description: LCD showing 4 bars.
Load < 20% < 1.867V/cell Diagram Description: LCD showing 1 bar.
1.867V/cell ~ 1.95V/cell Diagram Description: LCD showing 2 bars.
1.95 ~ 2.033V/cell Diagram Description: LCD showing 3 bars.
> 2.033 Diagram Description: LCD showing 4 bars.

Load Information

OVER LOAD: Indicates overload.

Diagram Description: Shows load percentage icons for 0-24%, 25-49%, 50-74%, and 75-100%.

Mode Operation Information

  • Diagram Description: Shows icons indicating unit connects to the mains. Indicates unit connects to the mains.
  • Diagram Description: Shows icons indicating unit connects to the PV panel. Indicates unit connects to the PV panel.
  • Diagram Description: Shows icons indicating load is supplied by utility power. Indicates load is supplied by utility power.
  • Diagram Description: Shows icons indicating the utility charger circuit is working. Indicates the utility charger circuit is working.
  • Diagram Description: Shows icons indicating the DC/AC inverter circuit is working. Indicates the DC/AC inverter circuit is working.

Mute Operation

Diagram Description: Shows an icon indicating unit alarm is disabled. Indicates unit alarm is disabled.

LCD Setting

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Programs:

Program Description Selectable option
00 Exit setting mode Escape
01 Output source priority:
To configure load power source priority
Solar first Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power the loads at the same time. Utility provides power to the loads only when any one condition happens: Solar energy is not available, Battery voltage drops to either low-level warning voltage or the setting point in program 12.
Utility first (default) Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
SBU priority Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02 Maximum charging current:
To configure total charging current for solar and utility chargers.
(Max. charging current = utility charging current + solar charging current)
Available options in 1KVA 12V model: 10A, 20A, 30A, 40A (default), 50A, 60A
Available options in 1KVA 24V and 1KVA/3KVA 48V models: 10A, 20A (default), 30A, 40A
Available options in 2-3KVA 24V models: 20A, 30A (default), 40A, 50A, 60A
Available options in 2-3KVA 24V/48V Plus models: 10A (Not available for 2-3KVA 24V Plus), 20A, 30A, 40A, 50A, 60A (default), 70A, 80A
Available options in 4K/5K model 10A, 20A, 30A, 40A, 50A, 60A (default), 70A, 80A, 90A (Not available for 2-3KVA 48V Plus), 100A, 110A, 120A, 130A, 140A
03 AC input voltage range Appliances (default) If selected, acceptable AC input voltage range will be within 90-280VAC.
UPS If selected, acceptable AC input voltage range will be within 170-280VAC.
04 Power saving mode enable/disable Saving mode disable (default) If disabled, no matter connected load is low or high, the on/off status of inverter output will not be effected.
Saving mode enable If enabled, the output of inverter will be off when connected load is pretty low or not detected.
05 Battery type AGM (default) Flooded
User-Defined If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
06 Auto restart when overload occurs Restart disable (default) Restart enable
07 Auto restart when over temperature occurs Restart disable (default) Restart enable
08 Output voltage (only available for 110/120Vac models) 110V, 110V (default), 120V 120V (default)
09 Output frequency 50Hz (default), 60Hz 60Hz
11 Maximum utility charging current Available options in 1KVA 12V/ 24V and 2KVA 24V Plus 120Vac model: 10A, 20A(default)
Available options in 2-3KVA 24V and 2-3KVA 24V Plus models: 20A, 30A (default)
Available options in 1KVA/3KVA 48V and 2-3KVA 48V Plus models: 10A, 15A(default)
Available options in 2KVA 48V Plus 120Vac model: 5A, 10A(default)
Available options in 4KVA/5KVA models: 2A, 10A, 20A, 30A (default), 40A, 50A, 60A
12 Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01. Available options in 12V model: 11.0V, 11.3V, 11.5V (default), 11.8V, 12.0V, 12.3V
Available options in 24V models: 22.0V, 22.5V, 23.0V (default), 23.5V, 24.0V, 24.5V, 25.0V, 25.5V
Available options in 48V models: 44V, 45V, 46V (default), 47V, 48V, 49V, 50V, 51V
Below options only available for the model with 64VDC maximum charging voltage 52V, 53V, 54V (default), 55V, 56V, 57V, 58V
