Instruction Manual for TRU COMPONENTS models including: TK4S-14RC, 3016144, TCD210240AD, TK4S-14RC High Performance PID Temperature Controllers, TK4S-14RC, High Performance PID Temperature Controllers, PID Temperature Controllers, Temperature Controllers, Controllers

Navodila za uporabo 3016144 TRU COMPONENTS TK4S-14RC pid regulator temperature K, J, E, T, B, R, S, N, C, L, U, PL-II -199.9 do 999.9 °C SSR, rele 3

TRU COMPONENTS TK4S-14RC pid regulator temperature K, J, E, T, B, R, S, N, C, L, U, PL-II -199.9 do 999.9 °C SSR, rele 3 - MegaShop spletna trgovina - Megashop.si   

Upute za rukovanje 3016144 TRU COMPONENTS TK4S-14RC pid termostat K, J, E, T, B, R, S, N, C, L, U, PL-II -199.9 do 999.9 °C SSR, relej 3 A

TRU COMPONENTS TK4S-14RC pid termostat K, J, E, T, B, R, S, N, C, L, U, PL-II -199.9 do 999.9 °C SSR, relej 3 A - AC group - webshop   

Navodila za uporabo 3016144 TRU COMPONENTS TK4S-14RC pid regulator temperature K, J, E, T, B, R, S, N, C, L, U, PL-II -1999 do 9999 °C SSR, rele 3 A

TRU COMPONENTS TK4S-14RC pid regulator temperature K, J, E, T, B, R, S, N, C, L, U, PL-II -1999 do 9999 °C SSR, rele 3 A - MegaShop spletna trgovina - Megashop.si


File Info : application/pdf, 2 Pages, 1.26MB

PDF preview unavailable. Download the PDF instead.

navodila-za-uporabo-3016144-tru-components-tk4s-14rc-pid-regulator-temperature-k-j-e-t-b-r-s-n-c-l-u-pl-ii-1999-do-9999-c-ssr-re
Simultaneous Heating & Cooling Output PID Temperature Controller
TK4S-14RC
Item no.: 3016144
INSTRUCTION MANUAL
TCD210240AD
Read and understand the instruction manual before using the product. For your safety, read and follow the below safety considerations before using. For your safety, read and follow the considerations written in the instruction manual. Keep this instruction manual in a place where you can find easily. The specifications, dimensions, etc are subject to change without notice for product improvement.
Safety Considerations
· Observe all `Safety Considerations' for safe and proper operation to avoid hazards. · symbol indicates caution due to special circumstances in which hazards may occur.
Warning Failure to follow instructions may result in serious injury or death
01. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in personal injury, economic loss or fire.
02. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use. Failure to follow this instruction may result in electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in fire or electric shock.
05. Check `Connections' before wiring. Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit. Failure to follow this instruction may result in fire or electric shock.
Caution Failure to follow instructions may result in injury or product damage
01. When connecting the power input and relay output, use AWG 20 (0.50 mm2) cable or over, and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m. When connecting the sensor input and communication cable without dedicated cable, use AWG 28 to 16 cable and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m. Failure to follow this instruction may result in fire or malfunction due to contact failure.
02. Use the unit within the rated specifications. Failure to follow this instruction may result in fire or product damage
03. Use a dry cloth to clean the unit, and do not use water or organic solvent. Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which flow into the unit. Failure to follow this instruction may result in fire or product damage.
Cautions during Use
· Follow instructions in `Cautions during Use'. Otherwise, it may cause unexpected accidents. · Check the polarity of the terminals before wiring the temperature sensor. For RTD temperature sensor,
wire it as 3-wire type, using cables in same thickness and length. For thermocouple (TC) temperature sensor, use the designated compensation wire for extending wire. · Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise. · Do not apply excessive power when connecting or disconnecting the connectors of the product. · Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power. · Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller. · When changing the input sensor, turn off the power first before changing. After changing the input sensor, modify the value of the corresponding parameter. · Do not overlapping communication line and power line. Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect of external noise. · Make a required space around the unit for radiation of heat. For accurate temperature measurement, warm up the unit over 20 min after turning on the power. · Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power. · Do not wire to terminals which are not used. · This unit may be used in the following environments. - Indoors (in the environment condition rated in `Specifications') - Altitude Max. 2,000 m - Pollution degree 2 - Installation category II

Product Components
· Product (+ bracket)

· Instruction manual

Operating Instructions for download
Use the link www.conrad.com/downloads (alternatively scan the QR code) to download the complete operating instructions (or new/current versions if available). Follow the instructions on the web page.

