Braeburn 3020 & 3220 Detailed Installer Guide
This guide provides detailed instructions for installing Braeburn 3020 and 3220 non-programmable thermostats.
Models Covered:
- 3020: Single Stage Heat / Cool Conventional or Heat Pump
- 3220: Up to 3 Heat / 2 Cool Heat Pump, Up to 2 Heat / 2 Cool Conventional
Model numbers are located on the back of the thermostat.
1 Specifications
This thermostat is compatible with:
- Single stage heat / cool conventional and heat pump systems
- Conventional systems up to 2 stages of heating and 2 stages of cooling (3220 only)
- Heat pump systems up to 3 stages of heating and 2 stages of cooling (3220 only)
- 250 - 750 millivolt heating only systems
- 2 or 3 wire hydronic zone systems
Electrical and Control Specifications:
- Electrical Rating: 24 Volt AC
- 1 amp maximum load per terminal
- AC Power: 18 - 30 Volts AC
- DC Power: 3.0 Volt DC (2 "AA" Alkaline Batteries Included)
- Control Range: 45°-90°F (7°-32°C)
- Temperature Accuracy: +/- 1°F (+/- 0.5°C)
- Outdoor Temperature Display Range: -40°-120°F (-40°-49°C)
Terminations:
- 3020: G, Rc, Rh, W1, O/B/V3, Y1, C, S1, S2
- 3220: G, Rc, Rh, W1/E/W3, W2, O/B/V3, Y1, Y2, C, L, S1, S2
2 Installation and Wiring
Warning: Disconnect power before beginning installation.
Thermostat Location
Install the thermostat approximately 5 feet (1.5 m) above the floor in an area with good air circulation and consistent room temperature. Avoid locations affected by drafts, direct sunlight, heat or cold air ducts, appliances, or exterior walls.
Installation Steps:
- Install the Sub-Base
- Provide Power
- Connect Your Wires
- Attach Thermostat to Sub-Base
1. Install the Sub-Base:
Remove the sub-base from the thermostat body. Mount the sub-base securely to the wall. Drill 3/16" pilot holes as needed, using supplied anchors for drywall or plaster.
2. Provide Power:
The thermostat requires 24 Volt AC Power or 2 "AA" Alkaline batteries. Batteries can be installed as a backup when using 24 Volt AC power.
- For 24 Volt AC Power: Connect the common wire from the transformer to the 'C' terminal on the thermostat sub-base. For dual transformer systems, the common must come from the cooling transformer.
- For Battery Power: Insert 2 "AA" alkaline batteries into the battery compartment, ensuring correct polarity (+/-).
3. Connect Your Wires
Wiring Terminations for Model 3020:
Terminal | Function | Description |
Rc | Input | 24 Volt AC Cooling Transformer (Dual Transformer Systems Only) |
Rh | Input | Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source) |
G | Output | Fan Control |
W1 | Output | Conventional Heat Relay |
O / B / V3 | Output | (O) Cool Active Reversing Valve, (B) Heat Active Reversing Valve, (V3) Zone Valve Power Close |
Y1 | Output | Compressor Relay |
C | Input | 24 Volt AC Transformer Common |
S1 | Input | Optional Remote Sensor (indoor or outdoor) |
S2 |
Wiring Terminations for Model 3220:
Terminal | Function | Description |
Rc | Input | 24 Volt AC Cooling Transformer (Dual Transformer Systems Only) |
Rh | Input | Power Connection (24 Volt AC Heating Transformer or Millivolt Power Source) |
G | Output | Fan Control |
W1 / E / W3 | Output | (W1) 1st Stage Conventional Heat, (E) Emergency Heat, (W3) 3rd Stage Auxiliary Heat |
W2 | Output | 2nd Stage Conventional Heat |
O / B / V3 | Output | (O) Cool Active Reversing Valve, (B) Heat Active Reversing Valve, (V3) Zone Valve Power Close |
Y1 | Output | 1st Stage Compressor |
Y2 | Output | 2nd Stage Compressor |
L | Input | System Malfunction Indicator |
C | Input | 24 Volt AC Transformer Common |
S1 | Input | Optional Remote Sensor (indoor or outdoor) |
S2 |
Typical Wiring Configurations - Conventional Systems
Note: The "System Type" option is configured in the Installer Settings. The 3020 is single-stage.
