EMM 3- 24DC/500AC-IFS - Motor Management

Item Number: 2297497

Manufacturer: Phoenix Contact

Product URL: https://www.phoenixcontact.com/gb/products/2297497

Product Overview

Electronic motor management for operation with external current transformers. Features active power measurement for overload and underload monitoring of motors and systems, providing optimum protection for all performance classes. Offers freely parameterizable switching and signaling thresholds.

Your Advantages

Commercial Data

Item number 2297497
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key DK7512
Product key DK7512
GTIN 4046356175753
Weight per piece (including packing) 263 g
Weight per piece (excluding packing) 263 g
Customs tariff number 85371098
Country of origin DE

Technical Data

Notes

Utilization restriction: EMC: class A product, see manufacturer's declaration in the download area.

Product properties

Product type Electronic motor manager
Product family CONTACTRON
Operating mode 100% operating factor

Electrical properties

Number of phases 3
Maximum power dissipation for nominal condition 2.5 W
Test voltage input/output 8 kV

Supply

Rated control circuit supply voltage US 24 V DC
Control supply voltage range 19.2 V DC ... 30 V DC
Rated control supply current IS 25 mA
Switching threshold 9.6 V DC ("0" signal)
19.2 V DC ("1" signal)

Insulation characteristics

Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the input and output circuits Safe isolation (IEC 60947-1)
Insulation characteristics between the thermistor input and output Basic insulation (IEC 60947-1)

Input data

Digital inputs

Number of inputs 4 (IN1 - IN4)
Rated actuating voltage UC 24 V DC
Rated actuating current IC 3.3 mA

Voltage measuring input V1, V2, V3

Input voltage range 42 V AC ... 575 V AC
Typical input current at UN < 0.5 mA

Current measuring input L1/T1, L2/T2, L3/T3

Typical input current at UN 5 A (Secondary external converter)

Power measurement

Basic accuracy typ. 2%
Power range 4.5 kW (x amplitude transmission factor for current transformer)

Voltage measurement/star voltage

Basic accuracy typ. 0.75%
Voltage range 0 V AC ... 350 V AC (Phase-to-neutral voltage)

Current measurement

Basic accuracy typ. 0.5%
Current range 140 mA ... 5 A
Measuring via External push-through current transformers connected upstream

Output data

Output name Acknowledging contacts O1-O4
Note The meaning of the acknowledgement outputs can be freely parameterized, see user manual.
Number of outputs 4
Nominal output voltage 24 V DC (semiconductor output)
Output voltage range 19.2 V DC ... 30 V DC
Continuous load current 500 mA
Residual voltage < 200 mV
Protective circuit Suppressor diode
Surge voltage protection > 33 V DC

Connection Data

Control circuits

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Load circuit

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14

Signaling

Status display LED (yellow)
Operating voltage display Green LED
Error indication Red LED
Data communication display green LED

Dimensions

Width 22.5 mm
Height 99 mm
Depth 114.5 mm

Material Specifications

Color gray (RAL 7042)

Environmental and Real-Life Conditions

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C

Approvals

ATEX

Identification II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
Certificate PTB 10 ATEX 3024

UL, USA/Canada

Certificate NKCR.E140324

Safety Integrity Level (SIL, IEC 61508)

Identification ≤ 1
Note Safe shutdown

Safety Integrity Level (SIL, IEC 61508)

Identification 1
Note Motor protection

Category (ISO 13849)

Identification ≤ 1
Note Safe shutdown

Performance Level

Identification ≤ b
Note Safe shutdown

Standards and Regulations

Standards/regulations EN 60947
EN 60947-4-2

Mounting

Mounting type DIN rail mounting
Assembly note in rows with zero spacing
Mounting position Vertical (horizontal DIN rail)

Drawings

Connection diagram

A connection diagram illustrates the wiring for the EMM 3-24DC/500AC-IFS module. It shows connections for power supply, digital inputs (IN1-IN4), digital outputs (O1-O4), thermistor input (Th1, Th2), and current measurement inputs (I/L1, I/L2, I/L3 and T1/L1, T2/L2, T3/L3). It also indicates connections for external switching modules and a motor (M).

