Mitsubishi Electric PLA-AE24NL & PUZ-AK24NLHZ
24,000 BTU/H Ceiling Cassette Indoor Unit
24,000 BTU/H Hyper Heat Pump Outdoor Unit
Indoor Unit Features
- Multiple control options, including the comfort app for remote access, third-party interfaces, and both wired and wireless controllers.
- Up and down swing-mode: Utilizes horizontal vanes to move air up and down throughout the room like an oscillating fan.
- Space-efficient ductless installation.
- PLA Airflow settings: Supports high and low ceiling applications.
- Suitable for light commercial applications (e.g., small offices, restaurants, retail).
- Individual vane settings for direct/indirect airflow control or variable airflow patterns.
- Ideal for various spaces like retail shops, classrooms, office spaces, conference centers, building lobbies, and more.
- Filter indicator signal.
- Easy-to-clean, washable filter (optional high-efficiency filter available).
- Built-in condensate lift mechanism.
- Available knockouts for outside-air intake and branch-duct run.
- 3D i-see Sensor®: Advanced sensor scans the room to create a thermal profile, adjusting temperature and airflow based on user preference and occupancy for energy savings.
Outdoor Unit Features
- Built-in base pan heater.
- High Speed Start-up: Hyper-Heating INVERTER® reduces start-up heating time by approximately half compared to standard models.
- Hyper-Heating INVERTER®: Variable speed INVERTER-driven compressor.
- Pre-charged refrigerant for piping lengths up to 100 ft.
- Pressure/temp protection.
- Seacoast protection: Components rated for 2,000 hours of durability under ASTM B117 testing standards for longevity in corrosive coastal environments.
- Wide Heating Range: Provides heating performance down to -13°F (average of 80% heating capacity).
Specifications
Parameter | Value | Unit |
---|---|---|
Cooling at 95°F | ||
Maximum Capacity | 24,400 | Btu/h |
Rated Capacity | 24,000 | Btu/h |
Minimum Capacity | 13,600 | Btu/h |
Maximum Power Input | 1,590 | W |
Rated Power Input | 1,490 | W |
Moisture Removal | 4.7 | Pints/h |
Sensible Heat Factor | 0.79 | |
Power Factor [208V/230V] | 98 | % |
Heating at 47°F | ||
Maximum Capacity | 28,000 | Btu/h |
Rated Capacity | 28,000 | Btu/h |
Minimum Capacity | 13,200 | Btu/h |
Maximum Power Input | 1,780 | W |
Rated Power Input | 1,780 | W |
Power Factor [208V/230V] | 98 | % |
Heating at 17°F | ||
Maximum Capacity | 26,000 | Btu/h |
Rated Capacity | 16,400 | Btu/h |
Maximum Power Input | 3,690 | W |
Rated Power Input | 1,650 | W |
Heating at 5°F | ||
Maximum Capacity | 26,000 | Btu/h |
Maximum Power Input | 3,350 | W |
Heating at -13°F | ||
Maximum Capacity | 18,800 | Btu/h |
Efficiency | ||
SEER2 | 22.8 | |
EER2 | 16.1 | |
HSPF2 [IV] | 9.8 | |
COP at 47°F | 4.6 | |
COP at 17°F (Max Capacity) | 2.2 | |
COP at 5°F (Max Capacity) | 2.02 | |
ENERGY STAR® Certified | Yes | |
Electrical | ||
Voltage, Phase, Frequency | 208/230, 1, 60 | VAC/VAC, Ø, Hz |
Guaranteed Voltage Range | 198-253 | VAC |
Voltage: Indoor - Outdoor, S1-S2 | 208/230 | VAC |
Voltage: Indoor - Outdoor, S2-S3 | 12-24 | V DC |
