User Guide for Kentec models including: Taktis, Fire Alarm Control Panel

Man-1172EN Taktis QSG.book

paulm

Man-1172EN Taktis QSG.book

Taktis Quick Start Guide. This Start Guide describes 2 to 8 loop and 2 to 16 loop models of the Kentec Taktis FACP (Fire Alarm Control Panel). This Quick Start Guide covers.. View

Fire Alarm Control Panel Taktis - Kentec

Taktis Quick Start Guide Man-1172EN Rev. 04 Taktis Quick Start Guide 1 Taktis Quick Start Guide This Start Guide describes 2 to 8 loop and 2 to 16 loop mo dels of the Kentec Taktis FACP (Fire Alarm Control Panel).


File Info : application/pdf, 16 Pages, 1.42MB

PDF preview unavailable. Download the PDF instead.

Man-1172EN-Taktis-QSG-Rev.04
Fire Alarm Control Panel
Taktis
Quick Start Guide

Man-1172EN Rev. 04
Taktis Quick Start Guide

*Man-1172EN*

Taktis Quick Start Guide
Taktis Quick Start Guide
This Start Guide describes 2 to 8 loop and 2 to 16 loop models of the Kentec Taktis FACP (Fire Alarm Control Panel).
This Quick Start Guide covers: · What's in the box? · QR Codes · Panel at a Glance · Hanging the Enclosure · Compliance · Terms & Conditions
What's in the box?
The Taktis FACP includes the following components and hardware.
Figure A-1 Items in the box (NOT TO SCALE)

1x Control Panel

1x Pre-mounted Power Supply

2x Enclosure Lock Keys

2x

1x

Enable Key Switch Power Supply

Keys

Accessory Pack

1 x Quick Start
Guide

Man-1172EN Rev. 04 Taktis Quick Start Guide
1

Taktis Quick Start Guide
QR Codes
The QR codes below provide links to the Taktis FACP Installation and Operation Manuals. Using your Smartphone, tablet or device install a third party QR Code Reader and scan the code to open the documents.
Figure A-2 Reading the QR Codes

Installation Manual

Operation Manual

Should you be unable to work with QR codes Manuals can be obtained by visiting the following website pages:

Manual Variant Installation Manual Operation Manual

Website http://www.kentec.co.uk/manuals/man-1154GEN.pdf http://www.kentec.co.uk/manuals/man-1169GEN.pdf

Man-1172EN Rev. 04 Taktis Quick Start Guide
2

Taktis Quick Start Guide
Panel at a Glance
The diagrams below provide an overview of the panel main components and features:
Figure A-3 2 to 8 Loop Panel Internal Layout

1 2 3
4 5
6

4

7

10

8

9

ID Description 1 Panel Indicators 2 Hinge Pin 3 Touch Panel Display 4 Hinge Loops 5 Upper Panel Fascia

Comment
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation & Operation Manuals for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.

ID Description 6 Enable Keyswitch 7 Lower Panel Fascia 8 Zone Indicators 9 Printer (Optional) 10 Panel Lock Clearance

Comment
Refer to Installation & Operation Manuals for details.
Refer to Installation Manual for details.
Up to 144 Zone Indicators. Refer to Installation Manual for details.
Refer to Installation Manual for details.
-

Man-1172EN Rev. 04 Taktis Quick Start Guide
3

Figure A-4 2 to 8 Loop Panel Chassis Layout

14

13

12

1
2 3 4 2
5

Taktis Quick Start Guide
1 11
10 2 9 8 7

6

1

1

ID Description Enclosure Fixing
1 Hole

2 Field Terminals 3 PCB Cover fixing

4

Ribbon Cable Header

5 PCB Cover

6 Battery

7 Main Chassis

Comment
Use 5mm bolts/screw fixings. Refer to fixing the cabinet in installation section for details. Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.

ID Description Main Board
8
9 Cable Tie Point 10 Power Supply 11 Earth Terminals

Comment
Refer to Installation Manual for details.
Refer to Installation Manual for details. Power supply varies depending on version.5.25A shown. For field wiring.

Refer to Installation Manual for details.
Refer to Appendix section to determine battery type. Refer to Installation Manual for details.

