Rheem Indirect Water Heater Instruction Manual

This manual provides essential information for the installation, operation, and maintenance of Rheem Indirect Water Heaters. Please read and retain for future reference.

To the Installer

Please attach these instructions next to the indirect water heater.

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause serious injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer or service agency.

CAUTION: The recommended temperature for normal residential use is 120°F. The dial on the aquastat does not always reflect the out-coming water temperature, which could occasionally exceed 120°F. The variation in out-coming temperature could be based on factors including but not limited to usage patterns and type of installation. Test your water at the tap nearest to the indirect water heater.

WARNING: Hotter water increases the risk of scald injury. Before adjusting the water temperature setting, read this instruction manual. Temperatures at which injury occurs vary with the person's age and the length of exposure.

The slower reaction time of children, elderly, and physically or mentally challenged persons increases the scalding hazard to them. It is recommended that lower water temperatures be used where these exposure hazards exist. Such households may require a temperature setting less than 120°F to prevent accidental contact with hot water.

To lower water temperature use point-of-use temperature limiting devices.

WARNING: Water heater blankets are not recommended and will void the warranty.

This manual has been prepared to acquaint you with the installation, operation, and maintenance of your indirect water heater and to provide important safety information.

To the Consumer

Please read these and all component instructions and keep for future reference.

Indirect Water Heater Instruction Manual

Warranty and Parts List are included.

Installer Responsibilities

Please read all instructions thoroughly before installing or placing the indirect water heater into service. This unit must be installed by licensed or authorized installers, or technical personnel that service water heating equipment. The indirect water heater must be installed in accordance with all local codes and ordinances.

These instructions are a guide for the correct installation of the indirect water heater. The manufacturer will not be liable for damages caused by failure to comply with the installation and operating instructions outlined on the following pages.

CAUTION: The recommended water temperature setting for normal residential use is 120°F/49°C.

Handling

Before uncrating, check for shipping damage. Report any damage to your carrier. Note damage on bill of lading or delivery receipt and file a claim.

FAILURE TO FOLLOW THESE INSTRUCTIONS OR ALL APPLICABLE BUILDING CODES AND REGULATIONS VOIDS THE WARRANTY ON THIS INDIRECT WATER HEATER.

Read all instructions thoroughly before attempting installation or operation of your indirect water heater. Keep these instructions for future reference.

Local plumbing and electrical codes must be followed in the installation of this indirect water heater. In the absence of a local code use the UNIFORM PLUMBING CODE and the NFPA Code. Local codes may supersede instructions in this installation manual.

These instructions are a guide for the correct installation of the indirect water heater. The manufacturer will not be liable for damages caused by failure to comply with the installation and operating instructions outlined on the following pages.

Section I: Specifications

Figures and Dimensions

Figure 1 illustrates the port layout for models STID30, STID40, and STID50. Figure 2 illustrates the port layout for models STID80 and STID120. Key ports include Hot Outlet, Anode Rod, Cold Inlet, T&P Relief Valve, Drain Valve, and connections for Boiler Supply and Return.

ModelABCDEFGH
STID3022"35 1/4"27 3/4"19 1/2"11 1/4"6 1/2"4 1/2"n/a
STID4022"42 1/4"34 3/4"31 1/2"16 3/4"6 1/2"4 1/2"n/a
STID5022"48 1/4"39 3/4"31 1/2"16 3/4"6 1/2"4 1/2"n/a
STID8024"64"57 1/8"33"19 1/4"8"5"5"
STID12028"65"57 3/4"33 3/4"16 1/4"8 3/4"5"6 1/2"

Foam insulation is standard on all indirect water heater models. Working pressure is 150 PSI. Standard voltage is 120V, 60Hz, 1P. T&P valves are factory installed with nipples supplied for top connection.

WARNING: Installation should be in accordance with all national and/or local codes.

CAUTION: The recommended water temperature setting for normal residential use is 120°F. Rheem recommends a tempering valve or anti-scald valve be installed and used according to the manufacturer's directions to prevent scalding.

Section I: Specifications (cont.)