Heat Only or Millivolt:
Set System Type to 11CONV
Terminal | Function |
Rh | Power Connection |
W1 | Heat Relay |
G | Fan Relay [note 4] |
C | 24 Volt AC Transformer Common [note 1] |
1 HEAT / 1 COOL Single or Dual Transformer:
Set System Type to 11CONV
Terminal | Function |
Rh | 24 Volt AC Power (heating transformer) [note 2] |
Rc | 24 Volt AC Power (cooling transformer) [note 2] |
W1 | Heat Relay |
Y1 | Compressor Relay |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1, 3] |
2 HEAT / 2 COOL Single or Dual Transformer:
Set System Type to 22CONV
Terminal | Function |
Rh | 24 Volt AC Power (heating transformer) [note 2] |
Rc | 24 Volt AC Power (cooling transformer) [note 2] |
W1 | Heat Relay Stage 1 |
W2 | Heat Relay Stage 2 |
Y1 | Compressor Relay Stage 1 |
Y2 | Compressor Relay Stage 2 [note 4] |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1, 3] |
Hydronic Heat Only:
Set System Type to 1HD
Terminal | Function |
Rh | 24 Volt AC Power (heating transformer) |
W1 | Zone Valve Power Open |
V3 | Zone Valve Power Close |
G | Fan Relay [note 4] |
C | 24 Volt AC Transformer Common [note 1] |
Hydronic Heat / 1 Cool:
Set System Type to 11HD
Terminal | Function |
Rh | 24 Volt AC Power (heating transformer) [note 2] |
Rc | 24 Volt AC Power (cooling transformer) [note 2] |
W1 | Zone Valve Power Open |
V3 | Zone Valve Power Close |
Y1 | Compressor Relay |
G | Fan Relay (cooling fan only) |
C | 24 Volt AC Transformer Common [note 1, 3] |
Notes - Conventional Systems:
[1] Optional 24 Volt AC common connection.
[2] Remove factory installed jumper for dual transformer systems.
[3] In dual transformer systems, transformer common must come from the cooling transformer.
[4] If needed for system. Provide disconnect and overload protection as required.
Additional Wiring Options:
Note: Additional options are configured in the Installer Settings section.
Terminal | Function |
S1 | Indoor or Outdoor Remote Sensor [note 1] |
[1] These terminals can be used to connect a Braeburn ® indoor or outdoor remote sensor.
Typical Wiring Configurations - Heat Pump Systems
Note: The "System Type" option is configured in the Installer Settings. The 3020 is single-stage.
1 HEAT / 1 COOL - No Auxiliary Heat:
Set System Type to 11HP
Terminal | Function |
Rh | 24 Volt AC Power |
Rc | Connected to Rh with supplied Jumper Wire |
O / B | Changeover Valve [note 2] |
Y1 | Compressor Relay |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1] |
2 HEAT / 2 COOL - No Auxiliary Heat:
Set System Type to 32HP
Terminal | Function |
Rh | 24 Volt AC Power |
Rc | Connected to Rh with supplied Jumper Wire |
O / B | Changeover Valve [note 2] |
Y1 | Compressor 1 Relay (1st stage heating/cooling) |
Y2 | Compressor 2 Relay (2nd stage heating/cooling) |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1] |
L | Optional System Fault Monitor [note 4] |
2 HEAT / 1 COOL - Including Auxiliary Heat:
Set System Type to 22HP
Terminal | Function |
Rh | 24 Volt AC Power |
Rc | Connected to Rh with supplied Jumper Wire |
O / B | Changeover Valve [note 2] |
Y1 | Compressor Relay (1st stage heating/cooling) |
W2 | Auxiliary Heat Relay (2nd stage heating) [note 3] |
E | Emergency Heat Relay [note 3] |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1] |
L | Optional System Fault Monitor [note 4] |
3 HEAT / 2 COOL - Including Auxiliary Heat:
Set System Type to 32HP
Terminal | Function |
Rh | 24 Volt AC Power |
Rc | Connected to Rh with supplied Jumper Wire |
O/B | Changeover Valve [note 2] |
Y1 | Compressor 1 Relay (1st stage heating/cooling) |
Y2 | Compressor 2 Relay (2nd stage heating/cooling) |
E/W3 | Auxiliary Heat Relay (3rd stage heating) [note 5] |
G | Fan Relay |
C | 24 Volt AC Transformer Common [note 1] |
L | Optional System Fault Monitor [note 4] |
Notes - Heat Pump Systems:
[1] Optional 24 Volt AC common connection.
[2] O (cool active) or B (heat active) is selected in the Installer Settings menu.
[3] Install a field supplied jumper between the W2 and W1/E/W3 terminals if there is no separate emergency heat relay installed.
[4] If the L terminal is used, the 24 Volt AC common must be connected (C terminal).
[5] If a separate emergency heat relay is installed, the W1/E/W3 terminal should have both the auxiliary heat 1 relay and emergency heat relay connected. Provide disconnect and overload protection as required.
Notes - Additional Wiring Options:
[1] These terminals can be used to connect a Braeburn ® indoor or outdoor remote sensor.
4 Attach Thermostat to Sub-Base
- Line up the thermostat body with the sub-base.
- Carefully push the thermostat body against the sub-base until it snaps in place.
- Insert Quick Reference Card into the slot on top of the thermostat.
