Honeywell HE220A,B and HE260A,B Bypass Flow-Through Humidifier
Application
The HE220A,B and HE260A,B Bypass Flow-through Humidifiers utilize the warm air furnace blower to provide whole-house humidification. They are compatible with virtually any Honeywell humidity control, with optimal performance achieved when paired with the Honeywell Perfect Climate Comfort Center™ control.
Product Data
Features/Benefits
- Capable of humidifying a large area.
- Utilizes proven technology for high performance humidification and enhanced comfort.
- Preassembled for quicker installation.
- Features a small footprint and light weight with reversible components for easy mounting on either the warm air supply or return air duct of any forced air furnace.
- Interior components are designed for quick maintenance and service.
- Includes an easy-to-use humidity control that can be mounted on the wall or duct for flexible installation.
- The Perfect Climate Comfort Center™ control can replace both the thermostat and humidity control for improved aesthetics and convenience.
- Continuous flushing reduces the frequency of maintenance in hard water installations.
Contents
- Application
- Features/Benefits
- Specifications
- Ordering Information
- Installation
- Wiring the Humidifier
- Plumbing the Saddle Valve
- Checking the Installation
- Operating the Humidifier
- Operation
- Maintenance
- Checkout Procedure
- Troubleshooting
- Replacement Parts
Specifications
Capacity: At 120°F (49°C) plenum temperature and 0.20 static pressure drop across supply and return:
- HE220A,B: 12 gallons per day (gpd) or 46 liters per day (lpd).
- HE260A,B: 17 gallons per day (gpd) or 65 liters per day (lpd).
Humidified Area: See Table 1.
Electrical Ratings: 24 Vac, 60 Hz, 0.5A.
Humidifier Pad Dimensions: See Table 2.
Plenum Opening Dimensions (Height x Width): See Table 3.
Summer Shut-off Damper Dimensions (Height x Width): See Table 4.
Bypass Duct Opening (Diameter): 6 in. (152 mm).
Drain Connection: 1/2 in. (13 mm) I.D. plastic hose connected directly to the drain fitting on the unit.
Dimensions: Refer to Figure 1 and Figure 2.
Table 1. Size Of Area That Can Be Humidified.
House Description | Air Changes Per Hour | HE220 Area (Up To) | HE260 Area (Up To) | ||
---|---|---|---|---|---|
Sq ft | Sq m | Sq ft | Sq m | ||
Loose | Two | 750 | 70 | 1,000 | 93 |
Average | One | 1,500 | 140 | 2,000 | 186 |
Tight | One-half | 3,000 | 280 | 4,000 | 372 |
Table 2. Dimensions Of Humidifier Pads In In. (mm).
Model | Height | Width | Depth |
---|---|---|---|
HE220 | 9-13/16 (249) | 9-1/2 (241) | 1-1/2 (38) |
HE260 | 13 (330) | 10 (254) | 1-1/2 (38) |
Table 3. Dimensions Of Plenum Opening In In. (mm).
Model | Height | Width |
---|---|---|
HE220 | 9-7/16 (241) | 9-5/16 (238) |
HE260 | 12-5/8 (321) | 9-3/4 (248) |
Table 4. Dimensions Of Summer Shut-off Damper In In. (mm).
Model | Height | Width |
---|---|---|
HE220 | 9-3/16 (234) | 8-7/8 (226) |
HE260 | 12-3/8 (314) | 9-5/16 (236) |
Ordering Information
When purchasing replacement and modernization products, refer to the TRADELINE® Catalog or price sheets for complete ordering numbers from your TRADELINE® wholesaler or distributor.
For additional questions, further information, or comments on products or services, please write or phone:
- Your local Home and Building Control Sales Office (check white pages of your phone directory).
- Home and Building Control Customer Logistics, Honeywell Inc., 1985 Douglas Drive North, Minneapolis, Minnesota 55422-4386.
In Canada: Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices are located in all principal cities of the world. Manufacturing occurs in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, and U.S.A.
Installation
Standard: Air Conditioning and Refrigeration Institute Tested: Standard 610.
Models:
- HE220A TRADELINE® and HE260A TRADELINE® Bypass Flow-through Humidifier packages include: humidifier pad, mounting template, self-piercing saddle valve, 24 Vac transformer, H908A Convertible Humidity Control.
- HE220B TRADELINE® and HE260B TRADELINE® Bypass Flow-through Humidifier packages include: humidifier pad, mounting template, self-piercing saddle valve, 24 Vac transformer, H1008A Automatic Humidity Control with HumidiCalc™ Software.
Accessories:
- Current Sensor Relay, part no. 32001754-001.