13 Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01. Available options in 12V model: Battery fully charged 12.0V, 12.3V, 12.5V, 12.8V, 13.0V, 13.3V, 13.5V (default), 13.8V, 14.0V, 14.3V, 14.5V
Available options in 24V models: Battery fully charged 24V, 24.5V, 25V, 25.5V, 26V, 26.5V, 27V (default)
Available options in 48V models: Battery fully charged 48V, 49V, 50V, 51V, 52V, 53V, 54V (default), 55V, 56V, 57V, 58V
Below options only available for the model with 64VDC maximum charging voltage 59V, 60V, 61V, 62V, 63V, 64V
16 Charger source priority:
To configure charger source priority
If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below:
Solar first Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
Utility first Utility will charge battery as first priority. Solar energy will charge battery only when utility power is not available.
Solar and Utility Solar energy and utility will charge battery at the same time.
Only Solar Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
18 Alarm control Alarm on (default) Alarm off
19 Auto return to default display screen Return to default display screen (default) If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.
Stay at latest screen If selected, the display screen will stay at latest screen user finally switches.
20 Backlight control Backlight on (default) Backlight off
22 Beeps while primary source is interrupted Alarm on (default) Alarm off
23 Overload bypass:
When enabled, the unit will transfer to line mode if overload occurs in battery mode.
Bypass disable (default) Bypass enable
25 Record Fault code Record enable Record disable (default)
26 Bulk charging voltage (C.V voltage) 12V model default setting: 14.1V
24V model default setting: 28.2V
48V model default setting: 56.4V
If self-defined is selected in program 5, this program can be set up. Setting range is from 12.0V to 14.6V for 12V model, 24.0V to 29.2V for 24V model and 48.0V to 58.4V for 48V model. For the model with 64V maximum charging voltage, the setting range is from 48.0V to 64.0V. Increment of each click is 0.1V.
27 Floating charging voltage 12V model default setting: 13.5V
24V model default to 27.0V
48V model default setting: 54.0V
If self-defined is selected in program 5, this program can be set up. Setting range is from 12.0V to 14.6V for 12V model, 24.0V to 29.2V for 24V model, 48.0V to 58.4V for 48V model. For the model with 64V maximum charging voltage, the setting range is from 48.0V to 64.0V. Increment of each click is 0.1V.
29 Low DC cut-off voltage 12V model default setting: 10.5V
24V model default setting: 21.0V
48V model default setting: 42.0V
If self-defined in program 5, this program can be set up. Setting range is from 10.0V to 12.0V for 12V model, 20.0V to 24.0V for 24V model, 40.0V to 48.0V for 48V model. For the model with 64V maximum charging voltage, the setting range is from 40.0V to 54.0V. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
31 Solar power balance:
When enabled, solar input power will be automatically adjusted according to connected load power. (Only available for 4KVA/5KVA model)
Solar power balance enable (Default): If selected, solar input power will be automatically adjusted according to the following formula: Max. input solar power = Max. battery charging power + Connected load power.
Solar power balance disable: If selected, the solar input power will be the same to max. battery charging power no matter how much loads are connected. The max. battery charging power will be based on the setting current in program 02. (Max. solar power = Max. battery charging power)
32 Bulk charging time
(C.V stage)
(Only available for 4KVA/5KVA model)
Automatically (Default): If selected, inverter will judge this charging time automatically. The setting range is from 5 min to 900 min. Increment of each click is 5 min.
5 min 900 min
38 Allow neutral and grounding of AC output is connected together:
When enabled, inverter can deliver signal to trigger grounding box to short neutral and grounding
Disable: Neutral and grounding of AC output is disconnected. (Default) This function is only available when the inverter is working with external grounding box. Only when the inverter is working in battery mode, it will trigger grounding box to connect neutral and grounding of AC output.
Enable: Neutral and grounding of AC output is connected.

