Sungrow Smart Energy Meter Application Guide

The Sungrow Smart Meter presents a clear overview of energy consumption in combination with Sungrow iSolarCloud. The Sungrow Smart Meter is ideally suited for use with the Sungrow single-phase inverter and three-phase string inverters.

Note: The measurement range (primary current) of the current transformer should be selected according to actual maximum current at the grid-connected point, and the maximum secondary current of the current transformer should be 5A. The CTs shown as below are only suggestions for customer.

TypeInverter type of applicationCT requirement
S100SG2/2.5/3K-S, SG3/5/8K-D, SH5K-20, SH5K-30No, S100 itself owns CT.
DTSD1352-C/10(80)A
(only used for the phase current≤80A)
SG2/2.5/3K-S, SG3/5/8K-D, SH5K-20, SH5K-30, SG5/10KTL-MT, SG15/20KTL-MNo, this meter integrated CT inside.
DTSD1352-C/1(6)A
(only used for the phase current>80A)
SG5/10KTL-MT, SG15/20KTL-MYes, CT's with 5A secondary current output. Sungrow meters are compatible with CTs as below:
  • IPD CTME-3 Series for Single Turn Primary
  • a. 150A: CTME3150
  • b. 200A: CTME3200
  • c. 300A: CTME3300
  • d. 400A: CTME3400
  • e. 500A: CTME3500
  • SOCOMEC TCA 21/TCA14 SERIES
  • a. 75A: TCA21-75/5
  • b. 80A: TCA21-80/5
  • c. 100A: TCA21-100/5
  • d. 125A: TCA21-125/5
  • e. 150A: TCA21-150/5
  • f. 200A: TCA21-200/5
  • SOCOMEC TCB 18 - 20 SERIES
  • a. 100A: 192T3310
  • b. 150A: 192T3315
  • c. 200A: 192T3320
  • d. 250A: 192T3325

S100 Single-phase Smart Energy Meter

Electrical ParameterValue
Type designationS100
Nominal voltage240 Vac
Input voltage range180 Vac - 286 Vac
Power consumption<2W (10 VA)
Max. operating current100 A
Grid frequency50 Hz
Measurement accuracyClass 1
Interface and communicationRS485

Environmental Condition

Ingress protection ratingIP20
Operating ambient temperature-25 to 75 °C
Relative humidity0 - 95 %

Mechanical Data

Dimensions (W * H * D)18 * 117 * 65 mm
Weight0.2 kg
Installation35 mm DIN-rail

DTSD1352-C/10 (80)A Three-phase Smart Energy Meter

Electrical ParameterValue
Type designationDTD1352-C/10 (80)A
Nominal voltage230 Vac / 400 Vac
Input voltage range57.7 Vac - 268 Vac
Power consumption<2W (10 VA)
Max. operating current80 A
Grid frequency50 Hz / 60 Hz
Measurement accuracyClass 0.5 (Active)
Interface and communicationRS485

Environmental Condition

Ingress protection ratingIP20
Operating ambient temperature-25 to 55 °C
Relative humidity0 - 95 %

Mechanical Data

Dimensions (W * H * D)126 * 91 * 74 mm
Weight0.35 kg
Installation35 mm DIN-rail

DTSD1352-C/1 (6)A* Three-phase Smart Energy Meter

Electrical ParameterValue
Type designationDTSD1352
Nominal voltage230 Vac / 400 Vac
Input voltage range57.7 Vac - 268 Vac
Power consumption<2W (10 VA)
Max. operating current3×1 (6) A (via CTs)
Grid frequency50 Hz / 60 Hz
Measurement accuracyClass 0.5 (Active)
Interface and communicationRS485

Environmental Condition

Ingress protection ratingIP20
Operating ambient temperature-25 to 55 °C
Relative humidity0 - 95 %

Mechanical Data

Dimensions (W * H * D)126 * 91 * 74 mm
Weight0.35 kg
Installation35 mm DIN-rail

* DTSD1352-C/1 (6)A needs to be used with CT externally.

PDF preview unavailable. Download the PDF instead.

20200108 Sungrow Smart Energy Meter Application Guide Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)

Related Documents

Preview Sungrow Energy Meter Selection Guide: Choose the Right Meter for Your Solar System
A comprehensive guide to selecting the appropriate Sungrow Energy Meter, detailing compatibility with single-phase and three-phase inverters, CT requirements, and technical specifications for models S100, T65, DTSU666, and DTSD1352-C/1(6)A.
Preview DTSD1352-C Three-phase Energy Meter Quick Installation Guide
A quick installation guide for the DTSD1352-C three-phase energy meter, detailing its applicability, target group, intended use, technical data, delivery contents, and installation steps.
Preview Sungrow EyeM4 (WiFi) Commissioning Quick Guide for SG30/50/110CX Inverters
This quick guide provides instructions for installers on commissioning Sungrow EyeM4 (WiFi) dongles with SG30/50/110CX solar inverters, covering RS485 connections, energy meter integration, and iSolarCloud setup.
Preview Sungrow Commercial PV Plant System Solutions: Inverters and Monitoring
Explore Sungrow's comprehensive system solutions for commercial photovoltaic (PV) plants, featuring advanced inverters, communication modules, and monitoring platforms designed for high yield, reliability, and efficient O&M.
Preview Sungrow Energy Meter Selection Guide | DTSU666, DTSD1352-C/1(6)A
Comprehensive selection guide for Sungrow Energy Meters, including models DTSU666 and DTSD1352-C/1(6)A, detailing inverter compatibility and CT requirements for solar energy systems.
Preview Sungrow SG30/50/110CX Inverters Commissioning Quick Guide with Logger1000 and EyeM4
This guide provides step-by-step instructions for commissioning Sungrow SG30/50/110CX three-phase inverters. It covers RS485 connections, energy meter integration (DTSD1352, DTSU666), Logger1000 and EyeM4 setup, web portal access, internet connectivity (Ethernet, WiFi, 4G), remote control configuration, export control, and iSolarCloud plant creation and firmware updates.
Preview Sungrow Logger1000 Commissioning Quick Guide for SG30/50/110CX Inverters
A quick guide for commissioning Sungrow Logger1000 with SG30/50/110CX inverters, covering RS485 connections, energy meter setup, web portal configuration, and online monitoring.
Preview Sungrow EyeM4 (WiFi) Commissioning Quick Guide for SG30/50/110CX Inverters
A quick guide for commissioning Sungrow EyeM4 (WiFi) dongles with SG30/50/110CX inverters, covering RS485 connections, energy meter setup, web portal configuration, and online monitoring via iSolarCloud.