Capacity & Performance

ModelActual Tank Volume (gal)Coil Volume (gal)CapacitiesPerformance
First Hour Rating (gal)*Continuous Draw Rating (GPH)*First Draw Rating (gal)*Minimum Coil Output (BTU/Hr)**Standby Loss Rating (°F/hr)Heat Source Friction Loss (ft. w.c.)
STID30301.38110852555,0001.32.0
STID40382.301531203377,0001.13.0
STID50452.301601204077,0001.03.0
STID80752.762001307083,0000.95.0
STID1201102.7623213010283,0001.25.0

NOTES: * Based on 77°F rise with 58°F potable water inlet temperature at 8 GPM heat source flow rate. Heat source temperature was 180°F. ** Minimum Coil output based on continuous boiler operation over 30 minutes. See Section III for additional considerations. All data obtained through testing in accordance with GAMA Indirect Water Heater-FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003

Performance (cont.)

ModelFIRST HOUR RATING (gal) @ Coil Output (Btu/hr)
180°F 6 GPM*180°F 10 GPM*180°F 12 GPM*200°F 6 GPM*200°F 8 GPM*200°F 10 GPM*200°F 12 GPM*
STID30107 @ 53,000114 @ 57,000117 @ 59,000129 @ 67,000132 @ 69,000136 @ 71,000139 @ 73,000
STID40141 @ 69,000165 @ 84,000177 @ 92,000171 @ 88,000183 @ 96,000195 @ 104,000207 @ 111,000
STID50148 @ 69,000172 @ 84,000184 @ 92,000178 @ 88,000190 @ 96,000202 @ 104,000214 @ 111,000
STID80188 @ 76,000212 @ 91,000224 @ 98,000221 @ 97,000233 @ 104,000245 @ 112,000257 @ 119,000
STID120220 @ 76,000244 @ 91,000256 @ 98,000253 @ 97,000265 @ 104,000277 @ 112,000289 @ 119,000

NOTES: First Hour Rating = First Draw + Continuous Draw. * Coil Input (temperature, flow rate). Ratings based on 77°F rise with 58°F inlet potable water. All data obtained through testing in accordance with GAMA Indirect Water Heater -FIRED WATER HEATER TESTING STANDARD IWH-TS-1_MARCH 2003

Section II: General Information

Location

The indirect water heater should be located in a central location to the piping system, as close as practical to the boiler and in an area not subject to freezing temperatures. Leave sufficient space for servicing and maintaining the indirect water heater.

NOTICE: Long heating supply runs can lengthen recovery times.

Water Treatment/Filtration

In areas where poor water conditions are suspected (i.e. lime, iron, and other minerals), it is essential that the water be tested and appropriate action taken to prevent damage to the indirect water heater and ensure the quality of the water.

Temperature Control

Water temperature from the heat source / boiler to the indirect water heater is controlled by an immersion aquastat. This control operates the circulator, and provides limited control for domestic hot water temperature. The proper temperature setting for domestic hot water use is 120°F/49°C. If hotter water is required a tempering device or anti-scald device must be installed at the domestic hot water outlet of the indirect water heater or at the point of use.

CAUTION: Hot water in excess of 120°F can cause scalding!

Rheem recommends a tempering valve or anti-scald valve be installed and used according to the manufacturer's directions to prevent scalding. Many state and local codes now require installation of these devices. The tempering valve or anti-scald valve will ensure potable water temperatures at the desired set point with a higher degree of accuracy.

Approximate Temperature/Time Relationships to Scalding

TemperatureTime to Cause Scald
120°FMore than 5 minutes
125°F1 1/2 to 2 minutes
130°FAbout 30 seconds
135°FAbout 10 seconds
140°FLess than 5 seconds
145°FLess than 3 seconds
150°FAbout 1 1/2 seconds
155°FAbout 1 second

Immersion Control

Diagram shows immersion control for STID30, STID40, STID50, STID80, STID120. Temperature setting is 120°F for all models with a fixed differential of 8°F.

Section II: General Information (cont.)

Anode Rods

The anode rod is used as a sacrificial element within the storage tank to protect against corrosion. Anode rods should be inspected twice in the first year and at least yearly. Water conditions affect consumption rate. See the Maintenance section for replacement instructions.

CAUTION: Hydrogen gas is produced in a hot water system not used for a long period (2 weeks or more). Hydrogen gas is extremely flammable. To reduce risk, open a hot water faucet for several minutes before using electrical appliances connected to the system. Listen for escaping air; do not smoke or use open flames near the faucet.