Note: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings.
Thermostat and Display Overview:
- 1 Room Temperature: Displays the current room temperature.
- 2 Set Temperature: Displays the current set point temperature.
- 3 Reset Button: Resets current time, program, and user settings.
- 4 SYSTEM Button: Selects the system mode (Heat, Cool, Off, Auto).
- 5 BACK Button: Moves back in setup modes.
- 6 NEXT Button: Moves forward in setup modes.
- 7 RETURN Button: Returns to normal mode from setup modes.
- 8 Service Indicators: Displays service/maintenance information.
- 9 FAN Button: Selects the fan mode (Auto, On).
- 10 Quick Reference Instructions: Stored in the slot at the top of the thermostat.
- 11 Low Battery Indicator: Shows when batteries need replacement.
- 12 Fan Indicator: Shows when the system fan is running.
- 13 System Status Indicator: Displays system status information.
- 14 Lock Mode Indicator: Indicates if the thermostat is locked.
- 15 SpeedBar (↑/↓): Increases or decreases settings (time, temperature, etc.).
- 16 Outdoor Temperature Indicator: Displays outdoor temperature if a sensor is connected.
- Battery Compartment: Located in the back of the thermostat.
Note: To view outdoor temperature (if a Braeburn ® outdoor sensor is connected), press the BACK and NEXT buttons simultaneously.
4 Installer Settings
Installer Settings must be configured correctly for proper operation. These settings are menu-driven.
Accessing Installer Settings:
- Press and hold the RETURN and ↓ buttons for 3 seconds.
- Release both buttons. The first installer setting will be displayed.
- Change settings using the ↑ or ↓ portion of the SpeedBar ®.
- Press NEXT or BACK to navigate between settings. Press RETURN to exit.
Note: Shaded areas in the table below do not apply to the 3020 model.
No. | Installer Setting | Factory Default | Setting Options | Comments |
1 | Temperature Scale | F/C | F / C | Select Fahrenheit or Celsius display. |
2 | Auto Changeover | OFF / AUTO | OFF / AUTO | Disables or enables Auto Changeover mode. |
3 | System Type | 11COMU | 11COMU, 22COMU, 11HP, 22HP, 32HP, 1HD, 11HD | Selects the system type (Conventional, Heat Pump, Hydronic). |
4 | 1st Stage Differential | 0.5 DIF1 | 0.5°, 1.0°, 2.0° F (0.2°, 0.5°, 1.0° C) | Selects the 1st stage temperature differential. |
5 | 2nd Stage Differential [note 1] | 2.0 DIF2 | 1.0° to 6.0° F (0.5° to 3.0° C) | Selects the 2nd stage temperature differential. |
6 | 3rd Stage Differential [note 1] | 2.0 DIF3 | 1.0° to 6.0° F (0.5° to 3.0° C) | Selects the 3rd stage temperature differential. |
7 | 1st Stage Fan Control [note 2] | HG FAM 1 | HG FAM 1 / HE FAM 1 | Selects 1st stage Gas or Electric heat fan control. |
8 | Emergency Heat Fan Control [note 3] | HE E/NER | HE E/NER / HG E/NER | Selects Electric or Gas Emergency Heat fan control. |
9 | Reversing Valve (O/B Terminal) [note 4] | REUO | REUO (Cool Active) / REUB (Heat Active) | Selects the reversing valve state for cool or heat mode. |
10 | Fossil Fuel Backup Heat [note 3] | RE AUX | RE AUX (Electric) / RG AUX (Gas) | Selects Electric or Gas Auxiliary heat. |
11 | Compressor Power Outage Protection [notes 3, 5] | OFF CPOP | OFF CPOP / CPOP | Enables or disables compressor protection after power outages. |
12 | AC Power Interrupt Warning [note 5] | RC OF NOMR | RC OF NOMR / RC or NOMR | Enables or disables AC power interrupt warnings. |
13 | Compressor Short Cycle Protection [note 6] | 5 CSCP | 0 to 5 minutes | Selects compressor lockout delay to prevent short cycling. |
14 | Residual Cooling Fan Delay [note 6] | 60 FAM | 0, 30, 60, 90 seconds | Selects fan delay after cooling compressor shuts off. |
15 | Indoor Remote Sensor Control [note 7] | ISEMS | I SEMS (Thermostat only), E SEMS (Remote only), A SEMS (Combined) | Configures temperature sensing with remote sensors. |
16 | Lockout Security Level | 2 LOCK | 2 LOCK (Full) / 1 LOCK (Partial) | Sets the level of keypad lockout. |
17 | Auto Changeover Dead Band [note 8] | 3 BAMD | 2° to 5° F (1° to 3° C) | Sets the temperature separation for Auto Changeover mode. |
18 | Compressor Balance Point [notes 3, 9] | MO BRLC | MO BRLC (Disabled) / 15°-50° F (-9°-10° C) | Locks out compressor heat stage based on outdoor temperature. |
19 | Auxiliary Heat Balance Point [notes 3, 9] | MO BRLR | MO BRLR (Disabled) / 70°-40° F (21°-4° C) | Locks out auxiliary heat stage based on outdoor temperature. |
20 | Heat Set Point Upper Limit | 90 LIN | 60°-90° F (10°-32° C) | Sets the maximum adjustable heat set point. |
21 | Cool Set Point Lower Limit [note 6] | 45 LIN | 45°-80° F (7°-27° C) | Sets the minimum adjustable cool set point. |
*When a Braeburn ® outdoor sensor is connected, the thermostat automatically recognizes it. Press BACK and NEXT at the same time to display outdoor temperature.
