Hilti Technical Bulletin

Date: February 28, 2018

Subject: KWIK HUS-EZ 3/8 X 2-1/8 I 1/2

Hilti has introduced a new version of the KWIK HUS-EZ I anchor. The KWIK HUS-EZ 3/8"X2 1½" I 1½" anchor is a 3/8-in. diameter screw anchor with an internally threaded head for attachment of 1/2-in. diameter threaded rods. The tables below provide installation parameters and design load data in Normal Weight Concrete and Lightweight Concrete Over Metal Deck. The anchor is also approved by Factory Mutual for sprinkler pipe up to 8-in. in diameter. This product will be included in the next revision of ESR-3027.

The design tables in Tables 2 to 6 are Hilti Simplified Design Tables. The load values were developed using the design parameters and variables that are expected to be included in ESR-3027 and the equations of ACI 318-14 Chapter 17. For a detailed explanation of the Hilti Simplified Design Tables, refer to section 3.1.8 of Hilti Product Technical Guide Vol. 2 Ed. 17. Tables 7 to 11 are based on Canadian Limit State Design. Table 12 contains allowable loads for installations in Hollow Core Concrete Panels.

[Diagram of KWIK HUS-EZ anchor with wrench size, d_nom, f_nom, d_bit, h_nom, h_ef]

Figure 1 – KWIK HUS-EZ 3/8" X 2 1/8" I ½"

[Diagram illustrating KWIK HUS-EZ anchor installation details, showing d_nom, f_nom, h_nom, h_ef]

Figure 2 – KWIK HUS-EZ anchor installation details

Table 1 – KWIK HUS EZ I installation specifications

Setting information Symbol Units Nominal anchor diameter
Nominal bit diameter dbit in. 3/8
Nominal embedment hnom in. 2-1/8
Effective embedment hef in. 1.54
Minimum hole depth ho in. 2-3/8
Minimum Base Material Thickness hmin in. 3-5/8
Installation torque Tinst ft.-lb. 40
Wrench size in. 11/16
Hilti impact setting tools SID 4-A22/18-A and SIW 22/18-A
Insert diameter in. 1/2

Table 2 - Hilti KWIK HUS-EZ I design strength with concrete / pullout failure in uncracked concrete

Nominal anchor diameter in. Nominal embed. depth in. (mm) Tension - Nn Shear - Vn
f'c = 2500 psi (17.2 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 6000 psi (41.4MPa) lb (kN) f'c = 2500 psi (17.2MPa) lb (kN) f'c = 3000 psi (20.7MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 6000 psi (41.4 MPa) lb (kN)
3/8 2-1/8 (54) 1,490 (6.6) 1,630 (7.3) 1,885 (8.4) 2,305 (10.3) 1,605 (7.1) 1,755 (7.8) 2,030 (9.0) 2,485 (11.1)

Table 3 - Hilti KWIK HUS-EZ I design strength with concrete / pullout failure in cracked concrete

Nominal anchor diameter in. Nominal embed. depth in. (mm) Tension - Nn Shear - Vn
f'c = 2500 psi (17.2 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 6000 psi (41.4MPa) lb (kN) f'c = 2500 psi (17.2 MPa) lb (kN) f'c = 3000 psi (20.7MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 6000 psi (41.4 MPa) lb (kN)
3/8 2-1/8 (54) 1,055 (4.7) 1,155 (5.1) 1,335 (5.9) 1,635 (7.3) 1,135 (5.0) 1,245 (5.5) 1,435 (6.4) 1,760 (7.8)

Table 4 - Steel design strength for Hilti KWIK HUS-EZ I anchors

Nominal anchor diameter in. Nominal internal thread diameter in. Tensile Nsa lb (kN) Shear Vsa lb (kN) Seismic Shear Vsa,eq lb (kN)
3/8 1/2-13 UNC 5,990 (26.6) 1,130 (5.0) 1,130 (5.0)

Canadian Limit State Design

Limit State Design of anchors is described in the provisions of CSA A23.3-14 Annex D for post-installed anchors tested and assessed in accordance with ACI 355.2 for mechanical anchors and ACI 355.4 for adhesive anchors. Tables 7 to 11 of this section contains the Limit State Design tables with factored characteristic loads that are based on the loads that are expected to be published in ESR-3027. The factored resistance tables have characteristic design loads that are pre-factored by the applicable reduction factors for a single anchor with no anchor-to-anchor spacing or edge distance adjustments for the convenience of the user of this document. All the figures in the previous ACI 318-14 Chapter 17 design section are applicable to Limit State Design and the tables will reference these figures.