- C7089H Outdoor Temperature Sensor.
- H908A Convertible Humidity Control.
- H1008A Automatic Humidity Control with HumidiCalc+™ Software (software calculates dewpoint to prevent moisture condensation).
- HC22A Humidifier Pad (HE220A, B only).
- HE26A Humidifier Pad (HE 260A, B only).
- HumidiCalc+™ Humidifier Sizing Software (software calculates required humidifier capacity for application).
- PC8900 Perfect Climate Comfort Center™ Control.
- S688 Sail Switch.
WARNING: Hazardous Voltage. Can cause personal injury or equipment damage. Do not cut or drill into any air conditioning line or electrical accessory.
CAUTION: Freezing Water, Flooding or Static Pressure Hazard. Can cause water damage to home or permanent equipment damage.
- The humidifier must be located where the ambient temperature is above 32°F and below 160°F (0°C and 71°C).
- Ensure supply plenum static pressure is no greater than 0.3 in. w.c. and water pressure is no greater than 125 psi.
IMPORTANT: To assure optimal product performance, ensure the template is level before marking the location.
1. Determine the best location for the humidifier and draw a level line on the plenum. See Figure 3.
Figure 1: Dimensions of HE220A,B This diagram shows the external dimensions of the HE220A,B humidifier, including height, width, and duct opening diameter, with measurements provided in inches and millimeters.
Figure 2: Dimensions of HE260A,B This diagram shows the external dimensions of the HE260A,B humidifier, including height, width, and duct opening diameter, with measurements provided in inches and millimeters.
Figure 3: Typical humidifier installation locations This illustration shows how the humidifier can be installed in horizontal, lowboy, and highboy furnace configurations.
2. Tape the template in position and trace around the template.
3. Remove the template and carefully cut the rectangular opening.
4. Disassemble the humidifier: remove the cover and take out the humidifier pad assembly. See Figure 4.
NOTE: Sidewalls are interchangeable for either left or right by-pass installation. To change direction, remove the screws holding each sidewall, switch sidewall locations, and reinstall the screws.
5. Position the humidifier housing in the opening (ensure it is level), so the locking tabs are in place on the lower sheet metal edge of the opening.
6. Secure the humidifier housing to the opening at the top and bottom using sheet metal screws.
7. Locate the other plenum and cut an opening for a 6 in. (152 mm) collar.
8. Install the 6 in. (152 mm) collar.
NOTE: Install a duct damper for summer shutoff on systems with air conditioning.
9. Install a 6 in. (152 mm) diameter duct from the collar to the humidifier.
NOTE: Some installations require a 90° elbow attachment to the collar.
10. Seal the duct connections with duct tape.
NOTE: To avoid sagging and stress on the humidifier, add support when ducting is longer than 4 ft (120 cm).
11. Reinstall the humidifier pad assembly in the humidifier housing.
NOTE: Ensure the water feed tube is not pinched or kinked.
12. Hinge the cover in place and secure with the thumbscrew located at the bottom of the cover.
Figure 4: Humidifier components This diagram shows the individual parts of the humidifier, including the cover, water feed nozzle, humidifier pad assembly, frame, housing, water feed tube, and bypass sidewall.
Approvals: Underwriters Laboratories Inc. Listing: 56 BL. Canadian Underwriters Laboratories Inc. Listing: 56 BL.
Wiring the Humidifier
CAUTION: Hazardous Voltage. Can cause personal injury or equipment damage. Disconnect the power supply before installing or servicing.
- On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower, as premature transformer burnout may occur.
All wiring must comply with applicable local codes, ordinances, and regulations.
- Mount the transformer in a convenient location.
- Connect wires to the 120V side of the transformer.
- Wire the humidifier solenoid valve, current sensing relay, or sail switch, humidity control, and transformer. Refer to the humidity control installation instructions for mounting and wiring information.
NOTE: Select models of fan centers include humidifier taps, so the current sensing relay or sail switch is not needed.
Plumbing the Saddle Valve
Hot or cold water, either hard or softened, can be used in the humidifier.
- Use the self-piercing saddle valve (included) to tap into the water supply line at an appropriate location.
IMPORTANT:
- The saddle valve is not designed to regulate water flow; it is either open or closed.
- To prevent debris from clogging the solenoid inline filter, ensure the saddle valve handle is pointing toward the ceiling.
NOTE: Lightly clean the copper tubing ends with fine sandpaper before making any connections.
- Use 1/4 in. O.D. copper tubing and connect the saddle valve to the inlet side of the solenoid valve.
CAUTION: Hazardous Voltage. Can cause personal injury or equipment damage. Do not use any line connected to an air conditioner.
