Datasheet for Honeywell models including: HZ221K, TrueZONE Panel Kit

33-00291-01 - HZ221K TrueZONE Panel Kit

Submittal Sheet

Honeywell E&ES Technical Communication Grizli777

33-00291-01 - HZ221K TrueZONE Panel Kit

100°F (38°C) 28.8 VA 160°F (71°C) 16.8 VA 6.5 VA for HZ221 zone panel. 8 VA per ARD series zone damper. 8 VA per ZD series zone damper. 2.5 VA per MARD series zone damper.

33-00291-02 - HZ221K TrueZONE Panel Kit

SPECIFICATIONS. Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more. Current Draw: Zone Panel: 6.25 VA max. All VA specifications at 24 VAC View


File Info : application/pdf, 1 Pages, 144.93KB

PDF preview unavailable. Download the PDF instead.

33-00291
This is a legacy product supported by Resideo.

document This product

is

no HZ221K longer manufactured. TrueZONE Panel Kit

Job Name Engineer Mechanical Contractor Contractor's P.O. No. Representative Notes
APPLICATION
Model HZ221K: Kit includes HZ221 zone panel, C7735A1000 discharge sensor, and AT140A1042 40 VA transformer. 2 zones and 2H/1C heat pump with auxiliary electric heat only.
SPECIFICATIONS
Input Ratings: Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more. Current Draw: Zone Panel: 6.25 VA max. All VA specifications at 24 VAC. Wiring: 18-gauge solid (not stranded) wire. Mounting Means: The HZ221 has mounting holes on the sides top and bottom so it can be mounted on a wall, return duct, or stud. Humidity Ratings: 5% to 90% RH non-condensing. Temperature Ratings: Shipping: -20° to 150°F (-29° to 66°C). Operating: -40° to 165°F (-40° to 74°C). Emissions: Complies with FCC Class B, part 15 requirements. HZ221 TrueZONE Panel Dimensions in Inches (mm):

Model(s)

HZ221K

Qty.

Approval

Service

Tag No.

SUBMITTAL SHEET
Notes

Maximum Dampers Per Zone (Size Transformer Appropriately):

Max temperature in zone panel location

Maximum VA per zone *

100°F (38°C)

28.8 VA

160°F (71°C)

16.8 VA

6.5 VA for HZ221 zone panel.

8 VA per ARD series zone damper.

8 VA per ZD series zone damper.

2.5 VA per MARD series zone damper.

2.5 VA per RRD series zone damper.

* If exceeding max VA per zone, use SDCR relay to isolate a zone from panel. Separate SDCR required for each zone exceeding max VA.

Honeywell Zone Dampers for use with HZ221K:

Damper

Sizes

ZD series (rectangular)

Even sizes from 6" x 6" up to 28" x 20"

ARD series (round)

5-10" in 1" increments, 12-18" in 2" increments.

MARD series (round)

5, 6, 8, 9, 10, 12, 14, 16, and 18" models.

RRD series (retrofit) 5, 6, 7 and 8" models.

VA per damper (max)
8 VA
8 VA
2.5 VA 2.5 VA

Accessories:

Model number Description

AT140A1042 40 VA transformer (included in HZ311K (kit)).

AT175A1058 75 VA transformer.

C7735A1000 Discharge Sensor (included in HZ311K (kit)).

SDCR

Slave Damper Control Relay. Needed when there are too many dampers for a zone.

Thermostats

HZ221K is only compatible with heat pump thermostats that use a cool changeover valve terminal (O).

Home and Building Technologies
In the U.S.: Honeywell 1985 Douglas Drive North Golden Valley, MN 55422-3992 customer.honeywell.com

® U.S. Registered Trademark © 2017 Honeywell International Inc. 33-00291-01 M.S. 05-17 Printed in United States


Honeywell E&ES Technical Communication Adobe PDF Library 15.0