EBAC MODEL WM80 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL

Page 2 of 17 Drawing : - TPC543 Issue : - 3 Date : - 12/01/24 WM80 PACKAGE CONTENTS Item Description Quantity 11284GL-US Dehumidifier 1


File Info : application/pdf, 17 Pages, 329.32KB

PDF preview unavailable. Download the PDF instead.

TPC543
Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
EBAC MODEL WM80 INDUSTRIAL DEHUMIDIFIER
OWNER'S MANUAL
www.eipl.co.uk
Page 1 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

WM80 PACKAGE CONTENTS

Item 11284GL-US
3082214 3088525 3086144 3944110 TPC543

Description Dehumidifier Brass wood screws
Rawl plug Quick release hose coupling
PVC tube ­ 3/8" I/D Manual

Quantity 1 4 4 1
7.8M 1

Page 2 of 17

INTRODUCTION

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

Designed for a wide range of applications, the WM80 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
The WM80 has a number of special features:
· High efficiency rotary compressor · Ebac's "Hot Gas" defrost system · Integral pump out system · Provision for permanent drainage · Exterior epoxy powder-coated finish · Extra long power cord · Free Standing or Wall Mountable · Status Indicators · Control Humidistat
The fan draws the moist air through the cold evaporator coil, which cools the air below its dew point. Moisture forms on the evaporator coil and is collected in the condensate tray, which is equipped with a permanent drain. The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase, plus the additional heat generated by the compressor. The air is, therefore, discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered. Continuous circulation of air through the dehumidifier gradually reduces the relative humidity within the area.
The WM80 dehumidifier is a reliable drying unit designed to operate effectively over a broad range of temperature and humidity conditions. An active hot gas defrost system, controlled by an electronic timer, guarantees positive de-icing, thereby optimizing operation at low temperatures.

Page 3 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
SPECIFICATIONS

MODEL: 11284GL-US HEIGHT: 19.4" (495mm)

WIDTH: 22" (560mm)

DEPTH: 11.4" (290mm)

WEIGHT: 81.5 lbs (37Kg)

AIRFLOW: 153 CFM (260M3/hr)

POWER SUPPLY: 110V - 60Hz - 1 ph

FINISH:

Powder-coated Epoxy

OPERATING RANGE: 33°F ­ 105°F

REFRIGERANT: R-407c (13 oz)

"This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows
R134a ­ 1300 R407c ­ 1610
For type and weight of refrigerant contained in this unit, please refer to the product data label"

Page 4 of 17

OPERATION

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

The following procedures should be followed to test the WM80 for correct operation:
1. After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Connect the power cable to a grounded 13 Amp electrical socket. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain.
CAUTION DO NOT REMOVE COVERS WHEN THE UNIT IS IN OPERATION
2. Check dehumidification process as follows: a. Place unit on a level surface. b. Turn the power supply on, then turn the on / off switch to the `I' position, note the display will flash for approximately 1 second then show the humidity set point for approximately 12 seconds. Also all the indicator lights will illuminate for the same duration. After this brief period the display will show the room humidity and all the lights will go off. The machine is now powered up (POWER light illuminated) and ready to operate. Then carry out the following: c. Set the humidity set point to lowest setting (35% RH) as follows. i. Press the UP and DOWN arrow keys together for 3 seconds and the display will start to flash ii. Use the UP and DOWN arrow keys to adjust the set point to 35% iii. Press the RIGHT arrow key to save (if the RIGHT arrow key is not pressed for 3 seconds the selection is cancelled) iv. Once set to 35% and saved the compressor will start and the drying light will illuminate d. Check that the compressor is running. e. Leave the machine running for 15 minutes. f. Observe the evaporator coils through the rear upper grille, to confirm frost formation. g. If the air temperature is below 25ºC, an even coating of frost should cover the entire evaporator coil. h. If the air temperature is above 25°C, frost and/or droplets of condensed water should cover the entire evaporator coil. i. When the unit is operated in an ambient of less than 15°C, a defrost cycle should occur. This will be at intervals of no more than every hour and will last no more than 5 minutes. The exact time is impossible to predict as the unit is fitted with a temperature sensitive defrost control. When in defrost the DRYING lamp will extinguish and the DEFROST light illuminate. After defrost the lights will switch back
3. After using the WM80, turn it off for 5 minutes to allow the condensate on the coils to drain into the pump reservoir.