Display Setting

The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, main CPU Version and second CPU Version.

Selectable information LCD display
Input voltage/Output voltage
(Default Display Screen)
Diagram Description: LCD showing Input Voltage=230V, Output Voltage=230V, with AC/INV, CHG, FAULT indicators and load percentage.
Input frequency Diagram Description: LCD showing Input frequency=50Hz, Output Voltage=230V, with indicators and load percentage.
PV voltage Diagram Description: LCD showing PV voltage=60V, Output Voltage=230V, with indicators and load percentage.
MPPT Charging current Diagram Description: LCD showing Current >= 10A, Battery Voltage=25.5V, Output Voltage=230V, with indicators and load percentage.
Diagram Description: LCD showing Current < 10A, Battery Voltage=25.5V, Output Voltage=230V, with indicators and load percentage.
MPPT Charging power Diagram Description: LCD showing MPPT charging power=500W, Output Voltage=230V, with indicators and load percentage.
Battery voltage/ DC discharging current Diagram Description: LCD showing Battery Voltage=25.5V, Discharging Current=1A, with indicators and load percentage.
Output frequency Diagram Description: LCD showing Output frequency=50Hz, Battery Voltage=25.5V, with indicators and load percentage.
Load percentage Diagram Description: LCD showing Load percent=70%, Battery Voltage=25.5V, with indicators and load percentage.
Load in VA Diagram Description: LCD showing Load in VA for connected load lower than 1kVA (e.g., 350VA), Battery Voltage=25.5V, with indicators and load percentage.
Diagram Description: LCD showing Load in VA for connected load larger than 1kVA (e.g., 1.50kVA), Battery Voltage=25.5V, with indicators and load percentage.
Load in Watt Diagram Description: LCD showing Load in Watt for connected load lower than 1kW (e.g., 270W), Battery Voltage=230V, with indicators and load percentage.
Diagram Description: LCD showing Load in Watt for connected load larger than 1kW (e.g., 1.20kW), Battery Voltage=230V, with indicators and load percentage.
Main CPU version checking Diagram Description: LCD showing Main CPU version 00014.04.
Secondary CPU version checking Diagram Description: LCD showing Secondary CPU version 00003.03.

Operating Mode Description

Operation mode Description LCD display
Standby mode / Power saving mode
Note:
*Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output.
*Power saving mode: If enabled, the output of inverter will be off when connected load is pretty low or not detected.
No output is supplied by the unit but it still can charge batteries. Diagram Description: LCD showing Charging by utility and PV energy.
Diagram Description: LCD showing Charging by utility.
Diagram Description: LCD showing Charging by PV energy.
Diagram Description: LCD showing No charging.
Fault mode
Note:
*Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on.
PV energy and utility can charge batteries. Diagram Description: LCD showing Charging by utility and PV energy.
Diagram Description: LCD showing Charging by utility. (Only available in 1K/2K/3K model)
Diagram Description: LCD showing Charging by PV energy.
Diagram Description: LCD showing No charging.
Line Mode The unit will provide output power from the mains. It will also charge the battery at line mode. Diagram Description: LCD showing Charging by PV energy.
Diagram Description: LCD showing Charging by utility.
Battery Mode The unit will provide output power from battery and PV power. Diagram Description: LCD showing Power from battery and PV energy.
Diagram Description: LCD showing Power from battery only.

