MESCA

Submittal Data: PEFY-P48NMAU-E4

28 févr. 2022 — Designed specifically for use with CITY MULTI outdoor units. • Choice of three fan speeds for optimum comfort. • Built-in condensate lift; lifts to 27-9/16" ...

SPECIFICATION

Mitsubishi City Multi PEFY Series 48,000 BTU - Indoor - Medium Static - Ceiling-Concealed - VRF Heat Pump - 230/1 | Ferguson

PDF preview unavailable. Download the PDF instead.

9555930 12005550 specification
Job Name: Schedule Reference: Submitted To: Engineer:

Submittal Data: PEFY-P48NMAU-E4
48,000 BTU/H Medium Static Ceiling-Concealed Ducted

Location: Submitted By: Reference: Date:

Approval:

Construction:

Application:

· Designed specifically for use with CITY MULTI outdoor units · Choice of three fan speeds for optimum comfort · Built-in condensate lift; lifts to 27-9/16" (700mm) · 9-7/8" (250mm) high for low ceiling heights · Highly efficient DC motor · Dual setpoint functionality 7 · IT Terminal (CN105)

Images provided for reference purposes only

Rated Capacity:

( Cooling / Heating capacity indicated at the maximum value at operation under the following conditions Note: 1, 2 )

Cooling 1 Heating 2

Btu/h Btu/h

48,000 54,000

Specifications:

Power Supply Minimum Circuit Ampacity (MCA) 3

208/230V, 1Ph, 60Hz

A

4.38

Maximum Fuse/Breaker Size

A

15

Fan Type x Quantity

Sirocco fan x 3

Motor Type x Quantity

DC motor x 1

Airflow Rate

CFM

918 - 1,112 - 1,306

External Static Pressure (Selectable)

In. WG

<0.14> - 0.20 - <0.28> - <0.40> - <0.60>

Sound Pressure Level (measured in anechoic room)

dB(A)

35-40-44

Drain Pipe Size

In. (mm)

O.D.1-1/4 (32)

External Finish

Galvanized steel plate

Coil Type

Cross fin (Aluminum fin and copper tube)

Air Filter

PP honeycomb fabric.

H: In. (mm)

9-7/8 (250)

Unit Dimensions

W: In. (mm)

55-1/8 (1,400)

D: In. (mm)

28-7/8 (732)

Net Weight

Lbs. (kg)

86 (39)

Refrigerant Pipe Diameter (gas)

(Brazed)

In. (mm)

5/8 (15.88)

Refrigerant Pipe Diameter (liquid)

(Brazed)

In. (mm)

3/8 (9.52)

Model No.

Description: (Optional Accessories)

PAC-YU25HT

External Heater Adapter

FBM2-4-A PAC-KE94TB-E

Filter Box and Filter(s) (MERV13) Filter Box

Notes:

Note: 1. Cooling (Indoor // Outdoor) 80°F (26.7°C) DB, 67°F (19.4°C) WB // 95°F (35°C) DB
2. Heating (Indoor // Outdoor) 70°F (21.1°C) DB // 47°F (8.3°C) DB, 43°F (6.1°C) WB
3. All electrical work shall comply with National (CEC) and local codes and regulations.
4. Ventilation air to be introduced independent of or in series with VRF indoor units. Please refer to local codes for the required ventilation rates specific to the application.
5. Applications should be restricted to comfort heating and cooling only; process/equipment heating and cooling applications are not recommended. 6. Mitsubishi Electric Sales Canada Inc. (MESCA) supports the use of only MESCA supplied and approved components and accessories for proper functioning of the unit(s). Always consult relevant technical product documentation at mitsubishitechinfo.ca, your local distributor or MESCA BC sales office as applicable. Use of non - MESCA supported components and accessories will affect warranty coverage. MESCA recommends (A) consideration of all applicable design and application parameters and requirements specific to any project; and (B) implementation of any countermeasures needed to address those parameters and requirements, including the provision of antifreeze solution in water based systems used in conjunction with ducted indoor units. 7. All components of the system must be compatible. For more details on system control compatibility, please refer to Technical Bulletin 100-151 available on our website. 8. Should any person change this document in any manner whatsoever without MESCA's written permission, the document shall be of no force and effect and any change shall be deemed to be a representation and warranty made by that person and not MESCA. That person, and not MESCA, shall assume full responsibility for the consequences of such changes. MESCA assumes no responsibility for any consequences in such cases.

www.MitsubishiElectric.ca © 2022 Mitsubishi Electric Sales Canada Inc.

Page 1 of 3

Specifications are subject to change without notice. Form No. SB_PEFY-P48NMAU-E4_202202

40 (1-5/8) 200 (7-7/8)

Submittal Data: PEFY-P48NMAU-E4
Indoor Unit Outline and Dimensions:

www.MitsubishiElectric.ca © 2022 Mitsubishi Electric Sales Canada Inc.

