Mitsubishi Electric CITY MULTI PEFY-P30NMAU-E4
Submittal Data: Medium Static Ceiling-Concealed Ducted Unit
Key Features
- Designed specifically for use with CITY MULTI outdoor units
- Choice of three fan speeds for optimum comfort
- Built-in condensate lift; lifts to 27-9/16" (700mm)
- 9-7/8" (250mm) high for low ceiling heights
- Highly efficient DC motor
- Dual setpoint functionality
- IT Terminal (CN105)
A photograph shows the Mitsubishi Electric PEFY-P30NMAU-E4 indoor unit, a rectangular, white, ceiling-concealed ducted air handler.
Specifications
Parameter | Value |
---|---|
Rated Capacity (Cooling) | 30,000 Btu/h |
Rated Capacity (Heating) | 34,000 Btu/h |
Power Supply | 208/230V, 1Ph, 60Hz |
Minimum Circuit Ampacity (MCA) | 2.88 A |
Maximum Fuse/Breaker Size | 15 A |
Fan Type x Quantity | Sirocco fan x 2 |
Motor Type x Quantity | DC motor x 1 |
Airflow Rate | 618 - 742 - 883 CFM |
External Static Pressure (Selectable) | <0.14> - 0.20 - <0.28> - <0.40> - <0.60> In. WG |
Sound Pressure Level (measured in anechoic room) | 31-35-39 dB(A) |
Drain Pipe Size | O.D. 1-1/4" (32 mm) |
External Finish | Galvanized steel plate |
Coil Type | Cross fin (Aluminum fin and copper tube) |
Air Filter | PP honeycomb fabric |
Unit Dimensions (H) | 9-7/8" (250 mm) |
Unit Dimensions (W) | 43-5/16" (1,100 mm) |
Unit Dimensions (D) | 28-7/8" (732 mm) |
Net Weight | 67 lbs. (30 kg) |
Refrigerant Pipe Diameter (gas) (Brazed) | 5/8" (15.88 mm) |
Refrigerant Pipe Diameter (liquid) (Brazed) | 3/8" (9.52 mm) |
Unit Outline and Dimensions
Detailed unit dimensions for the PEFY-P24,27,30NMAU-E4 model series are provided:
- Height (A): 1100 mm (43-5/16 in.)
- Suspension bolt pitch (B): 1154 mm (45-7/16 in.)
- Width (C): 1200 mm (47-1/4 in.)
- Depth (D): 1060 mm (41-3/4 in.)
- Unit Length (E): 732 mm (28-7/8 in.)
- Other dimensions (F, G) and specific measurements for other model series (PEFY-P06-12, PEFY-P15-18, PEFY-P36-48, PEFY-P54) are also detailed in the original document.
The diagrams illustrate the unit from the top, front, and side views, showing air inlet, air outlet, drain connections (emergency and gravity), refrigerant piping connections (gas and liquid), control box, and terminal blocks. The unit features a fresh air intake knockout hole and specific notes regarding installation, such as using M10 suspension bolts and maintaining service space.
Optional Accessories
- PAC-YU25HT: External Heater Adapter
- FBM2-3-A: Filter Box and Filter(s) (MERV13)
- PAC-KE93TB-E: Filter Box
Notes
- Cooling conditions: Indoor 80°F (26.7°C) DB, 67°F (19.4°C) WB // Outdoor 95°F (35°C) DB.
- Heating conditions: Indoor 70°F (21.1°C) DB // Outdoor 47°F (8.3°C) DB, 43°F (6.1°C) WB.
- All electrical work must comply with National (CEC) and local codes and regulations.
- Ventilation air should be introduced independently of or in series with VRF indoor units. Refer to local codes for required ventilation rates.
- Applications are restricted to comfort heating and cooling; process/equipment heating and cooling applications are not recommended.
- Mitsubishi Electric Sales Canada Inc. (MESCA) supports only MESCA supplied and approved components and accessories for proper functioning. Use of non-MESCA components may affect warranty. MESCA recommends considering all applicable design parameters and implementing necessary countermeasures, including antifreeze solutions for water-based systems.
- All system components must be compatible. Refer to Technical Bulletin 100-151 for control compatibility details.
- Any unauthorized changes to this document are void and the responsible party assumes full liability.
Fan Characteristics Curves
These graphs illustrate the fan performance characteristics for the PEFY-P24,27,30NMAU-E4 model under various operating conditions. The vertical axis represents External Static Pressure (in Pascals and inches of water gauge), and the horizontal axis represents Airflow Rate (in cubic meters per minute and cubic feet per minute). Each graph shows performance curves for Low, Middle, and High fan speeds, along with a 'Limit' line indicating operational boundaries. The curves are presented for different selectable external static pressure settings: 35Pa (0.14 in.WG), 50Pa (0.20 in.WG), 70Pa (0.28 in.WG), 100Pa (0.40 in.WG), and 150Pa (0.60 in.WG).
Note: MERV13 filter Box & Filter is not reflected in these displayed curves. Refer to Form # SB_FBM2-Series_Filter_Boxes for full details.