Fault Reference Code

Fault Code Fault Event Icon on
01 Fan is locked when inverter is off. Diagram Description: Icon showing 'ERROR' with '01'.
02 Over temperature Diagram Description: Icon showing 'ERROR' with '02'.
03 Battery voltage is too high Diagram Description: Icon showing 'ERROR' with '03'.
04 Battery voltage is too low Diagram Description: Icon showing 'ERROR' with '04'.
05 Output short circuited or over temperature is detected by internal converter components. Diagram Description: Icon showing 'ERROR' with '05'.
06 Output voltage is abnormal. (For 1K/2K/3K model)
Output voltage is too high. (For 4K/5K model)
Diagram Description: Icon showing 'ERROR' with '06'.
07 Overload time out Diagram Description: Icon showing 'ERROR' with '07'.
08 Bus voltage is too high Diagram Description: Icon showing 'ERROR' with '08'.
09 Bus soft start failed Diagram Description: Icon showing 'ERROR' with '09'.
11 Main relay failed Diagram Description: Icon showing 'ERROR' with '11'.
51 Over current or surge Diagram Description: Icon showing 'ERROR' with '51'.
52 Bus voltage is too low Diagram Description: Icon showing 'ERROR' with '52'.
53 Inverter soft start failed Diagram Description: Icon showing 'ERROR' with '53'.
55 Over DC voltage in AC output Diagram Description: Icon showing 'ERROR' with '55'.
56 Battery connection is open Diagram Description: Icon showing 'ERROR' with '56'.
57 Current sensor failed Diagram Description: Icon showing 'ERROR' with '57'.
58 Output voltage is too low Diagram Description: Icon showing 'ERROR' with '58'.

NOTE: Fault codes 51, 52, 53, 55, 56, 57 and 58 are only available in 4K/5K model.

Warning Indicator

Warning Code Warning Event Audible Alarm Icon flashing
01 Fan is locked when inverter is on. Beep three times every second Diagram Description: Icon showing '01' with a fan symbol.
03 Battery is over-charged Beep once every second Diagram Description: Icon showing '03' with a battery symbol.
04 Low battery Beep once every second Diagram Description: Icon showing '04' with a battery symbol and '25%'.
07 Overload Beep once every 0.5 second Diagram Description: Icon showing 'OVER LOAD' with '07'.
10 Output power derating Beep twice every 3 seconds Diagram Description: Icon showing '10' with a power symbol.
12 Solar charger stops due to low battery. Diagram Description: Icon showing '12' with a solar panel and battery symbol.
13 Solar charger stops due to high PV voltage. Diagram Description: Icon showing '13' with a solar panel symbol and voltage warning.
14 Solar charger stops due to overload. Diagram Description: Icon showing '14' with a solar panel symbol and overload warning.

Equalization (Only available for 4KVA/5KVA model)

Equalization function is for refreshed battery capacity. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Equalization

Users can equalize battery manually. Please follow below steps to set up battery equalization.

  1. After pressing and holding ENTER button for 3 seconds, LCD will go to setting page.
  2. Select program 01 and set it as "UTI". The output priority will be utility first.
  3. Select program 02 and set the equalization charging current you need for battery. Below screen is to set up equalization current as 60A.
  4. Select program 05 and set it as "USE". It's use-defined battery type.
  5. Select program 16 and set it as "SNU". Charging priority will be solar and utility together.
  6. Select program 26 and set the bulk charging current you need for battery. It will be max. charging voltage for equalization. Below screen is to set up max. charging voltage as 56.4V.
  7. Select program 32 and set the charging time for C.V stage. It will be charging time for battery equalization. Below screen is to set up charging time as 900 min.

After following above steps, PV power and utility will charge battery at setting max. charging voltage in program 26 and keep charging for the period of setting in program 32 (equalization charging time). After that, battery will be in floating charging stage. Once the CHG LED lights on, it means battery is fully charged and one equalization cycle is complete. At this time, please be sure to restore above settings to previous setting for normal operation.