Temperature and Pressure Relief Valve (T&P)

The T&P valve is factory installed. A discharge drain tube must be installed, terminating plain, 6 inches above the floor drain. The drain tube material must be approved for temperatures of 120°F or greater, and a pressure of 150 PSI or greater.

Back-Flow Preventor (Closed Loop System)

Some local codes require back-flow preventors on potable water lines. If required, install a thermal expansion tank (designed for potable water) to prevent pressure buildup that could cause the T&P valve to discharge. Follow expansion tank manufacturer's recommendations.

NOTICE: Working pressure of the indirect water heater is 150 PSI. Do not exceed 150 PSI.

Section III: Pre-Installation

Boiler and Circulator Sizing

Ratings in this manual are based on proper selection of boiler output and circulator capacity. Table 2 ratings are based on a 77°F rise with 58°F potable water inlet temperature at an 8 GPM circulator pump flow rate, with the boiler set at 180°F. Table 3 provides additional first hour ratings at various flow rates and boiler water temperatures.

To determine the appropriate circulator, follow these steps:

  1. Calculate the pressure drop of all straight pipe and fittings on the supply and return at the desired flow rate.
  2. Add the pressure drop from Step 1 to the pressure drop through the indirect water heater coil (see Table 2 for friction loss) to obtain a total pressure drop.
  3. Select a circulator pump that will provide adequate flow at the total pressure drop.

A pump performance curve should accompany every circulator pump. Figures 3-5 contain performance curves for Taco and Grundfos circulator pumps, recommended by Rheem.

Figure 3: Taco 00 Series Performance Curves

This graph illustrates the performance curves for Taco 00 Series circulator pumps, showing Total Head (feet) versus Flow (GPM) and Flow (m³/h).

Figure 4: GRUNDFOS UP 15-42F Performance Curve

This graph illustrates the performance curve for the GRUNDFOS UP 15-42F circulator pump, showing Head (ft) versus Flow (US GPM) for closed systems at 60 Hz.

Figure 5: GRUNDFOS UP 26-64F Performance Curve

This graph illustrates the performance curve for the GRUNDFOS UP 26-64F circulator pump, showing Head (ft) versus Flow (US GPM) for closed systems at 60 Hz.

NOTICE: Zone valves on the heat source supply to the indirect water heater are not recommended and will drastically reduce performance.

System performance can also vary based on the heating capacity of the boiler. If the minimum coil output (assume coil output = boiler output) listed in Tables 2 and 3 is not met, the output (first hour rating) of the indirect water heater will not be met at the selected flow rate. To approximate the reduction in first hour rating as a result of low boiler capacity, use the following formula:

New first hour rating = (First hour rating) * (Actual boiler output)/(Minimum coil output)

For example, the first hour rating of a STID50 at a 77°F rise with an 8 GPM heat source flow rate using a boiler having a DOE heating capacity (output) of 60,000 BTU/Hr would be: New first hour rating = (160 gal) * (60,000 BTU/Hr)/(77,000 BTU/Hr) = 125 gal

Section IV: Installation

Water Connections

Piping between the boiler and the indirect water heater should be new copper: 3/4" ID for STID30, STID40, STID50; 1" ID for STID80, STID120. Minimize elbows. Install a flow check valve on the return line.

Domestic water connections (cold inlet and hot outlet) should be new copper: 1/2" ID for STID30, STID40, STID50; 3/4" ID for STID80, STID120.

All piping must conform to local codes and ordinances. If no local codes apply, refer to ILHR 84. Insulate all piping with approved material to ensure minimum heat loss. If a re-circulation line is used, ensure it is well insulated and the circulator is temperature controlled.

Install isolation valves for servicing. Consider installing a union on the domestic outlet for easier replacement of the hot outlet / anode nipple on STID30, STID40, and STID50 models.

Figure 6: STID30, STID40, STID50 Water Connections

Diagram shows water connections for STID30, STID40, STID50 models, illustrating connections for Domestic Hot Out (3/4"), Cold Inlet (3/4"), Boiler System Supply (1" NPT), Boiler System Return (1" NPT), Circulator Pump, Indirect Water Heater, Boiler, and a Check Valve.