Short-circuit Current Rating [SCCR] | 5 | KA |
Recommended Fuse/Breaker Size (Outdoor) | 25 | A |
Recommended Wire Size [Indoor - Outdoor] | 14 | AWG |
Indoor Unit | ||
Fan Motor Output | 120 | W |
Airflow Rate at Cooling, Dry | 530, 640, 710, 810 | CFM |
Airflow Rate at Heating, Dry | 530, 640, 710, 810 | CFM |
Sound Pressure Level [Cooling] | 28, 30, 33, 36 | dB (A) |
Sound Pressure Level [Heating] | 28, 30, 33, 36 | dB (A) |
External Finish Color | 1.0Y 9.2/0.2 | |
Unit Dimensions (W x D x H) | 33-1/16 x 33-1/16 x 11-3/4 [840 x 840 x 298] | inch x inch x inch [mm x mm x mm] |
Package Dimensions (W x D x H) | 34-5/16 x 35-9/16 x 15 [871 x 903 x 381] | inch x inch x inch [mm x mm x mm] |
Unit Weight | 57 | lbs [kg] |
Package Weight | 82 | lbs [kg] |
Fan Motor Type | DC Motor | |
Cooling Intake Air Temp [Maximum / Minimum] | 90, 73/66, 59 | °FDB, °FWB / °FDB, °FWB |
Heating Intake Air Temp [Maximum / Minimum] | 82/50 | °FDB |
ODU Operating Temp. Range | ||
Cooling Intake Air Temp [Maximum / Minimum*] | 115/23 | °FDB, °FWB / °FDB, °FWB |
Heating Intake Air Temp [Maximum / Minimum] | 70, 59/-13, -13 | °FDB |
Heating Thermal Lock-out / Re-start Temperatures** | -22/-13 | °FDB |
Refrigerant | ||
Pre-Charged Refrigerant Amount | 9, 14 | lbs, oz |
Refrigerant | R454B | |
Maximum Pre-Charged Piping Length | 100 | ft [m] |
Additional Refrigerant Charge Per Additional Piping Length | 0.6 | oz/ft |
Gas Pipe Size O.D. [Flared] | 5/8 | inch [mm] |
Liquid Pipe Size O.D. [Flared] | 3/8 | inch [mm] |
Maximum Piping Length | 165 | ft [m] |
Maximum Height Difference | 100 | ft [m] |
Maximum Number of Bends | 15 |
Indoor Unit Accessories
Category | Item | Model Number |
---|---|---|
Space Panel | Space Panel | PAC-SJ38AS-E |
Wireless Remote Controller | Lockdown Bracket for Wireless Handheld Remote Controllers | RCMKP1CB |
RedLINK Wireless Remote Controller | MHK2 | |
Universal Wireless MA Handheld Remote Controller | PAR-FL32MA-E | |
Universal Wireless Receiver for PAR-FL32MA-E | PAR-FA32MA-W | |
Wireless Handheld Remote Controller for SLZ PLA and PLFY models | PAR-SL101A-E | |
Wireless Receiver for PAR-SL101A-E on PLA-NL and PLFY-ELNEMU models | PAR-SR4LU-E | |
Wireless Remote Receiver Panel | PAR-SR3LA-E | |
Lineset | 10 x 3/8 x 10 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-10 |
100 x 3/8 x 65 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-100 | |
15 x 3/8 x 15 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-15 | |
30 x 3/8 x 30 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-30 | |
50 x 3/8 x 50 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-50 | |
65 x 3/8 x 65 x 5/8 Lineset Twin-Tube Insulation | MPLS385812T-65 | |
Power Supplies & Auxiliary Components | 3-Pin Wiring Harness | PAC-715AD |
5-Pin Wiring Harness | PAC-725AD | |
Filter | High Efficiency Filter Element | PAC-SH59KF-E |
Condensate | Blue Diamond Advanced Mini Condensate Pump w Reservoir Sensor 208-230V recommended | X87-721 |
Blue Diamond MaxiBlue Advanced Mini Condensate Pump w Reservoir Sensor 110V up to 48000 BTUH recommended | X87-711 | |
