Hytronik SensorDIM Integrated HF Sensor and LED Driver
HEC6028 HEC6018 - Tri-level Control Version
Applications
Occupancy sensor and single constant current LED driver, 2-in-1.
Suitable for building into the fixture for:
- Office / Commercial Lighting
- Classroom
- Meeting Room
Use for retrofit and new luminaire designs/installations.
Features
- Tri-level dimming control based upon occupancy (also known as corridor function).
- Easy-on-the-eye operation which makes the light turning on/off less uncomfortable.
- 5 Year, 50,000hr Warranty.
Technical Data
Input Characteristics
Model No. | HEC6028 | HEC6018 |
---|---|---|
Input current | 0.15-0.14A | 0.09-0.08A |
Input power | 32.5W | 20W |
Mains voltage | 220~240VAC 50/60Hz | |
Warming-up | 20s |
Driver Data
Model No. | HEC6028 | HEC6018 |
---|---|---|
Empty load voltage | 56V | 50V |
Output LED current | 700mA | 500mA |
Output LED voltage | 23~40VDC | 23~36VDC |
Output LED power | 16~28W | 11.5~18W |
Power factor | ≥0.9 | ≥0.9 |
Efficiency | 85% (Max.) | 85% (Max.) |
Sensor Data
Model No. | HEC6028 | HEC6018 |
---|---|---|
Sensor principle | High Frequency (microwave) | |
Operation frequency | 5.8GHz +/-75MHz | |
Transmission power | <0.2mW | |
Detection range | Max. (Ø x H) 8m x 5m | |
Detection angle | 30°~150° | |
Setting adjustments: | ||
Sensitivity | 50%/100% | 50%/100% |
Hold time | 5s~10min (selectable) | 5s~10min (selectable) |
Daylight threshold | 2~50 lux, disabled | 2~50 lux, disabled |
Stand-by period | 0s/30s/10min / +∞ | 0s/30s/10min / +∞ |
Stand-by dimming level | 10% / 30% | 10% / 30% |
Safety and EMC
EMC standard (EMC) | EN55015, EN61547, EN6100-2/3 | |
Safety standard (LVD) | EN61347-1, EN61347-2-13 | |
Dielectric strength | Input output: 3750VAC / 5mA/1min | |
Abnormal protection | Output short-circuit protection | |
Certification | Semko, CB, CE, EMC, RED, SAA |
Environment
Operation temperature | Ta: -20°C ~ +50°C |
Case temperature (Max.) | Tc: +75°C |
IP rating | IP20 |
CE ? emc RED SAA CB IP20
Functions and Features
Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light -->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
With sufficient natural light, the light does not switch on when presence is detected.
With insufficient natural light, the sensor switches on the light automatically when presence is detected.
After hold-time, the light dims to stand-by level preset.
Light switches off automatically after the stand-by period elapses.
Assembly
The sensor antenna features the DIP switches (or rotary switch) and protrudes the LED panel. This feature enables the end user to access the sensor settings without removing the gear tray / LED board.
The QR code links the installer to the user manual on the on-line user guide to check the detail of settings (program).
Cut-out size: 36 x 29.5 (mm)
Detection Pattern
Ceiling mounted detection pattern (m)
Wall mounted detection pattern (m)
DIP Switch Settings
-
Detection Range
Sensor sensitivity can be adjusted by selecting the combination on the DIP switches to fit precisely for each specific application.
I II III IV 100% ● 50% ● 1-100% ● II-50% ● -
Hold Time
Select the DIP switch configuration for the light on-time after presence detection. This function is disabled when natural light is sufficient.
I II III IV 1-5s ● II-30s ● III- 3min ● IV-10min ● -
Daylight Threshold
Set the level according to the fixture and environment. The light will not turn on if ambient lux level exceeds the daylight threshold preset. Please note that the ambient lux level refers to internal light reaching the sensor. Disabling the daylight sensor will put the sensor into occupancy detection only mode.
I II III IV Disable ● II-50Lux ● III- 10Lux ● IV- 2Lux ● -
Stand-by period (corridor function)
This is the time period you would like to keep at the low light output level before it is completely switched off in the long absence of people. Note: "0s" means on/off control; "+∞" means the stand-by period is infinite and the light never switches off but stays at dimming level.
I II III IV 0s ● II-30s ● III- 10min ● IV- +∞ ● -
Stand-by dimming level
The setting is used to select the desired dimmed light level used in periods of absence for enhanced comfort and safety.
I II 10% ● 30% ●