Diagrams illustrating operational status

Several diagrams illustrate the device's performance monitoring capabilities:

Block diagram

A block diagram shows the internal components and connections of the EMM 3-24DC/500AC-IFS. It includes the logic microcontroller (μP), digital inputs, digital outputs, IFS-Port, Reset button, Thermistor input, T-BUS connection, and various input/output terminals (Us, IN1-IN4, O1-O4, US0, V1-V3, I1, I21, I31, I12, I22, I32, Th1, Th2).

Classifications

ECLASS ECLASS-13.0 27370804
ETIM ETIM 9.0 EC002572
UNSPSC UNSPSC 21.0 39121100

Environmental Product Compliance

EU RoHS Fulfills EU RoHS substance requirements Yes
Exemption 7(a), 7(c)-1, 7(c)-II
China RoHS Environment friendly use period (EFUP) EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1)
SCIP 141e0f24-6c49-48b6-a9f1-f1b2bd215171
Models: 2297497, EMM 3-24DC Electronic Motor Management, EMM 3-24DC, Electronic Motor Management, Motor Management

File Info : application/pdf, 13 Pages, 649.09KB

PDF preview unavailable. Download the PDF instead.

phoenix-contact-2297497-en

References

iText Core 8.0.5 (production version), pdfHTML 5.0.5 (production version) ©2000-2024 Apryse Group NV,

Related Documents

Preview Phoenix Contact EMM 3- 24DC/500AC-16-IFS Motor Management
Technical specifications and features of the Phoenix Contact EMM 3- 24DC/500AC-16-IFS electronic motor management device, including electrical properties, connection data, dimensions, and approvals.
Preview PTCB E1 24DC/0.63A SI-R: Electronic Device Protection
Phoenix Contact PTCB E1 24DC/0.63A SI-R is a single-channel electronic device protector for 12-24 V DC loads. Features fixed nominal current of 0.63 A, remote signaling, remote reset, and active current limitation. Designed for DIN rail mounting and compatible with CLIPLINE terminal blocks.
Preview Phoenix Contact RAD-2400-IFS Wireless Module CCC Certificate
This document contains the China Compulsory Certification (CCC) for the Phoenix Contact RAD-2400-IFS wireless module. It details the product's electrical parameters, safety certifications, and usage conditions, including its explosion-proof rating.
Preview Phoenix Contact Relay Modules: Comprehensive Product Overview
Explore Phoenix Contact's extensive range of relay modules, including industrial, compact, time, and monitoring relays. Discover solutions for automation, signal switching, isolation, and amplification, featuring Push-in Technology and various application-specific variants.
Preview Phoenix Contact Electronics Housings: Optimized Cooling Solutions
Discover Phoenix Contact's advanced electronics housings designed for optimized cooling, ensuring efficient power management and reliable performance for electronic components.
Preview Phoenix Contact FBI 3-20 Vaste Brug - Productgegevens en Specificaties
Gedetailleerde productinformatie voor de Phoenix Contact FBI 3-20 vaste brug (Artikelnummer 0201317), inclusief commerciële gegevens, technische specificaties en contactinformatie.
Preview Phoenix Contact HC-BB18-I-PT-M Contact Insert - Technical Specifications and Features
Detailed technical specifications, features, and compliance information for the Phoenix Contact HC-BB18-I-PT-M contact insert, including its advantages, dimensions, electrical and mechanical properties, and approvals.
Preview Phoenix Contact Product Discontinuation Notification: VARIOCON Item Selection
Notification regarding the discontinuation of the VARIOCON item selection by Phoenix Contact, including affected article categories, change details, and a comprehensive material list with discontinuation dates.