Specifications

Series Power supply

AC type

Permissible voltage range

Power consumption

AC type

Unit weight (packaged)

TK4S 100 - 240 VAC~ 50/60 Hz 90 to 110 % of rated voltage
 8 VA  105 g ( 150 g)

Sampling period

Input specification

Control output

Relay SSR Current

Alarm output

Relay

Display type

Control type

Heating, Cooling Heating & Cooling

50 ms Refer to 'Input Type and Using Range' 250 VAC ~ 3 A, 30 VDC 3 A 1a 11 VDC ±2 V,  20 mA DC 4-20 mA or DC 0-20 mA (parameter), Load resistance:  500  AL1: 250 VAC~ 3 A 1a 7 segment (red, green, yellow), LED type
ON/OFF, P, PI, PD, PID Control

Hysteresis Proportional band (P) Integral time (I) Derivative time (D) Control cycle (T) Manual reset

· Thermocouple, RTD: 1 to 100 (0.1 to 100.0) °C/°F · Analog: 1 to 100 digit
0.1 to 999.9 °C/°F (0.1 to 999.9%)
0 to 9,999 sec
0 to 9,999 sec
· Relay output, SSR drive output: 0.1 to 120.0 sec · Selectable current or SSR drive output: 1.0 to 120.0 sec
0.0 to 100.0%

Relay life Mechanical cycle
Electrical
Dielectric strength

OUT1/2:  5,000,000 operations AL1/2:  20,000,000 operations  100,000 operations Dependent on the power supply

AC voltage type

Between the charging part and the case: 3,000 VAC ~ 50/60 Hz for 1 minute

Vibration Insulation resistance Noise immunity Memory retention Ambient temperature Ambient humidity

0.75 mm amplitude at frequency of 5 to 55 Hz in each X, Y, Z direction for 2 hours
 100 M (500 VDC megger) ±2 kV square shaped noise by noise simulator (pulse width: 1 µs) R-phase, S-phase
 10 years (non-volatile semiconductor memory type) -10 to 50 °C, storage: -20 to 60 °C (no freezing or condensation)
35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)

Protection structure

IP65 (Front panel, IEC standards)

Insulation type Certification

Double insulation or reinforced insulation (mark: , dielectric strength between the measuring input part and the power part: 2 kV)

Input Type and Using Range

The setting range of some parameters is limited when using the decimal point display.

Input type K (CA)

J (IC)

E (CR)

T (CC)

Thermo -couple

B (PR) R (PR) S (PR) N (NN) C (TT) 01) G (TT) 02)

L (IC)

RTD Analog

U (CC)
Platinel II Cu50  Cu100 
JPt100 
DPt50 
DPt100 
Nickel120  0 to 10 V 0 to 5 V 1 to 5 V 0 to 100 mV 0 to 20 mA 4 to 20 mA

Decimal point 1 0.1 1 0.1 1 0.1 1 0.1 1 1 1 1 1 1 1 0.1 1 0.1 1 0.1 0.1 1 0.1 0.1 1 0.1 1 -

Display

Using range (°C)

Using range (°F)

-200 to 1,350

-328 to 2,462

-199.9 to 999.9

-199.9 to 999.9

-200 to 800

-328 to 1,472

-199.9 to 800.0

-199.9 to 999.9

-200 to 800

-328 to 1,472

-199.9 to 800.0

-199.9 to 999.9

-200 to 400

-328 to 752

-199.9 to 400.0

-199.9 to 752.0

0 to 1,800

32 to 3,272

0 to 1,750

32 to 3,182

0 to 1,750

32 to 3,182

-200 to 1,300

-328 to 2,372

0 to 2,300

32 to 4,172

0 to 2,300

32 to 4,172

-200 to 900

-328 to 1,652

-199.9 to 900.0

-199.9 to 999.9

-200 to 400

-328 to 752

-199.9 to 400.0

-199.9 to 752.0

0 to 1,390

32 to 2,534

-199.9 to 200.0

-199.9 to 392.0

-199.9 to 200.0

-199.9 to 392.0

-200 to 650

-328 to 1,202

-199.9 to 650.0

-199.9 to 999.9

-199.9 to 600.0

-199.9 to 999.9

-200 to 650

-328 to 1,202

-199.9 to 650.0

-199.9 to 999.9

-80 to 200

-112 to 392

0 to 10 V

0 to 5 V

1 to 5 V

0 to 100 mV

0 to 20 mA

4 to 20 mA

01) C (TT): Same as existing W5 (TT) type sensor 02) G (TT): Same as existing W (TT) type sensor · Permissible line resistance per line:  5 