12 Knock-out 28mm dia. 13 Knock-out 21mm dia. 14 Earth Link

Refer to Installation Manual for details. Refer to Installation Manual for details.
For continuity only. Refer to Installation Manual for details.

Man-1172EN Rev. 04 Taktis Quick Start Guide
4

Taktis Quick Start Guide
Figure A-5 2 to 8 Loop Panel Rear of Door
1 2
3
6 4

5

5

1

ID Description 1 Hinge Loops 2 Earth Link 3 Upper Opening

Comment
Refer to Installation Manual for details.
For continuity only. Refer to Installation Manual for details.
-

ID Description 4 Lower Opening

5

Product Label/Logo Position

6 Panel lock

Comment
-
-

Man-1172EN Rev. 04 Taktis Quick Start Guide
5

Figure A-6 2 to 16 Loop Front Panel Layout
1 2 3 4 6

Taktis Quick Start Guide 5

ID Description 1 Panel Indicators 2 Touch Panel Display 3 Enable Keyswitch

Comment

ID Description

Refer to Installation Manual for details.

4 Zone Indications

Refer to Installation and Operation Manuals for details.

5

Panel Lock

Refer to Operation Manual for details.

6 Printer (Optional)

Comment
Up to 144 Zone Indications. Refer to Installation Manual for details. -
Refer to Installation Manual for details.

Man-1172EN Rev. 04 Taktis Quick Start Guide
6

Taktis Quick Start Guide

Figure A-7 2 to 16 Loop Panel Internal Layout

16

15

14

1

1

2

3

13

4

3

5

3

5

12

6

11

7

3

3 2

8 10

9

2

1

ID Description Enclosure fixing hole
1
2 Hinge Loop 3 Field Terminals 4 PCB Cover Fixing 5 Ribbon Cable Header 6 Cable Tie Point 7 Main Board 8 Chassis Locating Lug
Man-1172EN Rev. 04 Taktis Quick Start Guide 7

Comment
Use 5mm bolts/screws fixings. Refer to fixing the cabinet in installation section for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.

ID Description Battery
9
10 Power Supply 11 Example Board 12 Board Slot 13 Main Chassis 14 Knock-out 28mm dia. 15 Knock-out 21mm dia. 16 Earth Link

Comment
Refer to Installation manual for details.
Power supply varies depending on version.10.25A shown.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
For continuity only. Refer to Installation Manual for details.

Figure A-8 2 to 16 Loop Panel Rear of Door
9

Taktis Quick Start Guide
1 2 3 4
5 2 6 7

2 8

ID Description 1 Earth Link 2 Hinge Loop 3 Door Chassis

4

LCD Main Processor Board

5 Zone LED Board

Comment
For continuity only. Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.
Refer to Installation Manual for details.

ID Description 6 Printer (Optional)

7 Door Chassis

8

Product Label/Logo Position

9 Panel Lock

Comment
Refer to Installation Manual for details. Refer to Installation Manual for details. -
-

Man-1172EN Rev. 04 Taktis Quick Start Guide
8

Taktis Quick Start Guide
Hanging the Enclosure
To hang the enclosure proceed with the following steps. For details on how to remove the enclose components please refer to the Installation Section of the FACP Installation Manual.
1. Start by marking the fixing centres for the upper two enclosure fixing points. Ensure your fixing centres are level.
Figure A-9 Marking the enclosure fixing centres
487mm 368mm
LEVEL LINE
2 to 8 Loop Enclosure External Dimensions:
420mm x 590mm
2 to 16 Loop Enclosure External Dimensions:
537mm x 716mm
Note: Where permissible use the appropriate wall plugs for your fixings.
Man-1172EN Rev. 04 Taktis Quick Start Guide 9

Taktis Quick Start Guide 2. Attach the two fixings to the wall using appropriate wall plugs. Screw fixings half-way home 3. Hang the enclosure on the two fixings, through the enclosure key-way fixing points.
Figure A-10 Hanging the enclosure on the key-way fixing points
1 2
4. With the enclosure in place, mark for the two lower fixings and attach as appropriate. Depending on fixing/wall type, you may need to temporarily remove the enclosure when making the lower fixing holes.
Figure A-11 Fixing the enclosure to the wall

5. With the enclose in place, tighten all four fixings using appropriate force.

Man-1172EN Rev. 04 Taktis Quick Start Guide
10

Taktis Quick Start Guide

Compliance
Taktis FACP's are compliant with EN54-2, EN54-4 and are available with 2 to 8 loop or 2 to 16 loop, in four standard enclosure sizes.