- Place the brass compression nut over the copper tubing.
NOTE: Do not over-tighten the compression nut. Moderate tightness prevents leaking.
- Slide the brass ferrule over the tubing.
- Insert the tubing into the solenoid valve fitting and support the valve while tightening the compression nut.
- Connect a 1/2 in. (13 mm) drain tube to the humidifier drain fitting and run it to a suitable drain.
NOTE: Slope the drain tube downward for correct drainage.
Checking the Installation
Use the following procedure to check the humidifier installation:
- Open the saddle valve.
- Set the thermostat setpoint to 10°F (6°C) above the room temperature.
NOTE: The furnace blower must be on for the humidifier to operate.
- Set the Convertible Humidity Control to a high setting, or place the H1008A Automatic Humidity Control in the Test position.
- Observe water running out of the drain line to confirm the humidifier is working.
- Check for leaks.
- Reset the thermostat and Convertible Humidity Control to a comfortable setting, or the Automatic Humidity Control to the desired frost factor setting, for automatic operation.
Operating the Humidifier
The HE220A and HE260A Humidifiers are controlled by the Convertible Humidity Control, which is installed either on an interior wall in the living area or on the return air duct. Choose the humidity control setting using the combination relative humidity/outdoor temperature setting scale on the humidity control dial. Match the dial setting to the outdoor temperature for optimizing the humidity level while reducing moisture condensation on inside windows. Table 5 can also be used to adjust the humidity control to the recommended setting.
NOTE: As the outside temperature drops, the recommended setting is lowered to accommodate the effects of dewpoint. These settings should reduce the accumulation of moisture and ice on windows and in other areas of the house.
Some indoor activities (cooking, showering, clothes drying) can cause excessive humidity levels and lead to moisture accumulation on windows.
NOTE: If this condition persists for more than a few hours, set the humidity control to the lowest setting to turn off the humidifier. If the condition does not improve, ventilate your home to remove moisture.
The Honeywell HE220B and HE260B Humidifiers are controlled by the Honeywell H1008A Automatic Humidity Control with HumidiCalc+™ Software. This automatic humidity control is mounted in the return air duct, exposed to the air stream. The HumidiCalc+™ Software automatically adjusts the humidity level based on indoor temperature and humidity, inferred or measured outdoor temperature, and the frost factor dial setting. The frost factor accounts for variations in furnace size, window insulation, and average daily climate temperature.
The Automatic Humidity Control with HumidiCalc+™ Software requires an initial adjustment period. Set the frost factor dial to 5 and use Table 6 to adjust the frost factor, one setting at a time, increasing for more humidity or decreasing if moisture develops on inside windows. For more precise adjustment, set the frost factor between dial settings. Allow two days for the humidity level to stabilize before making further adjustments. Once the proper setting is found, HumidiCalc+™ Software takes over and makes future adjustments based on varying outdoor temperatures, maintaining optimal humidity and reducing moisture build-up on windows.
Table 5. Recommended Convertible Humidity Control Settings.
At Outside Temperature | Recommended Setting | ||||
---|---|---|---|---|---|
-20°F (-29°C) | -10°F (-23°C) | 0°F (-18°C) | +10°F (-12°C) | +20°F (-7°C) | Above 20°F (-7°C) |
15 | 20 | 25 | 30 | 35 | 40 |
Table 6. Recommended Frost Factor Settings.
Humidity Level | Recommended Adjustment |
---|---|
Insufficient humidity | Increase the frost factor dial by one setting. |
Condensation on windows | Decrease the frost factor dial by one setting. |
Operation
The HE220A,B and HE260A,B Humidifiers create vapor (evaporated water) when warm air blows over a water-soaked area. As the vapor circulates, relative humidity rises.
The humidity control monitors relative humidity and activates the humidifier accordingly. The humidifier has a water supply that disburses water over a humidifier pad. Warm, dry air from the furnace passes over the pad, collects moisture, and circulates it through the house.
Humidified air feels warmer and more comfortable, potentially allowing homeowners to lower the thermostat heating setpoint and save on heating fuel bills. The result is a more comfortable and energy-efficient home environment.
Maintenance
A regular maintenance program prolongs the humidifier's life and ensures a more comfortable environment. Either hard or soft water can be used. Cleaning frequency depends on water quality.
CAUTION: Voltage Hazard. Can cause electrical shock and equipment damage. Disconnect power supply before installing or servicing.
IMPORTANT: Never oil any part of the humidifier.
Every 1 to 3 Months (Depending on Water Quality)
Use the following procedure to clean the humidifier:
- Disconnect power and turn off the humidifier water supply.