 Display accuracy
Input type Using temperature

At room temperature (23 °C ±5 °C)
Thermo -couple RTD
Out of room temperature range

Analog

At room temperature (23 °C ±5 °C)
Out of room temperature range

Display accuracy
(PV ±0.3% or ±1 °C higher one) ±1-digit · Thermocouple K, J, T, N, E below -100 °C and L, U, PLII,
RTD Cu50 , DPt50 : (PV ±0.3% or ±2 °C higher one) ±1-digit · Thermocouple C, G and R, S below 200 °C: (PV ±0.3% or ±3 °C higher one) ±1-digit · Thermocouple B below 400 °C: There is no accuracy standards
(PV ±0.5% or ±2 °C higher one) ±1-digit · RTD Cu50 , DPt50 :
(PV ±0.5% or ±3 °C higher one) ±1-digit · Thermocouple R, S, B, C, G:
(PV ±0.5% or ±5 °C higher one) ±1-digit · Other sensors:  ±5 °C (-100 °C)
±0.3% F.S. ±1-digit
±0.5% F.S. ±1-digit

Unit Descriptions

4. Indicator

1. PV display part (Red) · Run mode: Displays PV (Present value). · Setting mode: Displays parameter name. 2. SV display part (Green) · Run mode: Displays SV (Setting value). · Setting mode: Displays parameter setting value. 3. Input key

Display [A/M] [MODE] [], [], []

Name Control switching key Mode key Setting value control key

Display °C, %, °F AT
OUT1/2
AL1 MAN SV1/2/3

Name Unit Auto tuning
Control output
Alarm output Manual control Multi SV

Description Displays selected unit (parameter) Flashes during auto tuning every 1 sec Turns ON when the control output is ON · SSR output (cycle/phase control)
MV over 5% ON · Current output
Manual control: 0% OFF, over ON Auto control: below 2% OFF, over 3% ON
Turns ON when the alarm output is ON
Turns ON during manual control
The SV indicator is ON which is currently displayed. (When using multi SV function)

TK4S
5. PC loader port: For connecting communication converter (SCM series).

Dimensions
· Unit: mm

 Panel cut-out

Body

A B CD

E

F

TK4S 48 48 6 64.5 1.7 45

 Bracket
TK4S

Panel cut-out

G

H

65 65

I 45 +0.6
0

J 45 +0.6
0

Installation Method  TK4S

Flathead screwdriver

After mounting the product to panel with bracket, insert the unit into a panel, fasten the bracket by pushing with a flathead screwdriver.

Errors

Display

Input
Temperature sensor

Analog

Temperature sensor

Analog

Temperature sensor

Analog

Temperature sensor
Analog

01) Be careful that when

/

depending on the control type.

Description

Output

Flashes at 0.5 sec interval when input sensor is disconnected or sensor is not connected.

'Sensor error, MV' parameter setting value

Flashes at 0.5 sec interval when input is over F.S. ±10%.

'Sensor error, MV' parameter setting value

Flashes at 0.5 sec intervals if
the input value is above the input range.01)

Heating: 0%, Cooling: 100%

Flashes at 0.5 sec intervals if the input value is over 5 to 10% Normal output of high limit or low limit value.

Flashes at 0.5 sec. intervals
if the input value is below the input range.01)

Heating: 100%, Cooling: 0%

Flashes at 0.5 sec intervals if the input value is over 5 to 10% Normal output of low limit or high limit value.

Flashes at 0.5 sec intervals if

there is error for setting and it returns to the error-before

-

screen.

Troubleshooting Check input sensor status. Check analog input status.
When input is within the rated input range, this display disappears.
Check setting method.

error occurs, the control output may occur by recognizing the maximum or minimum input

Connections
· Shaded terminals are standard model. · Digital input is not electrically insulated from internal circuits, so it should be insulated when
connecting other circuits.
 TK4S

Crimp Terminal Specifications
· Unit: mm, use the crimp terminal of the following shape.

3.0 5.8 Fork crimp terminal

3.0 5.8 Round crimp terminal

Initial Display When Power is ON

When power is supplied, after all display will flash for 1 sec, model name is displayed sequentially. After input sensor type will flash twice, enter into RUN mode.