CAUTION ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT LEAST
5 MINUTES BEFORE RESTARTING
Page 5 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

Light Functions:

The unit has four LED indicators, located on the side of the unit. The following lists the functions of these lights:

1

2

3

4

1 - ON / OFF Green solid ­ Indicates power ON
2 ­ DRYING Blue flashing ­ Indicates drying selected (compressor has not started) Blue solid ­ Indicates drying ON (compressor has started)
3 ­ DEFROST Yellow flashing (Approximately every 5 seconds) ­ Defrost cycle active Yellow solid ­ Defrost in progress
4 ­ Alarm Indicates the pump is running, colour can be Flashing Yellow or Red Initially flashes yellow for a minimum time of 5 seconds. If after 10 seconds the pump is still running the controller assumes a fault / restriction and turns to solid Red. If the fault clears and the float returns to its normal position, the pump will stop and the LED extinguishes
If, after carrying out the above procedures, the appliance does not appear to function properly, refer to the Trouble Shooting section, which
follows, or contact EIPL.
Page 6 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
INSTALLATION
The WM80 Dehumidifier can be left free standing unit, alternatively can be wall mounted for instructions on mounting the unit please read the following:
A full installation kit is included in the package to allow a problem free install. This kit comprises of the following :-
1 X WM80 Dehumidifier 1 X Mounting Bracket 4 X Rawl plugs and screws 4 X M6 Hex Head Bolts, flat and spring washers
For mounting the WM80 Dehumidifier to a wall you will first need to remove the cover from the unit and detach the wall mounting bracket from the rear of the unit by removing the 4 bolts that secures it.
With reference to the installation drawing at the rear of this manual, maintain the minimum clearances from adjacent objects (ie walls celings etc). Maintaining these distances will ensure easy access for installation and maintaining the unit during the products life
Place the wall mounting bracket onto the wall, ensuring the correct orientation, and the bracket is level. Mark off 4 points on the wall where you will be securing the bracket, the bracket has numerous holes and slots to allow the bracket to be mounted at different points depending on the wall you are mounting it to. It is advised to have the fixing points spaced out as far as possible to allow a more ridged and secure installation.
Using a 7mm masonry bit, drill the 4 points you marked off earlier to a depth of 40mm, insert the 4 Rawl plugs into the wall that are supplied with this unit.
Secure the wall mounting bracket to the wall using the 4 brass screws supplied with the unit.
Ensure all fixings are tight and bracket is secured to the wall.
Screw 2 X M6 Bolts into the top fixings on the bracket, only screwing them in a 2-3 turns. Lift the unit onto the bracket and hook the unit onto the bolts using the keyhole slots in the rear of the unit do not tighten the bolts yet. Fit the 2 remaining bolts through bottom holes in the rear of unit and into the wall mounting bracket and tighten all 4 bolts.
Check to make sure the unit is secure to the wall mounting bracket.
Replace cover and refit all fixings that have been removed.
Page 7 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
ROUTINE SERVICE
WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE
CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING: DO NOT STEAM CLEAN REFRIGERATION COILS
2. Remove the air filter and clean by either blowing compressed air through, vacuuming or washing in warm water
3. Check that the fan is firmly secured to the motor shaft and that the fan rotates freely. The fan motor is sealed for life and therefore does not need oiling.
4. To check the refrigerant charge, run the unit for 15 minutes and briefly remove the top cover. The evaporator coil should be evenly frost coated across its surface. At temperatures above 25°C, the coil may be covered with droplets of water rather than frost. Partial frosting accompanied by frosting of the thin capillary tubes, indicates loss of refrigerant gas or low charge. During this inspection, check visually to ensure that the pump rollers are turning.
5. Check all wiring connections.
6. To check the operation of the defrost system, switch the machine on and leave it running for approximately 55 minutes. The machine will then enter "Hot Gas" defrost mode for approximately 5 minutes before returning to normal operation. If the unit will not defrost, the printed circuit timer board may be defective or the by-pass valve may be inoperable.
IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC SERVICE CENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO
PREVENT PERMANENT DAMAGE.
Page 8 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
REPAIRS
1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
2. If refrigerant gas is lost from the machine, it will be necessary to use a Refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action.
Any competent refrigeration technician will be able to service the equipment. The following procedure must be used:
a. The source of the leak must be determined and corrected.
b. The machine should be thoroughly evacuated before recharging.
c. The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and rebrazed after servicing. NEVER allow permanent service valves to be fitted to any part of the circuit. Service valves may leak causing further loss of refrigerant gas.
3. The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service. Compressor failure can result from the machine losing its refrigerant gas. The compressor can be replaced by a competent refrigeration technician.
Failure of the compressor can be confirmed by the following procedure:
a. Establish that power is present at the compressor terminals using a voltmeter.
b. With the power disconnected, check the continuity of the internal winding by using meter across the compressor terminals. An open circuit indicates that the compressor should be replaced.
c. Check that the compressor is not grounded by establishing that a circuit does not exist between the compressor terminals and the shell of the compressor.
Page 9 of 17

TROUBLESHOOTING

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

SYMPTOM Unit inoperative
Little or no airflow
Little or no water extraction
Little or no defrost when required Unit vibrates excessively
Water flooding inside the machine

CAUSE 1. No power to unit
1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils / filter 4. Loose electrical wiring
1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas
1. Faulty timer 2. Faulty by-pass valve
1. Loose compressor 2. Damaged fan
1. Drain pipe blocked/frozen 2. Drain pipe too high 3. Crimped or blocked tubing