Specifications

Table 1 Line Mode Specifications

INVERTER MODEL 1KVA 12V 1KVA 24V
2KVA 24V
3KVA 24V
2KVA 24V Plus
3KVA 24V Plus
1KVA 48V
3KVA 48V
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 110/120Vac or 230Vac
Low Loss Voltage 95Vac±7V or 170Vac±7V (UPS)
65Vac±7V or 90Vac±7V (Appliances)
Low Loss Return Voltage 100Vac±7V or 180Vac±7V (UPS);
70Vac±7V or 100Vac±7V (Appliances)
High Loss Voltage 140Vac±7V or 280Vac±7V
High Loss Return Voltage 135Vac±7V or 270Vac±7V
Max AC Input Voltage 150Vac or 300Vac
Nominal Input Frequency 50Hz / 60Hz (Auto detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit Protection Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode) >95% (Rated R load, battery full charged )
Transfer Time 10ms typical (UPS);
20ms typical (Appliances)
Output Power Diagram Description: Graph showing Output Power vs Input Voltage for 110/120Vac models and 230Vac models, illustrating derating.
Output power derating:
When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.

Table 2 Inverter Mode Specifications

INVERTER MODEL 1KVA 12V 1KVA 24V
2KVA 24V
3KVA 24V
1KVA 48V
3KVA 48V
2KVA 24V Plus
3KVA 24V Plus
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Rated Output Power 1KVA/0.8KW 1KVA/0.8KW
2KVA/1.6KW
3KVA/2.4KW
1KVA/1KW
3KVA/2.4KW
2KVA/1.6KW
3KVA/2.4KW
2KVA/1.6KW
3KVA/2.4KW
4KVA/3.2KW
5KVA/4KW
Output Voltage Waveform Pure Sine Wave
Output Voltage Regulation 110/120VAC±5%* or 230Vac±5%
Output Frequency 60Hz or 50Hz
Peak Efficiency 90%
Overload Protection 5s@≥150% load; 10s@110%~150% load
Surge Capacity 2* rated power for 5 seconds
Nominal DC Input Voltage 12Vdc 24Vdc 48Vdc 24Vdc 48Vdc 48Vdc
Cold Start Voltage 11.5Vdc 23.0Vdc 46.0Vdc 23.0Vdc 46.0Vdc 46.0Vdc
Low DC Warning Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
11.0Vdc
10.7Vdc
10.1Vdc
22.0Vdc
21.4Vdc
20.2Vdc
44.0Vdc
42.8Vdc
40.4Vdc
22.0Vdc
21.4Vdc
20.2Vdc
44.0Vdc
42.8Vdc
40.4Vdc
44.0Vdc
42.8Vdc
40.4Vdc
Low DC Warning Return Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
11.5Vdc
11.2Vdc
10.6Vdc
23.0Vdc
22.4Vdc
21.2Vdc
46.0Vdc
44.8Vdc
42.4Vdc
23.0Vdc
22.4Vdc
21.2Vdc
46.0Vdc
44.8Vdc
42.4Vdc
46.0Vdc
44.8Vdc
42.4Vdc
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
10.5Vdc
10.2Vdc
9.6Vdc
21.0Vdc
20.4Vdc
19.2Vdc
42.0Vdc
40.8Vdc
38.4Vdc
21.0Vdc
20.4Vdc
19.2Vdc
42.0Vdc
40.8Vdc
38.4Vdc
42.0Vdc
40.8Vdc
38.4Vdc
High DC Recovery Voltage 14.5Vdc 29Vdc 58Vdc 29Vdc 58Vdc 58Vdc or 62Vdc
High DC Cut-off Voltage 15.5Vdc 31Vdc 62Vdc 31Vdc 62Vdc 60Vdc or 66Vdc
No Load Power Consumption <15W <25W <50W <25W <50W <50W
Saving Mode Power Consumption <5W <10W <15W <10W <15W <15W

*4KVA/5KVA only supports 230VAC system.