For a detailed explanation of the tables developed in accordance with CSA A23.3-14 Annex D, refer to Section 3.1.8 of the Hilti Product Technical Guide Ed. 17.

Table 7 - Hilti KWIK HUS-EZ I carbon steel screw anchor factored resistance with concrete / pullout failure in uncracked concrete

Nominal anchor diameter in. Nominal embed. in. (mm) Tension - Nr Shear - Vr
f'c = 20 MPa (2,900 psi) lb (kN) f'c = 25 MPa (3,625 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 40 MPa (5,800 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 25 MPa (3,625 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 40 MPa (5,800 psi) lb (kN)
3/8 2-1/8 (54) 1,595 (7.1) 1,785 (7.9) 1,955 (8.7) 2,260 (10.0) 1,595 (7.1) 1,785 (7.9) 1,955 (8.7) 2,260 (10.0)

Table 8 - Hilti KWIK HUS-EZ I carbon steel screw anchor factored resistance with concrete / pullout failure in cracked concrete

Nominal anchor diameter in. Nominal embed. in. (mm) Tension - Nr Shear - Vr
f'c = 20 MPa (2,900 psi) lb (kN) f'c = 25 MPa (3,625 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 40 MPa (5,800 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 25 MPa (3,625 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 40 MPa (5,800 psi) lb (kN)
3/8 2-1/8 (54) 1,120 (5.0) 1,250 (5.6) 1,370 (6.1) 1,580 (7.0) 1,120 (5.0) 1,250 (5.6) 1,370 (6.1) 1,580 (7.0)

Table 5 - Hilti KWIK HUS-EZ I in the soffit of uncracked lightweight concrete over metal deck

Nominal anchor diameter in. Nominal internal thread diameter in. Nominal embed. depth in. (mm) Installation in lower flute Installation in upper flute
Tension - Nr Shear - Vr Tension - Nr Shear - Vr
f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN)
3/8 1/2-13 UNC 2-1/8 (54) 1,225 (5.4) 1,415 (6.3) 1,565 (7.0) 1,565 (7.0) 1,895 (8.4) 2,190 (9.7) 2,400 (10.7) 2,400 (10.7)

Table 6 - Hilti KWIK HUS-EZ I in the soffit of cracked lightweight concrete over metal deck

Nominal anchor diameter in. Nominal internal thread diameter in. Nominal embed. depth in. (mm) Installation in lower flute Installation in upper flute
Tension - σNn Shear - Vn Tension - σNn Shear - Vn
f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN) f'c = 3000 psi (20.7 MPa) lb (kN) f'c = 4000 psi (27.6 MPa) lb (kN)
3/8 1/2-13 UNC 2-1/8 (54) 855 (3.8) 985 (4.4) 1,565 (7.0) 1,565 (7.0) 1,325 (5.9) 1,530 (6.8) 2400 (10.7) 2,400 (10.7)

[Diagram illustrating installations of KWIK HUS EZ I (KH-EZ I) in soffit of concrete over metal deck assemblies, showing minimum dimensions and concrete types]

Figure 3 – Installations of KWIK HUS EZ I (KH-EZ I) in soffit of concrete over metal deck assemblies

Table 9 - Steel resistance for Hilti KWIK HUS-EZ I carbon steel screw anchor

Nominal anchor diameter in. Internal thread diameter (UNC) Tensile Nsar lb (kN) Shear Vsar lb (kN) Seismic Shear Vsar,eq lb (kN)
3/8 1/2-13 UNC 5,515 (24.5) 1,040 (4.6) 1,040 (4.6)

Table 10 - Hilti KWIK HUS-EZ I in the soffit of uncracked lightweight concrete over metal deck