PV display part SV display part

1. All display

2. Model

3. Input specification

4. Run mode

Mode Setting
Auto before entering to mode (when using password)
[], [], []

Password input

Password Pass
Fail

Key input Auto [], [], []
[MODE]

Entering mode Selected mode Password input
Run mode

SV setting

Move digits: []

Save: [MODE] or no

Change value: [], [] key input over 5 sec

RUN RUN

[MODE] over 2 sec [] + [] + [] over 5 sec

Parameter group

[MODE] over 3 sec

Parameter reset

Refer to `Parameter Reset'

[A/M] 01)

Auto/Manual control switching

[A/M]

[] + [] over 3 sec

Digital input key

Auto

01) In case of TK4S model, short press of [MODE] key replaces [A/M] key function.

Parameter Reset
01. Press the [] + [] + [] keys for over 5 sec. in run mode, INIT turns ON. 02. Change the setting value as YES by pressing the [] , [] keys. 03. Press the [MODE] key to reset all parameter values as default and to return to run mode.

Parameter Setting
· Some parameters are activated/deactivated depending on the model or setting of other parameters. · The 'Parameter mask' feature hides unnecessary or inactive parameters, and the 'User parameter
group' feature quickly and easily sets up certain parameters that are frequently used. · Refer to the user manual for the details.

Disposal
This symbol must appear on any electrical and electronic equipment placed on the EU market. This symbol indicates that this device should not be disposed of as unsorted municipal waste at the end of its service life. Owners of WEEE (Waste from Electrical and Electronic Equipment) shall dispose of it separately from unsorted municipal waste. Spent batteries and accumulators, which are not enclosed by the WEEE, as well as lamps that can be removed from the WEEE in a nondestructive manner, must be removed by end users from the WEEE in a non-destructive manner before it is handed over to a collection point.
Distributors of electrical and electronic equipment are legally obliged to provide free take-back of waste. Conrad provides the following return options free of charge (more details on our website): · in our Conrad offices · at the Conrad collection points · at the collection points of public waste management authorities or the collection points set up by
manufacturers or distributors within the meaning of the ElektroG End users are responsible for deleting personal data from the WEEE to be disposed of. It should be noted that different obligations about the return or recycling of WEEE may apply in countries outside of Germany.

 Parameter 1 group
Parameter Control output RUN/STOP Multi SV selection Heater current monitoring Alarm output1 low limit Alarm output1 high limit Multi SV 0 Multi SV 1 Multi SV 2 Multi SV 3

Display

Default

 Parameter 2 group
Parameter Auto tuning RUN/STOP Heating proportional band Cooling proportional band Heating integral time Cooling integral time Heating derivative time Cooling derivative time Dead overlap band Manual reset Heating hysteresis Heating OFF offset Cooling hysteresis Cooling OFF offset MV low limit MV high limit RAMP up change rate RAMP down change rate RAMP time unit
 Parameter 3 group
Parameter Input specification Temperature unit Analog low limit Analog high limit Scaling decimal point Low limit scale High limit scale Display unit Input correction Input digital filter SV low limit SV high limit
Control output mode
Control type
Auto tuning mode OUT1 control output selection OUT2 control output selection OUT2 current output range Heating control cycle
Cooling control cycle

Display

Default

Display

Default

(Normal type) (Heating& Cooling type) (Normal type) (Heating& Cooling-type)
(Relay) (SSR)

 Parameter 4 group
Parameter Alarm output1 Operation mode Alarm output1 Option Alarm output1 Hysteresis Alarm output1 contact type Alarm output1 ON delay time Alarm output1 OFF delay time LBA time
LBA band
Analog Transmission output1 Mode Transmission output1 low limit Transmission output1 high limit Analog Transmission output2 Mode Transmission output2 low limit Transmission output2 high limit Communication address Communication speed Comm. parity bit Comm. stop bit Response time Comm. write
 Parameter 5 group
Parameter Multi SV number Digital input key
Digital input1 Terminal Function
Digital input2 Terminal Function Manual control, initial MV Manual control, preset MV Sensor error MV Control stop MV Control stop alarm output User level SV setting lock Parameter 1 group lock Parameter 2 group lock Parameter 3 group lock Parameter 4 group lock Parameter 5 group lock Password setting

Display

Default

Display

Default

This is a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com). All rights including translation reserved. Reproduction by any method, e.g. photocopy, microfilming, or the capture in electronic data processing systems require the prior written approval by the editor. Reprinting, also in part, is prohibited. This publication represents the technical status at the time of printing.