Table 3 Charge Mode Specifications

Utility Charging Mode

INVERTER MODEL 1KVA 12V 1KVA 24V
2KVA 24V
3KVA 24V
2KVA 24V Plus
3KVA 24V Plus
120Vac
1KVA 48V
3KVA 48V
2KVA 48V Plus
120Vac
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Charging Current (UPS)
@ Nominal Input Voltage
10/20A 20/30A 5/10A 10/15A 20/30A 2/10A/
20/30A/
40/50/60A
Bulk
Charging
Voltage
Flooded Battery
14.6
29.2 58.4 29.2 58.4 58.4
AGM / Gel
Battery
14.1
28.2 56.4 28.2 56.4 56.4 or 64Vdc
Floating Charging Voltage 13.5Vdc 27Vdc 54Vdc 27Vdc 54Vdc 54Vdc or 64Vdc
Overcharge Protection 15.5Vdvc 31Vdc 60Vdc 31Vdc 60Vdc 60Vdc or 66Vdc
Charging Algorithm 3-Step
Diagram Description: Charging Curve graph showing Battery Voltage vs Time, and Charging Current vs Time. It illustrates Bulk, Absorption, and Maintenance (Floating) stages.

Solar Charging Mode

INVERTER MODEL 1KVA 12V 1KVA 24V
2KVA 24V
3KVA 24V
2KVA 24V Plus
3KVA 24V Plus
1KVA 48V
3KVA 48V
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Rated Power 500W 600W 900W 1500W 3000W 4000W
Efficiency 98.0% max.
Max. PV Array Open Circuit Voltage 102Vdc 75Vdc 102Vdc 145Vdc 145Vdc 145Vdc
PV Array MPPT Voltage Range 15~80Vdc 30~66Vdc 60~88Vdc 30~115Vdc 60~115Vdc 60~115Vdc
Min battery voltage for PV charge 8.5Vdc 17Vdc 34Vdc 17Vdc 34Vdc 34Vdc
Standby Power Consumption 2W
Battery Voltage Accuracy +/-0.3%
PV Voltage Accuracy +/-2V
Charging Algorithm 3-Step
Joint Utility and Solar Charging
Max Charging Current 60Amp 1K: 45Amp
2K/3K: 55Amp
33Amp 90Amp 75Amp 140Amp
Default Charging Current 40Amp 1K: 20Amp
2K/3K: 30Amp
20Amp 60 Amp 60 Amp 60Amp

Table 4 General Specifications

INVERTER MODEL 1KVA 12V
230Vac
1KVA 12V
110Vac
1KVA 24V
1KVA 48V
2KVA 24V
3KVA 24V
3KVA 48V
2KVA 24V Plus
3KVA 24V Plus
2KVA 48V Plus
3KVA 48V Plus
4KVA
5KVA
Safety Certification CE
Operating Temperature Range 0°C to 55°C
Storage temperature -15°C~ 60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm 95 x 240 x 316 100 x 272 x 355 140 x 295 x 479 120 x 295 x 468 140 x 295 x 479 120 x 295 x 468
Net Weight, kg 5.2 6.8 7.0 7.4 11.5 11

Trouble Shooting

Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Mains exist but the unit works in battery mode. Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
When the unit is turned on, internal relay is switched on and off repeatedly. Green LED is flashing. Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance)
Green LED is flashing. Set "Solar First" as the priority of output source. Change output source priority to Utility first.
LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Temperature of internal converter component is over 120°C. (Only available for 1-3KVA models.) Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03 Internal temperature of inverter component is over 100°C. Return to repair center.
Fault code 01 Battery is over-charged. Check if spec and quantity of batteries are meet requirements.
Fault code 06/58 The battery voltage is too high. Replace the fan.
Fault code 08/09/53/57 Fan fault 1. Reduce the connected load.
2. Return to repair center
Fault code 51 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) Return to repair center.
Fault code 52 Internal components failed. Restart the unit, if the error happens again, please return to repair center.
Fault code 55 Over current or surge.
Fault code 56 Bus voltage is too low.
Fault code 57 Output voltage is unbalanced.
Fault code 58 Battery is not connected well or fuse is burnt. If the battery is connected well, please return to repair center.