Nominal anchor diameter in. Nominal internal thread diameter in. Nominal embed. depth in. (mm) Installation in lower flute Installation in upper flute
Tension - Nr Shear - Vr Tension - Nr Shear - Vr
f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN)
3/8 1/2-13 UNC 2-1/8 (54) 1,205 (5.4) 1,475 (6.6) 1,440 (6.4) 1,440 (6.4) 1,865 (8.3) 2,210 (9.8) 2,280 (10.1) 2,210 (9.8)

Table 11 - Hilti KWIK HUS-EZ I in the soffit of cracked lightweight concrete over metal deck

Nominal anchor diameter in. Nominal internal thread diameter in. Nominal embed. depth in. (mm) Installation in lower flute Installation in upper flute
Tension - Nr Shear - Vr Tension - Nr Shear - Vr
f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN) f'c = 20 MPa (2,900 psi) lb (kN) f'c = 30 MPa (4,350 psi) lb (kN)
3/8 1/2-13 UNC 2-1/8 (54) 845 (3.8) 1,030 (4.6) 1,440 (6.4) 1,440 (6.4) 1,305 (5.8) 1,595 (7.1) 2,210 (9.8) 2,210 (9.8)

Table 12 - Hilti KWIK HUS-EZ I allowable stress tension design values for installation into hollow core concrete panels

Hanger rod size Minimum effective embedment hef in. Allowable Tension Load3 lb. Ultimate Tension Load Ib.
1/2-13 UNC 1-1/8 435 1750

[Diagram showing installation of KWIK HUS-EZ I (KH-EZ I) in hollow core concrete panels, indicating admissible anchor location and dimensions]

Figure 4 - Installation of KWIK HUS-EZ I (KH-EZ I) in hollow core concrete panels

Contact Information

Please feel free to contact our Engineering Technical Services department for more information or any questions.

Hilti Engineering Technical Services – United States
(877) 749-6337 toll free
hnatechnicalservices@hilti.com

Hilti Engineering Technical Services – Canada
(800) 363-4458 toll free
CATechnicalServices@hilti.com

PDF preview unavailable. Download the PDF instead.

Technical-information-ASSET-DOC-LOC-8761957 Microsoft Word 2016

Related Documents

Preview Hilti HST4-R (BW) M16 Anchor: Technical Specifications and Installation Guide
Comprehensive operating instructions and technical data for the Hilti HST4-R (BW) M16 anchor, detailing installation procedures, dimensions, and performance specifications for construction applications.
Preview Hilti KB-TZ2 Wedge Anchor Installation and Specifications
Guide for installing the Hilti KB-TZ2 wedge anchor (1/2" x 3"). Details installation steps, required tools, and technical specifications for concrete and CMU applications.
Preview Hilti HST4-R/HST4 Expansion Anchor: European Technical Assessment ETA-21/0878
Detailed European Technical Assessment (ETA-21/0878) for Hilti HST4-R and HST4 expansion anchors. Covers technical specifications, performance data, intended use, and installation for torque-controlled concrete anchoring.
Preview Hilti HIT-HY 170: Universal Adhesive Anchoring System
Discover the Hilti HIT-HY 170, a high-performance universal adhesive anchoring system designed for reliable and versatile fixing in concrete and various masonry types. Learn about its applications, safety, and technical specifications.
Preview Hilti HUS4 Masonry Screw Anchor: European Technical Assessment ETA-23/0936
Comprehensive European Technical Assessment (ETA) for the Hilti HUS4 masonry screw anchor, detailing product specifications, intended use, performance data, and installation guidelines. Issued by Deutsches Institut für Bautechnik (DIBt).
Preview Hilti HIT-RE 100 Adhesive Anchoring System: Instructions for Use and Technical Data
Comprehensive instructions and technical specifications for the Hilti HIT-RE 100 adhesive anchoring system, covering rebar and anchor fastenings in concrete. Includes safety information, application guidelines, and accessory compatibility.
Preview Hilti HSL4-G with AT Module: Technical Specifications and Installation Guide
Comprehensive technical data, dimensions, and step-by-step installation instructions for the Hilti HSL4-G heavy-duty wedge anchor, including guidance on using the AT module for installation monitoring and compatibility with SIW tools.
Preview Hilti HST2-R V3 / HST2-HCR V3 Anchor Operating Instructions
Detailed operating instructions and technical specifications for Hilti HST2-R V3 and HST2-HCR V3 anchors, covering installation procedures, dimensions, and load data for professional construction applications.