Figure 7: STID80, STID120 Water Connections

Diagram shows water connections for STID80, STID120 models, illustrating connections for Domestic Hot Out (1 1/2"), Cold Inlet (1"), Boiler System Supply (1" NPT), Boiler System Return (1" NPT), Circulator Pump, Indirect Water Heater, Boiler, and a Check Valve.

NOTICE: An indirect water heater may be connected to a steam boiler provided all piping to and from the boiler is below the boiler's water line. The boiler must also be protected by a low water cut-off safety device.

Figure 8: Rheem Indirect Water Heater with Low-Mass Boiler

Diagram illustrates piping for a Rheem indirect water heater connected to a low-mass boiler, showing components such as Isolation Valves, Additional Zones, Boiler, Circulator, Air Vent, Air Separator, Expansion Tank, Cold Water Inlet, Indirect Circulator, Indirect Water Heater, and connections to the Heating Zone.

Electrical Connections

Figures 9 and 10 are general wiring diagrams. For a maintaining temperature boiler, Figure 9 should match your system. For cold start boilers, Figure 10 may be similar, but wiring varies by boiler type and controls.

When connecting to a cold start boiler, the indirect water heater operates as another heating zone. When it calls for heat, its circulator starts, the system circulator stays off, and the boiler must light to reach high limit.

Wiring Notes:

  • Dashed lines indicate low voltage (24 VAC).
  • Use jumper wire between terminals #1 and #3 on R845 relay.

Thermostat Specifications:

Thermostats can operate at low or line voltages.

VoltageAmperage
24 voltN/A
120 volt8 amp
240 volt5 amp

This equipment must be properly grounded to prevent a potential shock hazard and to reduce anode deterioration due to electrolysis. Refer to local electrical codes and ordinances.

Section V: Maintenance

Water Piping

On an annual basis, check all piping for leakage at joints, shut-off valves, and unions.

T&P Relief Valve

On an annual basis, check the temperature and pressure relief valve for proper operation. Attach a drain line to direct discharge to an open drain. Lift the valve lever several times. The valve should operate freely and return to its original position. If water does not flow, remove and inspect for corrosion or obstructions. Replace if necessary. Do not repair a faulty valve.

Anode Rods

Anode rods should be inspected twice in the first year and at least yearly. Check six months after installation. If the anode rod has reduced in size by two-thirds of its original diameter (3/4") or shows pitting, it is time for replacement. Follow these steps:

  1. Shut off water supply.
  2. Open any faucet to relieve tank pressure.
  3. Remove caps on indirect water heater top; push insulation aside.
  4. Use a 1 1/16" six-sided socket wrench and a breaker bar to break the anode rod seal.
  5. Remove rod(s) and replace with new rod(s).
  6. Turn water supply back on and leave faucet open until air is out of line.
  7. Turn faucet off and check that new rod(s) doesn't leak.
  8. Snap caps back into place.

Flush the Tank

The indirect water heater is glass lined. Lime, iron, and other minerals may accumulate. Drain and flush the tank thoroughly once a year to prevent buildup.

Section VI: Troubleshooting

ProblemCauseSolution
No hot water at faucetBoiler does not operateRefer to boiler installation instructions. Check main service switch.
Circulator does not operateCheck fused disconnect. Check power supply. Replace as necessary. Check aquastat setting. Turn tank aquastat to safe temperature setting.
Improper aquastat settingCheck aquastat setting.
Electrical problem (relay, wiring, etc.)Check fuse and replace. Check circuit breaker and reset (if applicable). Check power supply.
Scale build-upIf boiler, circulator, and tank are operating satisfactorily, coil may have scale coating. See Section VI for tank flushing procedure.
Water at faucet too hotAquastat set too highLower aquastat setting to safe level. Check manufacturer's instructions.
Tempering valve not properly set or defectiveCheck manufacturer's instructions.
Insufficient hot waterAquastat set too lowRaise aquastat setting to safe level. See Section III.
Undersized boiler with no priority to domestic hot waterRewire for priority.
Peak use of hot water is greater than tank storage capacityDetermine peak usage, compare to tank capacity, and add additional storage (storage tank) if necessary.
Boiler cycles more than 5 times per day during hottest monthsFaulty tank aquastatReplace aquastat.
Excessive demandReduce demand or consider larger tank.
Faulty aquastatReplace aquastat.
Boiler high limit set too lowIncrease boiler high limit setting.
Scale, hard white particles from faucets, popping sound from tankLime, water hardness above 7 grains / 120ppmWater treatment; softener; etc.
Rust staining; bad taste and odor in waterIron/minerals in water supplyFiltration.
Rotten egg odorHydrogen SulfideFlush tank with chlorine solution and install aluminum anode rod(s). Properly ground heater & replace anode rod(s). Check well pump system.
Air from hot water fixtureElectrolysis or air introduced by water supplyReplace dip tube.
Reduction in recoveryDip tube broken or compromised by high chlorine in waterReplace dip tube.
Inlet/Outlet fitting corrosionGalvanic corrosion of dissimilar metalsInstall dielectric unions.
T&P Valve dripping waterExcessive water supply pressure; closed loop system (System Plus) requires expansion tank.Check incoming water supply pressure; closed loop system (System Plus) requires expansion tank.
T&P gushing waterExcessive water temp. (above 210 °F)Adjust or replace aquastat and T&P valve.