The modular construction allows control panels to be configured with a range of options including, zonal fire indicators, a printer, additional supervised ancillary inputs and outputs, networking Taktis FACP's together for larger system applications and remote communications.

A large format, touch screen display is used to provide an exceptionally clear and intuitive user interface. This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:

(i)

Regulations for electrical equipment in buildings specific to the country of use

(ii)

Codes of practice

(iii) Statutory requirements

(iv) Any instructions specifically advised by the manufacturer

(v)

Only fire rated and shielded cable should be used.

Note: For LPCB approved installations use only FP200*, 1.5mm2 2 core cable.

Environmental Considerations
The PSU's are mounted in steel enclosures within the CIE with an ingress protection rating of IP30. The operating temperature range should not exceed -5°C to +40°C (±2°C). Humidity levels should not exceed 95% (non-condensing).

Standards and Directives The control equipment is designed in compliance for:

Table 1: Standards and Directives

Low Voltage Directive 2014/35/EU
EN62368 Audio/Video, Information and Communication Technology Equipment, Safety Requirements
EN54-2

EMC Directive 2014/30/EU EN50130 Electromagnetic compatibility - product family standard EN54-4 EN54-13

Declaration Of Performance
Taktis fire alarm control and indicating equipment and power supply equipment conform to the essential requirements of the Construction Products Regulation No.305/2011

Table 2: Certified with the following Options with requirements from EN 54-2:1997

7.8 Output to fire alarm device(s) 7.9.1 Output to fire alarm routing equipment 7.9.2 Alarm confirmation input from fire alarm routing equipment 7.10.3 Output to type C 7.10.4 Fault monitoring of fire protection equipment 7.11 Delay to outputs 7.12.1 Dependencies on more than one alarm signal ­ Type A 7.12.2 Dependencies on more than one alarm signal ­ Type B 7.12.3 Dependencies on more than one alarm signal ­ Type C

7.13 Alarm counter 8.3 Fault signals from points 8.9 Output to fault warning routing equipment 9.5 Disablement of addressable points 10 Test condition

Man-1172EN Rev. 04 Taktis Quick Start Guide
11

Taktis Quick Start Guide

EN54-4: 1997 +A1:2002 +A2:2006 (Power supply equipment for fire detection and fire alarm systems for buildings.)

Table 3: EN54-4: 1997 +A1:2002 +A2:2006 (Functions Provided)

Operation from a main power supply- EN54-4 clause 5.1
Monitor and charge the standby battery - EN54-4 clause 5.3
S408 10.25A Universal Input Power Supply has been approved with 230V AC mains input.

Operation from a standby battery - EN54-4 clause 5.2
Recognise and notify supply faults - EN54-4 clause 5.4
S406 5.25A Power Supply has been approved both with 230V AC and 115V AC mains input.

Table 4: Requirements subject to third party testing and approvals
IFAM German Interface Functionality

The products also comply with the following:

Table 5: Low Voltage and Electromagnetic Compatibility Directives

Low Voltage Directive 2014/35/EU
EN62368 - Audio/Video, Information and Communication Technology Equipment Safety Requirements

Electromagnetic Compatibility Directive 2014/30/EU
BS EN55022: 1998 - Emissions, Spur.
EN50130-4: 1995 +A1:1998 +A2:2003 EN50130-4: 2011 Alarm systems, Electromagnetic compatibility - Product family standard: Immunity requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems.
EN6100-6-3:2007:+A1:2001 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments.

Table 6: Additional functions provided that are not covered by EN54-2, EN54-4 or EN54-13

Auxiliary power outputs Programmable inputs Ethernet and GPRS remote connections

Programmable relay outputs Programmable cause and effects Panel mounted printer

Rating Label

Kentec Electronics Ltd. Dartford DA1 1JQ U.K.