Opposite piping side view
Drain pipe (O.D. Ø32 (1-1/4) (Emergency drain)
Bottom

Outlet air side view
15 (5/8)

Top
2XE-Ø2.9 (1/8)

Top view

378 (14-15/16) 120°
(4Ø-1152/516)

120° 135 (5-3/8)

Note 1. Use an M10 screw for the suspension bolt (field supply).

2. Keep the service space for maintenance at the bottom.

3. This drawing is for PEFY-P24·27·30NMAU-E4 models, which

153 (6-1/16)

have 2 fans. PEFY-P06·08·12NMAU-E4 models have 1 fan. PEFY-P15·18NMAU-E4 models have 2 fans.

Fresh air intake Ø100 (3-15/16) knock out hole Note 5 3-Ø2.9 (1/8) mount hole

PEFY-P36·48·54NMAU-E4 models have 3 fans. 4. If the inlet duct is used, remove the air filter
(supplied with the unit), then install the filter (field supply) at the suction side.

5. Heat air to 0°C (32°F) or higher when taking fresh air

Inlet air side view

with a fresh air intake.

18 (3/4) 210 (8-5/16)

A B (Suspension bolt pitch)
C G

100 (3-15/16)X(E-1)=F

D (Duct)

Page 2 of 3

58 (2-5/16) 73 (2-7/8)

100 (3-15/16) 40 (1-5/8)

40 (1-5/8) 122 (4-13/16)

23 (15/16)

178 (7-1/16) (DUCT) 100 (3-15/16)
33 (1-5/16)

Specifications are subject to change without notice. Form No. SB_PEFY-P48NMAU-E4_202202

Air

Air

outlet

inlet

100 (3-15/16)

10 (7/16)

30 (1-3/16)

20 (13/16)

57 (2-1/4)
32 (1-5/16) 2 Refrigerant piping
brazing connection (liquid)

(Suspension bolt pitch) 643 (25-3/8)

732 (28-7/8)

700 (27-9/16)

238 (9-3/8) 10 (7/16)

Drain pipe (Integral lift pump outlet) (O.D.Ø32 (1-1/4))

Drain pump

Top

41 (1-5/8) 217 (8-9/16) 250 (9-7/8)

2x2-Ø2.9 (1/8)

1 Refrigerant piping

brazing connection (gas) (5-3/8) (2-11/16)

Piping side view

136

67

356 (14-1/16)

Bottom
Control box Terminal block (Transmission) Terminal block (Power source)
Drain pipe (O.D.Ø32 (1-1/4)) (Gravity drain)

23 (15/16) 21 (7/8)

Air filter

Model

1 Gas pipe

PEFY-P06,08,12NMAU-E4 Ø12.7

PEFY-P15,18NMAU-E4

(1/2)

Unit:mm(in.)
2 Liquid pi
Ø6.35 (1/4)

PEFY-P24,27,30NMAU-E4 PEFY-P36,48NMAU-E4 PEFY-P54NMAU-E4

Ø15.88 (5/8)

Ø9.52 (3/8)

Unit:mm(in.)

Model

A

B

C

D

E

F

G

PEFY-P06,08,12NMAU-E4

700 (27-9/16)

754 (29-11/16)

800 (31-1/2)

660 (26)

7

600 658 (23-5/8) (25-15/16)

PEFY-P15,18NMAU-E4

900 954 1000 860 (35-7/16) (37-9/16) (39-3/8) (33-7/8)

9

800 858 (31-1/2) (33-13/16)

PEFY-P24,27,30NMAU-E4

1100 (43-5/16)

1154 (45-7/16)

1200 (47-1/4)

1060 (41-3/4)

11

1000 1058 (39-3/8) (41-11/16)

PEFY-P36,48NMAU-E4

1400 1454 1500 1360 (55-1/8) (57-1/4) (59-1/16) (53-9/16)

14

1300 1358 (51-3/16) (53-1/2)

PEFY-P54NMAU-E4

1600 (63)

1654 1700 1560 (65-1/8) (66-15/16) (61-7/16)

16

1500 1558 (59-1/16) (61-3/8)

Unit : mm(in.)

Fan Characteristics Curves:

Submittal Data: PEFY-P48NMAU-E4

Note: MERV13 filter Box & Filter is not reflected in these displayed curves, reference Form # SB_FBM2-Series_Filter_Boxes for full details. Page 3 of 3

www.MitsubishiElectric.ca © 2022 Mitsubishi Electric Sales Canada Inc.

Specifications are subject to change without notice. Form No. SB_PEFY-P48NMAU-E4_202202