Section VII: Parts List

Diagram and Parts

An exploded view diagram shows the components of the indirect water heater. The following parts are listed:

No.DescriptionApplicable Models
1AnodeAll models.
2Anode OutletSTID 30, STID 40, STID 50
3T&P Relief ValveAll models.
4Drain ValveAll models.
5AquastatAll models.

Section VIII: Limited Warranty

General

This Limited Warranty is available only to the original owner and is not transferable. Rheem warrants the water heater and its component parts to be free from defects in materials and workmanship under normal use and service for the Applicable Warranty Period. Rheem will repair or replace defective units or parts at its option.

Effective Date

The Effective Date of warranty coverage is the date of installation or the manufacture date of the water heater (whichever came first), if properly documented. Otherwise, it is the date of manufacture plus 90 days.

Applicable Warranty Periods

Tank: Six (6) years for single-family dwellings, three (3) years for other installations. Component parts: One (1) year, except LIFEGUARD™ elements (three (3) years).

Warranty Exclusions

This Limited Warranty does not cover:

  • Service trips for installation, use, or maintenance instruction.
  • Damages, malfunctions, or failures resulting from improper installation, non-compliance with codes, or failure to operate and maintain according to instructions.
  • Performance problems due to improper sizing, gas supply, venting, or electrical issues.
  • Failures from improper fuel conversion (natural gas to LP or vice versa).
  • Operation with anode rod removed or with unapproved parts.
  • Damage from abuse, accident, fire, flood, freeze, lightning, or acts of God.
  • Tank leaks caused by corrosive or contaminated atmospheres.
  • Operation with an empty tank ("dry firing").
  • Operation at temperatures exceeding maximum settings.
  • Operation without a supply of potable water.
  • Operation beyond specified pressures or firing rates.
  • Use of unauthorized attachments or energy saving devices.
  • Units installed outside the USA (50 states) and Canada (10 provinces).
  • Units moved from original installation location.
  • Units with removed rating labels.

Labor, Materials, Shipping, and Processing Costs

This Limited Warranty does not cover labor expenses for service, repairs, reinstallation, permits, or removal/disposal. It also does not cover reinstallation material costs (pipe, valves, fittings). Rheem pays transportation costs for in-warranty replacements to a convenient delivery point. You must pay any local freight charges and return costs.

Rheem does not authorize or reimburse for claims processing or similar fees charged by third parties.

How to Obtain Warranty Claim Assistance

Make claims promptly. Determine if the unit is "in-warranty" using the model number, serial number, and installation/purchase date. Visit www.rheem.com or contact the Rheem Warranty Department at (800) 621-5622. If in-warranty, refer to the Use and Care Manual or contact Rheem Technical Service at (800) 432-8373 or www.rheem.com. You may use a local plumber/contractor at your expense.

Provide complete model number, serial number, and installation/purchase date. If an exact replacement is unavailable, Rheem will provide a current or comparable model. You may be charged for features required by government regulations or industry standards.

Rheem reserves the right to inspect or require the return of failed units or parts. In-warranty failures require the unit or part to be made available to Rheem in exchange for replacement.

Warranty compensation is subject to validation by Rheem Claims Department.