2831-CPR-F0912

360b/01

G 220007

EN 54-2:1997 + A1: 2006 EN 54-4:1997 + A1: 2002 + A2: 2006
TAKTIS - CONTROL AND INDICATING EQUIPMENT FOR FIRE DETECTION AND FIRE ALARM SYSTEMS FOR BUILDINGS

PROVIDED OPTIONS:
Output to fire alarm device(s) - EN54-2 clause 7.8 Output to fire alarm routing equipment - EN54-2 clause 7.9.1 Alarm confirmation input from fire alarm routing equipment - EN54-2 clause 7.9.2 Output to type C - EN54-2 clause 7.10.3 Fault monitoring of fire protection equipment - EN54-2 clause 7.10.4 Delay to outputs - EN54-2 clause 7.11 Dependencies on more than one alarm signal ­ Type A - EN54-2 clause 7.12.1 Dependencies on more than one alarm signal ­ Type B - EN54-2 clause 7.12.2 Dependencies on more than one alarm signal ­ Type C - EN54-2 clause 7.12.3 Alarm counter - EN54-2 clause 7.13 Fault signals from points - EN54-2 clause 8.3 Output to fault warning routing equipment - EN54-2 clause 8.9 Disablement of addressable points - EN54-2 clause 9.5 Test condition - EN54-2 clause 10 For other technical data see O & M Manual Doc ref: Man-1154

Works Order No:
Model number:
Date of manufacture:

Power rating 230 VAC, 1A, 50Hz

Lab-1821 B4691

Mains fuse - 250V, 3A SB - Replace only with similar type.

V1.2

Man-1172EN Rev. 04 Taktis Quick Start Guide
12

Taktis Quick Start Guide

Safety
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used. An article is not regarded as properly used if it is used without regard to any relevant information or advice relating to its use made available by the supplier. This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:
(i) IEE regulations for electrical equipment in buildings (ii) Codes of practice (iii) Statutory requirements (iv) Any instructions specifically advised by the manufacturer

According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use This equipment is designed to operate from 230V 50Hz mains supplies and is of class 1 construction. As such it must be connected to a protective earthing conductor in the fixed wiring of the installation. A readily accessible double pole disconnect device with a disconnect air gap of at least 3mm and conforming to EN 60950, shall be incorporated in the fixed wiring. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe.
Terms and Conditions
Details of Kentec Electronics Ltd. Terms and Conditions including Warranties and Returns & Repair Policies can be found on our website at the following locations:

Terms, Conditions & Warranty Returns & Repairs

https://kentec.co.uk/terms-and-conditions/ https://kentec.co.uk/returns-policy/

Address of Kentec Electronics Ltd.
Units 25-26 Fawkes Avenue, Questor, Dartford, Kent. DA1 1JQ United Kingdom Registered in England:FACP No.1937570 Tel: +44 (0)1322 222121

http://www.kentec.co.uk
Disclaimer
In no event shall The Manufacturer be liable for any damages or injury of any nature or kind, no matter how caused, that arise from the use of the equipment referred to in this manual. Strict compliance with the safety procedures set out and referred to in this manual, and extreme care in the handling or use of the equipment, are essential to avoid or minimise the chance of personal injury or damage to the equipment. The information, figures, illustrations, tables, specifications, and schematics contained in this manual are believed to be correct and accurate as at the date of publication or revision. However, no representation or warranty with respect to such correctness or accuracy is given or implied and The Manufacturer will not, under any circumstances, be liable to any person or corporation for any loss or damages incurred in connection with the use of this manual.
The information, figures, illustrations, tables, specifications, and schematics contained in this manual are subject to change without notice. Unauthorised modifications to the fire detection system or its installation are not permitted, as these may give rise to unacceptable health and safety hazards. By installing this equipment on a computer network, the owner accepts full and unequivocal responsibility for ensuring that it is protected against all cyber threats and illegal tampering during the lifetime of the equipment. Any software forming part of this equipment should be used only for the purposes for which The Company supplied it. The user shall undertake no changes, modifications, conversions, translations into another computer language, or copies (except for a necessary backup copy). In no event shall The Manufacturer be liable for any equipment malfunction or damages whatsoever, including (without limitation) incidental, direct, indirect, special, and consequential damages, damages for loss of business profits, business interruption, loss of business information, or other pecuniary loss, resulting from any violation of the above prohibitions.

Man-1172EN Rev. 04 Taktis Quick Start Guide
13

This page is intentionally left blank.

Taktis Quick Start Guide

Man-1172EN Rev. 04 Taktis Quick Start Guide
14



References