Owner's Manual for Honeywell models including: SS3 Digital Multi Spectrum Electro Optical Fire and Flame Detectors, SS3, Digital Multi Spectrum Electro Optical Fire and Flame Detectors, Electro Optical Fire and Flame Detectors, Fire and Flame Detectors

Click here to download

Honeywell Fire Sentry SS3 Fire and Flame Detectors - Fire Alarm Resources - Free fire alarm PDF manuals, documents, installation instructions, and technical specifications


File Info : application/pdf, 4 Pages, 1.13MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676770230
Fire Sentry SS3 Fire and Flame Detectors
Digital Multi-Spectrum Electro-Optical Fire and Flame Detectors firealarmresources.com

Fire Sentry SS3 Detectors

Features:
·Multi-SpectrumTMsensesenergyinthe ultraviolet, Visible and Wide Band InfraredTM
·Falsealarmimmunity ·Detectshydrocarbonand
non-hydrocarbonfires ·Microprocessorbasedalgorithms:
FirePicTMandTri-ModePlotTM ·Widefield-of-view ·FS2000TMSystemcompatibleorstand
alone operation
·Compatiblewithapproved fire alarm panels

Fire Sentry SS3 Multi-Spectrum Optical Fire and Flame Detectors are fast reacting, digital, reprogrammable, computerized -- smart technology.
The Fire Sentry SS3 fast-reacting, Ultraviolet (UV), Wide Band Infrared (IR) and Visible spectral brand electro-optical digital fire and flame detectors are designed to alarm on all types of fires. They have an alarm range of 30 ft for a one square foot gasoline reference fire with a 120° circular field of view coverage.

Applications include:
·Warehouses ·ConventionCenters ·ComputerRooms ·Hospitals ·TelephoneSwitchingStations

firealarmresources.com

Fire Sentry SS3 Detectors
To eliminate common nuisance false alarms that occasionally occur with UV-only, IR-only, Dual IR or Dual Mode UV/IR detectors, the Fire Sentry SS3 detectors' FireLogic signal processing requires that UV, visible and Wide Band IR radiant energy all be evaluated before declaring a fire. The smart detector utilizes real-time signal processing algorithms that are optimized to alarm on all types of fires, while virtually eliminating the possibility of false alarms. The Fire Sentry SS3 detectors perform the same whether they are connected to the FS2000 Fire Early Warning System (with CM1-A Controller and FireBus) or whether they operate in the stand-alone mode. The only difference between FS2000 System model and the stand-alone models is how each is wired. The Fire Sentry SS3 detectors are available in latching (Fire Sentry SS3-A) and non-latching (Fire Sentry SS3-AN) models.
firealarmresources.com

General Specifications Sensitivity Response Time Field-of-View Spectral Sensitivity
Input Power Power Consumption Output Relays
Operating Temperature Housing Weight Dimensions Mounting Warranty

1 sq. ft. gasoline fire at 30 feet within 5 seconds

2-5 seconds to 1 sq. ft. of gasoline fire at 30 ft.

SS3-A (UV/IR):120 degrees cone of vision (±60 degrees from on axis)

SS3-AB (UV): 180 degrees cone of vision (± 90 degrees from on axis)

Ultraviolet:

185 to 260 nanometers

Wide Band Infrared:

0.7 to 3.5 micrometers (SS4-A only)

Visible:

400 to 700 nanometers (SS4-A only)

24 VDC nominal

12V minimum, 28V maximum

18 mA normal operation, typical

55 mA alarm condition, typical

Fire Alarm Relay:

NO & NC contacts

Latching / Non-Latching, switch selectable

Relay contact ratings:

0/5A at 120 VAC, 1.0A at 24VDC

Fire alarm relay is de-energized during normal operation

Operartion: -32 to 170°F (0 to 77°C)

Storage: -4 to 185°F (-20 to 85°C)

NEMA 1 high impact ABS; general purpose indoor use only

12 ounces (0.340 kg)

4 x 5.25 x 1.75 in.

Installs on a wall, ceiling, etc. with the included mounting bracket or on two

properly spaced panhead screws using the Detector's double keyhole

One years from factory shipping date

5.25 LED

2.00 4.00

1.77

0.13

GENERAL DIMENSIONS

2.80

1.75 2.00

LED

1.77

0.13

Rear View SS3-AB & SS3-ABN

Side View SS3-AB & SS3-ABN

0.29 5.25

1.16 LED

2.00

0.96

1.77

0.13

SS3-A & SS3-AN Front SS3-A & SS3-AN Side

1.0
5.070 4.310

0.55
0.190 1.250

0.330 1.40

2.87

1.27

SS3-AB & SS3-ABN Domed Mounted Bracket

Customer business centre
Korea: +82-2-69090300 Singapore: +65-65803776 Australia: +61-3-94642770 Taiwan: +886-3-5169284 China: +86-21-28943293

Technical Services AP: ha.ap.service@honeywell.com EMEA: ha.emea.service@honeywell.com US: ha.us.service@honeywell.com
www.honeywell.com

Please Note: While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines.This publication is not intended to form the basis of a contract.
SS01142_v1 09/12 © 2012 Honeywell Analytics

firealarmresources.com



References

Adobe PDF Library 9.9 Adobe InDesign CS5 (7.0.2)