Growatt APX 5.0~30.0P-S0 Quick Guide
Environmental Conditions
Maximum operating temperature: +50°C
Minimum operating temperature: -10°C
Relative Humidity: 5% to 95%
Installation Tools
Required tools include M6 tools with a torque specification of 2 N·m and M4 tools with a torque specification of 1 N·m.
System Size
The APX 55027-P0 Power Module measures 690mm (height) x 220mm (width) x 185mm (depth).
The APX 5.0P-B1 Battery Module measures 690mm (height) x 295mm (width) x 185mm (depth).
1. Inspection Upon Delivery
1-1 Checking the APX 55027-P0 Packing List
The APX 55027-P0 (Power Module) package should contain:
- User Manual *1
- Quick Guide *1
- Warranty Card *1
- BM Install-location Card *1
- PM Install-location Card *1
- System cable
Included accessories:
- Protective rubber ring *4
- Anti-tipping plate *2
- M6 explosive screw *2
- M6x12 stainless steel screws *1
- M4x9 stainless steel screws *3
1-2 Check APX 5.0P-B1 List
The APX 5.0P-B1 (Battery Module) package should contain:
- APX 5.0P-B1 Base *1
- Left trim-cover *1
- Right trim-cover *1
- Trim-cover *2
- Warranty Card *1
- Parallel cable *1
Included accessories:
- Anti-tipping plate *2
- M6 explosive screw *2
- M4x9 stainless steel screws *3
1-3 Check the APX Battery System of Different Capacities
The system configuration depends on the desired capacity:
Floor Installation Compound Mode:
- 5kWh: APX 55027-P0 (A) + APX 5.0P-B1 (B)
- 10kWh: APX 55027-P0 (A) + 2 x APX 5.0P-B1 (B)
- 15kWh: APX 55027-P0 (A) + 3 x APX 5.0P-B1 (B)
- 20kWh: APX 55027-P0 (A) + 4 x APX 5.0P-B1 (B)
- 25kWh: APX 55027-P0 (A) + 5 x APX 5.0P-B1 (B) + APX 5.0P-B1 Base (E) + APX 5.0P-B1 Parallel extension cable (D)
- 30kWh: APX 55027-P0 (A) + 6 x APX 5.0P-B1 (B) + APX 5.0P-B1 Base (E) + APX 5.0P-B1 Parallel extension cable (D)
Wall-Mounted Installation Compound Mode:
- 5kWh: APX 55027-P0 (A) + APX 5.0P-B1 (B) + Wall bracket (C)
- 10kWh: APX 55027-P0 (A) + 2 x APX 5.0P-B1 (B) + Wall bracket (C)
- 15kWh: APX 55027-P0 (A) + 3 x APX 5.0P-B1 (B) + Wall bracket (C)
- 20kWh: APX 55027-P0 (A) + 4 x APX 5.0P-B1 (B) + Wall bracket (C)
- 25kWh: APX 55027-P0 (A) + 5 x APX 5.0P-B1 (B) + 2 x Wall bracket (C) + APX 5.0P-B1 Parallel extension cable (D)
- 30kWh: APX 55027-P0 (A) + 6 x APX 5.0P-B1 (B) + 2 x Wall bracket (C) + APX 5.0P-B1 Parallel extension cable (D)
2. Installation Environment Requirements
Note: When installed outdoors, a sun/rain shelter is recommended to protect the battery system from direct sunlight and rain.
3. Floor-Mounted Installation
3-1 Installation Location Requirements
The installation requires a stable ground surface. For floor-mounted installations using the base, a maximum of six battery modules can be configured. If more than four modules are installed, it is advised to arrange them in two columns.
3-2 Installation Procedure
Mounting Hole Dimensions:
Dimensions are provided for 5kWh, 10kWh, 15kWh, and 20kWh configurations, indicating spacing for multiple modules.
Power Module Installation Size: The Power Module installation size is detailed in the diagrams, showing its footprint and mounting points.
Battery Module Installation Size: The Battery Module installation size is detailed in the diagrams, showing its footprint and mounting points.
Steps:
- Mark the hole positions using a marking pen and template, ensuring alignment marks are correct.
- Drill holes with a diameter of 8.0mm to a depth of 45-50mm.
- Fix the M6 explosive screws into the wall.
- Install the connecting pieces on both sides of the module and tighten the two screws.
- Level the battery module using a spirit level.
- Install the anti-tipping plate on both sides and tighten the two screws.
- Secure the module on both sides to the wall by loosening two screws, moving up the handle, and then tightening the screws to fix the modules. This applies to both battery and power modules.
