OSAME115R ERV - Energy Recovery Air Exchanger with Recirculation
A high-efficiency ventilation solution designed for residential and small commercial applications.
Product Overview
The OSAME115R is an Energy Recovery Air Exchanger (ERV) with recirculation capabilities, designed by Ouellet. It offers efficient air exchange while recovering both sensible heat and latent humidity, contributing to reduced heating and cooling demands and improved indoor air quality.
The unit is designed for whisper-quiet operation, easy installation, and maintenance, and is manufactured in Canada to withstand variable climatic conditions. It features a compact, ultra-thin profile and is available in two configurations: Side Port and Top Port models.
Key Features and Benefits
- Airflow and Performance: Fully adjustable airflow up to 113 cfm at 0 in.w.g. Offers 67% sensible recovery effectiveness at 0°C (32°F) and 60% at -25°C (-13°F). Includes recirculation defrosts.
- Voltage: Operates on 120V, 60Hz, 0.8A.
- Benefits: Reduces winter heating and summer cooling demands. Operates quietly due to factory calibration and balancing. Simplifies installation and maintenance. Engineered for diverse climates.
- Construction: Features a corrosion-resistant galvanized steel housing (24-gauge) with a pre-painted neutral white finish. Includes a convenient, screwless hinged door. The unit is ultra-thin at 9 inches (229 mm) and requires no drain. It is lightweight (37 lb / 16.8 kg) with 5-inch (127 mm) port sizes. Equipped with MERV 8 charcoal polyester filters.
- Motor: Utilizes an energy-efficient, sealed European motor with a closed housing and automatic reset thermal protection. Features electronic adjustment for balancing without flow keys and integrated pressure ports for precise balancing.
- Energy Recovery Core: High-efficiency, durable 100% polymer core that recovers both latent and sensible energy (heat and humidity). Meets or exceeds ASHRAE 90.1-2010 standards. The core is washable to restore effectiveness.
- Advanced Features: Incorporates antimicrobial protection (ISO846), tested for virus transfer avoidance (ASTM F-1671), certified for zero crossflow contamination (AHRI 1060), and meets UL94 HB flammability standards.
Control Options
Two primary control options are available:
- SA-LT15: A Decora-style wall-mounted control/timer offering modes for Intermittent (20-40 min), Continuous, Off, and a Timer (20-40-60 min).
- SA-LCD15: A digital Decora-style wall-mounted control/timer with modes for Intermittent (20-40 min), Continuous, Humidity, and Recirculation Off.
Installation and Settings
The OSAME115R can be ceiling-mounted or suspended, fitting easily into ceiling voids or below fire-rated ceilings. Nylon suspension straps are included for installation. An optional steel mounting plate (SA-P5R) is available for Top Port models.
Balancing the unit is facilitated by integrated pressure ports and electronic adjustments, requiring minimal tools and time. Installers need to specify desired airflow rates for low and high speeds, ensuring ducting does not limit maximum flow.
A furnace interconnect plug connector is factory installed.
Note: A backdraft damper is required for the fresh air inlet and is not supplied with the unit.
Models and Specifications
The OSAME115R is available in two main configurations:
Product # | Airflow (cfm) | Recirculation | Sensible Recovery Effectiveness (SRE)¹ | Port Size (in/mm) | Volts | Hertz | Amps | Weight (lb/kg) |
---|---|---|---|---|---|---|---|---|
OSAME115RS | 113 | Yes | 67% (at 0°C, 30 L/s) 60% (at -25°C, 24 L/s) | 5 in. / 127 mm | 120 | 60 | 0.8 | 37 lb / 16.8 kg |
OSAME115RT | 113 | Yes | 67% (at 0°C, 30 L/s) 60% (at -25°C, 24 L/s) | 5 in. / 127 mm | 120 | 60 | 0.8 | 37 lb / 16.8 kg |
¹ SRE: Sensible Recovery Effectiveness.
Available Options
Product # Kit | Factory Installed* | Description |
---|---|---|
F | Yes | Foam for ceiling installation (for Top Port models only) |
R | Yes | Reverse air flow configuration |
SA-P5R | Yes | Steel mounting plate for Top Port model only (includes foam) |
KIT-OSA-INS-5 | No | Basic installation kit for air exchanger (5 in. ducts) |
KIT-SA-FI-115 | No | Kit of 2 filters for 115R air exchanger |
* For factory-installed options, add the option number to the base product number.
Energy Ratings and Performance Curves
The OSAME115R is HVI certified. The unit's performance is detailed in the following energy ratings and airflow curves:
Performance Curves at Highest Speed
Energy Ratings - HVI Certified
Supply temperature | Air flow | Power (W) | Sensible recovery effectiveness (SRE)¹ (%) | Adjusted sensible recovery (%) | Total recovery efficiency (%) | Latent recovery / moisture transfer (%) | |
---|---|---|---|---|---|---|---|
cfm | L/s | ||||||
Heating | |||||||
0 °C (32 °F) | 47 | 22 | 34 | 70 | 75 | 61 | 61 |
0 °C (32 °F) | 64 | 30 | 40 | 67 | 71 | 54 | 54 |
0 °C (32 °F) | 85 | 40 | 54 | 63 | 68 | 49 | 49 |
-25 °C (-13 °F) | 51 | 24 | 41 | 60 | 63 | 50 | 50 |
Cooling | |||||||
35 °C (95 °F) | 47 | 22 | 34 | 53 | 56 | 51 | 51 |
Application
The OSAME115R is an ideal solution for high-rise apartments and small to medium-sized homes. It effectively purifies indoor air by expelling pollutants, dust, and allergens to the outside, while simultaneously ensuring a balanced supply of fresh outdoor air.
Certifications
The unit is certified by HVI (Home Ventilating Institute), CSA (Canadian Standards Association), and is ENERGY STAR certified.