- Remove the humidifier cover. See Figure 5.
- Remove the humidifier pad assembly from the humidifier by grasping the tray and pulling it toward you.
- Pull one side of the humidifier pad assembly frame toward you and remove the tray from the frame.
- Gently pinch the water nozzle catches inward until the water nozzle can be lifted off the tray.
- Slide the humidifier pad out of the frame.
- Carefully scrape any mineral deposits from the tray and frame. Ensure the frame drain hole is clear.
- Check the humidifier pad; if excessive mineral deposits are present, replace it with a new pad.
- Disconnect the tube from the drain fitting on the bottom of the humidifier housing.
- Clean the drain fitting, if necessary.
- Bend the drain tube to loosen any mineral deposits.
- Flush the drain tube with pressurized water (e.g., from a running tap) to clean it.
- Reattach the drain tube to the drain fitting.
- Slide the humidifier pad back into the frame.
IMPORTANT: Ensure the marked side of the humidifier pad is facing up for proper performance.
- Snap the water nozzle back onto the tray.
- Reattach the tray to the frame.
- Place the humidifier pad assembly into the humidifier housing and press until it is completely seated. Be careful not to pinch or kink the water feed tube.
- Replace the humidifier cover.
- Verify humidifier operation by following the steps in the Checkout Procedure section.
End of Humidification Season
At the end of the heating season, follow steps 1 through 18 from the "Every 1 To 3 Months" section to clean the humidifier and shut it off.
IMPORTANT: Ensure the humidifier power is off.
Beginning of Humidification Season
Refer to the Checkout Procedure section to complete the humidifier startup.
Vacation
When leaving on vacation, turn off the humidifier water supply and the humidity control. Upon returning, turn on the humidifier water supply and reset the humidity control to restart the humidifier.
Figure 5: Location of humidifier parts This diagram illustrates the key components of the humidifier for maintenance purposes, including the cover, water feed nozzle, humidifier pad assembly, frame, housing, and water feed tube.
Checkout Procedure
After winter startup or servicing, use the following procedure to check the humidifier operation:
- Turn on the humidifier power and water supply.
- Set the Convertible Humidity Control to the highest setting, or place the H1008A Automatic Humidity Control in the Test position and set the thermostat to 10°F (6°C) above the room temperature.
- Observe that water is flowing out of the drain hose.
NOTE: The furnace blower must be on for the humidifier to operate.
- Reset the thermostat and Convertible Humidity Control to a comfortable setting, or the H1008A Automatic Humidity Control to the desired frost factor setting, for automatic operation.
Troubleshooting
Refer to Table 7 for troubleshooting procedures.
Table 7. Troubleshooting Procedures.
Problem | What To Look For | What To Do |
---|---|---|
Low humidity | Furnace blower not operating |
|
Rapid air changes. Drafts (cold air is dry and is an added load to the humidifier). |
|
|
High humidity | Condensation on walls. |
|
Heavy condensation on windows. |
|
Replacement Parts
Refer to Figure 6 and Table 8 when ordering replacement parts.
Figure 6. Exploded view of humidifier parts This diagram provides an exploded view of the humidifier, with numbered components corresponding to the replacement parts list in Table 8.
Table 8. List Of Replacement Parts For HE220A,B, HE260A,B Humidifiers.
Exploded View Number | Description | HE220 Part Number | HE260 Part Number |
---|---|---|---|
1 | Side wall | 32001612-001 | 32001626-001 |
2 | Bypass side wall | 32001613-001 | 32001627-001 |
3 | Cover Assembly | 32001611-001 | 32001611-002 |
4 | PerfectFlo™ water distribution tray | 32001619-001 | 32001630-001 |
5 | Humidifier pad | HC22A1007 | HC26A1008 |
6 | Frame | 32001621-001 | 32001632-001 |
7 | Drain fitting | 32001615-001 | 32001615-001 |
8 | Solenoid valve assembly (includes water feed tube and nozzle) | 32001639-002 | 32001639-002 |
9 | Saddle valve assembly | 32001616-001 | 32001616-001 |
10 | Transformer (10 VA) | 32001652-001 | 32001652-001 |
11 | Convertible Humidity Control | H908A1003 | H908A1003 |
12 | Automatic Humidity control with HumidiCalc™+ Software | H1008A1008 | H1008A1008 |
13 | Base insert assembly, includes no. 8 above | 32001625-001 | 32001625-002 |
— | Hardware Kit for Solenoid Assembly (same as Solenoid valve assembly without the solenoid valve) | 32001752-001 | 32001752-001 |
— | Current Sensing Relay | 32001754-001 | 32001754-001 |