4. Wall-Mounted Installation
4-1 Installation Location Requirements
Maintain minimum clearances of 300mm on the sides and top, and 100mm at the bottom. Ensure the wall's load-bearing capacity exceeds the total system weight (Power Module: 10 kg, Battery Module: 50 kg each). For configurations with more than four battery modules, installation in two columns is advised.
4-2 Installation Procedure
Mounting Hole Dimensions:
Dimensions are provided for 5kWh, 10kWh, 15kWh, and 20kWh configurations, indicating spacing for multiple modules and brackets.
Power Module Installation Size: The Power Module installation size is detailed in the diagrams, showing its footprint and mounting points.
Battery Module Installation Size: The Battery Module installation size is detailed in the diagrams, showing its footprint and mounting points.
Steps:
- Install the wall bracket onto the wall.
- Level the battery module using a spirit level.
- Mark the hole positions on the wall using a marking pen and the install-location card for alignment.
- Drill eight holes with a diameter of 8.0mm to a depth of 45-50mm.
- Fix the M6 explosive screws into the wall.
- Install the anti-tipping plate on both sides and tighten the two screws.
- Fix the wall bracket onto the wall using the installed screws.
- Secure the battery module onto the bracket. This involves loosening two screws, moving up the handle, and then tightening the screws to fix the module. Repeat for power modules.
5. Cable Connection
APX 55027-P0 Terminal & Key Description
Terminals on the Power Module (APX 55027-P0):
- B+: Battery positive terminal to INV
- B-: Battery negative terminal to INV
- Link-in: Inverter communication to INV
- Link-out: Battery module communication to battery module (BMU)
APX 5.0P-B1 Terminal Description
Terminals on the Battery Module (APX 5.0P-B1):
- Link-in: Communication to another battery module (Link-out) or power module (BMU).
- Link-out: Communication to another battery module (Link-in).
- B+: Battery positive terminal to another battery module or power module.
- B-: Battery negative terminal to another battery module or power module.
- USB: USB terminal.
Battery Capacity Description
The battery system supports expansion of power and capacity. Up to two power control modules can be connected in parallel. One power control module supports a maximum of four battery expansion modules.
System configurations by capacity:
- 2.5KW / 5KWh
- 5KW / 10KWh
- 6.2KW / 15KWh
- 6.2KW / 20KWh
- 6.2KW / 25KWh
- 6.2KW / 30KWh
System Wiring Diagram
Connections include grounding cable, communication cable, and power cable. Ensure the waterproof cover of the communication cable is tightened to maintain waterproof performance. Failure to do so may void the warranty.
Note: It is not recommended to install a DC circuit breaker between the battery system and the inverter. If a DC circuit breaker with a rated working voltage greater than 600V and a rated working current greater than 63A is installed, do not operate it with power on, as this may damage the machine.
Cables are routed out of the designated cable holes.
6. Terminal Connection
Connections between the APX 55027-P0 (Power Module) and the inverter (e.g., MIN 2.5-6KTL-XH/MIN 2.5-6KTL-XH2) are made via specific terminals:
APX 55027-P0 Terminals:
| Terminal Serial Number | Definition |
|---|---|
| 1 | WAKE-(W-) |
| 2 | WAKE+(W+) |
| 7 | RS485_B (B) |
| 8 | RS485_A (A) |
Inverter Terminals (SYS COM):
| Terminal Serial Number | Definition |
|---|---|
| 1 | Enable- |
| 2 | Enable+ |
| 7 | BAT_B |
| 8 | BAT_A |
Connection Mapping:
- APX 55027-P0 "A" to Inverter SYS COM "8"
- APX 55027-P0 "B" to Inverter SYS COM "7"
- APX 55027-P0 "W+" to Inverter SYS COM "2"
- APX 55027-P0 "W-" to Inverter SYS COM "1"
Note: When wiring the communication cable to the inverter, connect it to PIN 1, 2, 7, 8 of the INV-COM terminal first.
7. Powering On/Off the Battery System
Powering On:
- Turn on the DC Switch.
- Press and hold the start key for more than 5 seconds.
Powering Off:
- Turn off the DC Switch.
- Wait for over 90 seconds.
Important Notes:
- Before maintenance or repair, ensure the AC circuit breaker and PV switch of the PCS, as well as the APX switch, are disconnected. Wait 15 minutes after powering off and confirm the GROWATT indicator is off before proceeding.
- When multiple battery systems are connected in parallel, press the start key of only one module to start the entire system.
Disclaimer: Growatt reserves the right to amend this document at any time without notice. Information provided is for quick installation guidance and does not constitute a warranty. Growatt holds the right to final interpretation.