Notes - Installer Settings:
1 Only available if a 2 or 3 stage system type was selected in option 3.
2 Only available if a Conventional system was selected in option 3.
3 Only available if a 2 or 3 stage Heat Pump system was selected in option 3.
4 Only available if a Heat Pump system was selected in option 3.
5 Only available if the 24 Volt AC common wire is connected to the C terminal.
6 Not available if a Heat Only Hydronic system is selected in option 3.
7 Only available if a Braeburn ® indoor remote sensor was connected.
8 Only available if auto changeover was enabled in option 2.
9 Only available if a Braeburn outdoor sensor was connected.
Detailed Explanation of Installer Settings:
- Temperature Scale: Selects the display scale in °F or °C.
- Auto Changeover: Enables or disables the automatic switching between heating and cooling modes. A 5-minute delay is active when switching modes.
- System Type: Configures the thermostat for the specific HVAC system. Changes here may reset other settings.
- 1st Stage Differential: Sets the temperature difference for the first stage of heating or cooling.
- 2nd Stage Differential: Sets the temperature difference for the second stage of heating or cooling.
- 3rd Stage Differential: Sets the temperature difference for the third stage of heating or cooling.
- 1st Stage Fan Control: Selects the fan control type for the first stage of heating (Gas or Electric).
- Emergency Heat Fan Control: Selects the fan control type for emergency heat (Electric or Gas).
- Reversing Valve (O/B Terminal): Configures the O/B terminal for cool-active or heat-active reversing valve operation.
- Fossil Fuel Backup Heat: Selects the type of auxiliary heat (Electric or Gas) for heat pump systems.
- Compressor Power Outage Protection: Enables or disables a delay for the compressor after a power outage to prevent damage.
- AC Power Interrupt Warning: Enables or disables a warning message when AC power is lost.
- Compressor Short Cycle Protection: Sets a delay to prevent the compressor from cycling on and off too rapidly.
- Residual Cooling Fan Delay: Sets a delay for the fan after the cooling compressor turns off to improve efficiency.
- Indoor Remote Sensor Control: Configures how the thermostat uses readings from an indoor remote sensor (thermostat only, remote only, or combined).
- Lockout Security Level: Sets the level of keypad lockout (full or partial).
- Auto Changeover Dead Band: Sets the temperature difference between heating and cooling set points in Auto Changeover mode to prevent system conflict.
- Compressor Balance Point: Locks out the compressor's heating function below a specified outdoor temperature.
- Auxiliary Heat Balance Point: Locks out the auxiliary heat function above a specified outdoor temperature.
- Heat Set Point Upper Limit: Sets the maximum adjustable temperature for heating.
- Cool Set Point Lower Limit: Sets the minimum adjustable temperature for cooling.
5 System Testing
Warning: Read Before Testing
- Do not short terminals on the gas valve or control board.
- Do not select COOL mode if the outside temperature is below 50°F (10°C).
- The thermostat has an automatic compressor protection delay.
Note: The compressor delay can be bypassed by pressing the reset button. This will reset user settings but retain installer settings.
Testing Procedure:
- Heat Mode: Press SYSTEM until HEAT mode is selected. Raise the set temperature at least 3°F above the room temperature. The heating system should start.
- Off Mode: Press SYSTEM to turn the system OFF. Allow the heating system to shut down.
- Cool Mode: Press SYSTEM until COOL mode is selected. Lower the set temperature at least 3°F below the room temperature. The cooling system should start (unless compressor protection is active).
- Off Mode: Press SYSTEM to turn the system OFF. Allow the cooling system to shut down.
- Fan ON Mode: Press FAN until FAN ON is selected. The system fan should start.
- Fan AUTO Mode: Press FAN until FAN AUTO is selected. Allow the system fan to turn off.
Limited Warranty
When installed by a professional contractor, this product is backed by a 5-year limited warranty. For full warranty details, visit www.braeburnonline.com/warranty or contact Braeburn Systems LLC at 866.268.5599.
Store this manual for future reference.
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S.)
630-844-1968 (Outside the U.S.)