REMEDY 1. Check the power from power supply panel 1. Tighten fan 2. Replace the fan motor 3. See Routine Maintenance
Section 4. Check the wiring diagram to find fault and repair 1. Check all of the above 2. Contact the Factory Service Center 3. Contact the Factory Service Center 1. Contact the Factory Service Center 2. Contact the Factory Service Center 1. Tighten the nuts on the
compressor mounts 2. Replace fan 1. Clear the obstruction 2. Ensure that no section of the drain hose is above the level of the water outlet 3. Straighten, clear, or replace
tubing

Page 10 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

SPARE PARTS LIST

Description Product Part Number
PCB Timer Controls Display PCB Humidity Sensor PCB PCB Connecting Cable
Condenser Coil Evaporator Coil
Filter Mains Cable Keypad Label
Drain Tray Insulation Tube 10mm ID Silicone Drain Tray Tube
By-Pass Valve Filter Dryer
Solenoid Coil 20mm Open Grommet
3/8" Open Grommet M16 Gland Nut
Humidity Sensor Housing M16 Gland
On / Off Switch Fan Motor Spire Clip
No. 10 x 5/8" Screw Large Hose Clip
Quick Release Tube Coupling Small Hose Clip
Edge Fastener Clip PCB Mounting Pin
Feet Condensate Pump
Relay Light Pipe Lens Compressor Capacitor Condensate Drain Tube Condensate Pump Outlet Tube
Compressor

Part Number 11284GL-US 1619522 1619524 1619526 2013748 2026014 2026074 2028420 3035148 2128417 2131107 3014301 3014368 3020837 3020901 3030451 3032101 3032104 3032512 3035164 3035442 3035914 3040137 3080501 3084095 3086135 3086144 3086146 3088520 3101413 3101436 3160145 3036157 3931733 3030908 3944110 3944113 3944932

Spare parts available online www.EIPLDIRECT.com
Page 11 of 17

300mm

300mm

300mm

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
300mm

Page 12 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

LIMITED WARRANTY

Our products carry a one-year unconditional warranty against any defects in workmanship or material. This warranty will cover all parts and labor required to repair your Ebac product. This warranty is invalid if the unit has been abused, damaged, whether intentional or accidental, or if any modifications have been made to the unit.

THE FOREGOING WARRANTY IS EXCLUSIVE AND IS ISSUED IN LIEU OF ALL OTHER WARRANTIES (WHETHER WRITTEN, ORAL, OR IMPLIED) INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. EBAC INDUSTRIAL PRODUCTS, INC. DISCLAIMS ANY LIABILITY FOR CONSEQUENTIAL DAMAGES, LOST PROFITS, OR INCIDENTAL DAMAGES FOR BREACH OF ANY WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE.

For Your Records:

Model: ____________________ S/N: ______________________ Date Received: ______________

SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD

PLEASE NOTE
To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty, please complete and mail this card at your earliest convenience.
Thank You

WARRANTY REGISTRATION
DATE MODEL ___________ S/N ________________ RECEIVED ________________
OWNER __________________________________________________________
ADDRESS ________________________________________________________
CITY __________________________ STATE ________ ZIP _______________
COMMENTS ______________________________________________________
_________________________________________________________________
Ebac Industrial Products. 700 Thimble Shoals Boulevard, Suite 109, Newport News, Virginia. 23606-2575

Page 13 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
WARNINGS
This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified person in order to avoid hazard.
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a ­ 1300 R407c ­ 1610
For type and weight of refrigerant contained in this unit, please refer to the product data label
Due to the high pressures within the refrigeration circuit, under no circumstances must direct heat be applied to the evaporator coil in an attempt
to remove the build-up of ice. No attempt should be made to cut open any part of the refrigeration circuit
due to high pressures and gas involved. If the unit is switched off at the mains power supply for any reason, the unit must be allowed to stand at rest for at least three minutes before restarting. For correct installation and operation the unit inlet and outlet must have a
clearance of 0.5M from all adjacent surfaces and or structures.
Page 14 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
Page 15 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24
Page 16 of 17

Drawing : - TPC543 Issue : - 3 Date : - 12/01/24

UK Head Office
Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD
Tel: +44 (0) 1388 664400 Fax: +44 (0) 1388 662590
www.eipl.co.uk sales@eipl.co.uk

American Sales Office

German Sales Office

Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA

Ebac Industrial Products Ltd. Gartenfelder Str. 29-37 Gebäude 35 D-13599, Berlin Germany

Tel: +01 757 873 6800 Fax: +01 757 873 3632

Tel: +49 3043 557241 Fax: +49 3043 557240

www.ebacusa.com sales@ebacusa.com

www.eip-ltd.de sales@eip-ltd.de

Page 17 of 17



References

GPL Ghostscript 9.06