Appendix: Approximate Back-up Time Table

1KVA

Load (VA) Backup Time @ 12Vdc 100Ah (min) Backup Time @ 12Vdc 200Ah (min)
1007661610
200335766
300198503
400139339
500112269
60095227
70081176
80062140
90055125
100050112

1KVA / 2KVA / 3KVA

Load (VA) Backup Time @24Vdc 100Ah (min) Backup Time @24Vdc 200Ah (min)
2007661610
400335766
600198503
800139339
1000112269
2007661610
400335766
600198503
800139339
1000112269
120095227
140081176
160062140
180055125
200050112
3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
30002867

1KVA / 2KVA / 3KVA / 4KVA

Load (VA) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
10025295058
20012642529
3008431686
4006081279
5004821035
600406872
700310710
800268615
900231540
1000186471
20015813161
4007511581
6004911054
800331760
1000268615
1200221508
1400172387
1600136335
1800120295
2000106257
30010542107
6004911054
900291668
1200196497
1500159402
1800123301
2100105253
240091219
270071174
300063155
4007661610
800335766
1200198503
1600139339
2000112269
240095227
280081176
320062140
360055125
400050112

5KVA

Load (VA) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
5006131288
1000268613
1500158402
2000111271
250090215
300076182
350065141
400050112
450044100
50004090

Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.

PDF preview unavailable. Download the PDF instead.

PIP-MS LV PF0.8 1-5KVA manual 20170804 Microsoft Word 2013 Microsoft Word 2013

Related Documents

Preview MPP Solar 1KVA-5KVA (PF1) Inverter/Charger User Manual
User manual for MPP Solar's 1KVA-5KVA (PF1) Inverter/Charger. Covers installation, operation, safety, specifications, and troubleshooting for reliable solar power systems.
Preview MPP Solar 3KVA Inverter/Charger User Manual
This user manual provides comprehensive instructions for the MPP Solar 3KVA Inverter/Charger, covering installation, operation, specifications, and troubleshooting for reliable power solutions.
Preview PIP-LC Series Inverter Service Manual: 1.2K to 8.0KVA
Comprehensive service manual for MPP Solar PIP-LC series inverters, covering models from 1.2KVA to 8.0KVA. Includes detailed specifications, troubleshooting guides, maintenance procedures, reference data, and circuit diagrams.
Preview PIP-GE Series 3KVA, 5KVA Inverter/Charger User Manual - MPP Solar
Comprehensive user manual for the MPP Solar PIP-GE Series 3KVA and 5KVA Inverter/Charger, covering installation, operation, specifications, and troubleshooting for this high PV input model.
Preview MPP Solar Hybrid 10KW PV Inverter User Manual: Installation and Operation Guide
Comprehensive user manual for the MPP Solar Hybrid 10KW PV Inverter, covering installation, safety warnings, operation modes, maintenance, troubleshooting, and technical specifications. Essential guide for users and installers.
Preview MPP Solar 1.5KW/3KW/5KW User Manual: Installation, Operation, and Safety Guide
This user manual provides comprehensive instructions for MPP Solar's 1.5KW, 3KW, and 5KW solar inverter/chargers. It covers installation, operation, key features, system integration, safety precautions, and troubleshooting for efficient solar power management.
Preview MPP Solar PIP3624MAX/PIP7248MAX Solar Inverter/Charger User Manual
Comprehensive user manual for MPP Solar PIP3624MAX and PIP7248MAX solar inverter/charger units, detailing installation, operation, specifications, and troubleshooting for reliable solar energy systems.
Preview MPP Solar Hybrid 4KW PV Inverter User Manual
User manual for the MPP Solar Hybrid 4KW PV Inverter (Version 1.2). Covers installation, safety, operation, specifications, and troubleshooting for solar power systems.