To obtain warranty compensation, provide Rheem with the failed unit (with rating label and all parts intact) or the original rating label, complete model and serial numbers of the replacement unit, and date of failure. Proof of original installation/purchase date may be required.

For defective component parts, provide the part, complete model/serial numbers of the water heater it was removed from, and date of failure. Proof of installation/purchase date may also be required.

Warranty claim documentation should be mailed to: Rheem Water Heaters, Claims Department, 101 Bell Road, Montgomery, Alabama 36117.

Exclusive Warranty & Limitation of Liability

This Limited Warranty is the sole warranty provided by the manufacturer. No one is authorized to make other warranties. Implied warranties, including merchantability or fitness for a particular purpose, are limited to the Applicable Warranty Periods. Rheem's sole liability for any defect is as set forth in this warranty. Claims for incidental or consequential damages (including water leakage) are excluded. Some states do not allow limitations on implied warranties or exclusions of incidental/consequential damages, so these limitations may not apply to you. This warranty gives you specific legal rights, which may vary by state.

Complete the information below and retain this Certificate of Limited Warranty for service needs. Reasonable proof of installation or purchase date may be required. Otherwise, the warranty effective date will be the date of manufacture plus ninety (90) days.

Owner Information:

  • Name of Owner/Business: ________________________________________________________
  • Water Heater Installation Location Address: _________________________________________________ _____________________________________________________________________________________
  • Date Water Heater was Installed:___________________________________________________________
  • Name of Rheem Retailer:_________________________________________________________________
  • Address of Rheem Retailer:______________________________________________________________ _____________________________________________________________________________________
  • Telephone Number of Rheem Retailer:_______________________________________________________
  • Complete Model Number of Water Heater:______________________________________________________

DO NOT RETURN THIS DOCUMENT TO RHEEM. KEEP IT WITH YOUR WATER HEATER OR BUSINESS RECORDS.

PDF preview unavailable. Download the PDF instead.

e8hxzj910nav Adobe PDF Library 8.0 Adobe InDesign CS3 (5.0.2)

Related Documents

Preview Rheem Indirect Water Heater Instruction Manual: Installation, Operation, and Maintenance
Comprehensive instruction manual for Rheem Indirect Water Heaters (STID30, STID40, STID50, STID80, STID120). Covers specifications, installation, maintenance, troubleshooting, and warranty information.
Preview Rheem Solar Indirect Water Heater Manual: RSID50, RSID80, RSID120 Installation & Operation Guide
Explore the Rheem Solar Indirect Water Heater Instruction Manual for comprehensive guidance on installation, operation, and maintenance of models RSID50, RSID80, and RSID120. Includes safety protocols, troubleshooting, and warranty details from Rheem Manufacturing Company.
Preview Rheem Water Heater 3-Year Limited Warranty - Parts & Tank Coverage
Official warranty details for Rheem residential water heaters, outlining the 3-year tank and 1-year parts limited warranty, coverage terms, exclusions, and service contact information.
Preview Rheem Electric Residential Hybrid Water Heater: Use & Care Manual with Installation Instructions
Comprehensive guide for Rheem Electric Residential Hybrid Water Heater, covering installation, operation, safety, maintenance, and troubleshooting. Includes important safety information, setup instructions for installers and owners, and troubleshooting tips.
Preview Rheem Commercial Air to Water Heat Pump Water Heater Owners Guide and Installation Instructions WMKA21549
Official owners guide and installation instructions for the Rheem WMKA21549 commercial air-to-water heat pump water heater. Covers installation, operation, maintenance, safety, and troubleshooting for optimal performance.
Preview Rheem STELLAR 850 Series Gas Water Heater: Owner's Guide & Installation Instructions
Comprehensive owner's guide and installation instructions for the Rheem STELLAR 850 series 330 and 360 gas domestic outdoor water heaters. Learn about operation, maintenance, and warranty.
Preview Rheem Electric Domestic Water Heater: Owners Guide and Installation Instructions
Comprehensive guide for Rheem electric domestic water heaters, covering operation, maintenance, installation, troubleshooting, and warranty information. Includes details on Rheemglas, Optima, and RheemPlus models.
Preview Rheem Performance Atmospheric Gas Water Heater Specifications and Features
Detailed specifications, features, and dimensions for Rheem Performance Atmospheric Gas Water Heaters, including efficiency, performance, warranty, and technical data.