Blue Diamond MegaBlue Advanced Condensate Pump w Reservoir Sensor | X87-835 | |
Blue Diamond Sensor Extension Cable 15 Ft | C13-103 | |
Refco Condensate Pump 100-240 VAC up to 120000 BTUH | COMBI | |
Sauermann Condensate Pump | S130-230 | |
Wired Remote Controller | Deluxe Wired MA Remote Controller 1 | PAR-42MAAUB |
Simple Direct Wired Remote Controller | PAC-SDW01RC-1 | |
Simple MA Remote Controller | PAC-YT53CRAU-J | |
Touch MA Wired Remote Controller 1 | PAR-CT01MAU-SB | |
Remote Sensor | Flush Mount Remote Temperature Sensor for SEZ SLZ SVZ and all P-Series models | PAC-USSEN002-FM-1 |
Wall Mount Remote Temperature Sensor | PAC-SE41TS-E | |
Wireless temperature and humidity sensor for the Comfort app | PAC-USWHS003-TH-1 | |
Control Interface | Airzone Wired Blueface Controller Black | AZZBSBLUEZEROCN |
Airzone Wired Blueface Controller White | AZZBSBLUEZEROCB | |
Airzone Wireless Lite Controller Black | AZZBSLITERN | |
Airzone Wireless Lite Controller White | AZZBSLITERB | |
Airzone Wireless Think Controller Black | AZZBSTHINKRN | |
Airzone Wireless Think Controller White | AZZBSTHINKRB | |
IT Extender for kumo station | PAC-WHS01IE-E | |
kumo station for the Comfort app | PAC-WHS01HC-E | |
Operation and Error Status Output Adapter | PAC-SF40RM-E | |
Procon BACnet and Modbus Interface | PAC-UKPRC001-CN-1 | |
Thermostat Interface for 3rd Party Thermostats | PAC-US445CN-1 | |
Wireless Interface Adapter for the Comfort app | PAC-USWHS002-WF-2 | |
Disconnect Switch | 30A 600V UL fits 2 X 4 utility box - Black | TAZ-MS303 |
30A 600V UL fits 2 X 4 utility box - White | TAZ-MS303W | |
Casement | 3D Total Flow Unit | PLP-U160ELR-E |
Multi-function Casement | PAC-SJ41TM-E | |
Power Supplies and Auxiliary Components | Backup Heat Relay Kit Adapter for CN24 or CN152 Connector | CN24RELAY-KIT-CM3 |
Shutter Plate | PAC-SJ37SP-E | |
Grille with 3D i-see Sensor (required) | PLP-41EAEU |
Outdoor Unit Accessories
Category | Item | Model Number |
---|---|---|
Stand | 18 Dual Fan Stand | QSMS1802M |
24 Dual Fan Stand | QSMS2402M | |
Condenser Wall Bracket | QSWB2000M-1 | |
Condenser Wall Bracket - Stainless Steel Finish | QSWBSS | |
Outdoor Unit 3-14 inch Mounting Base Pair - Plastic | DSD-400P | |
Outdoor Unit Stand 12 High | QSMS1202M | |
M-Net Controller | M-Net Interface for P-Series | PAC-SJ95MA-E |
M-NET Converter | SW144-250 | |
Mini-Split Wire | 14 Gauge 4 wire Armored MiniSplit Cable 250 ft roll | SW144-250 |
14 Gauge 4 wire Armored MiniSplit Cable 50 ft roll | SW144-50 | |
14 Gauge 4 wire MiniSplit Cable 250 ft roll | S144-250 | |
14 Gauge 4 wire MiniSplit Cable 50 ft roll | S144-50 | |
Air Outlet Guide | Air Outlet Guide 1 Piece | PAC-SH96SG-E (two pieces are required) |
Control/Service Tool | ControlService Tool | PAC-SK52ST |
M- & P-Series Maintenance Tool Cable Set | M21EC0397 | |
Centralized Drain Pan | Maintenance Tool Interface | PAC-USCMS-MN-1 |
Centralized Drain Pan | PAC-SH97DP-E | |
Drain Socket | Drain Socket | PAC-SG61DS-E |
Power Supplies & Auxiliary Components | 3-Pin Wiring Harness | PAC-715AD |
5-Pin Wiring Harness | PAC-725AD | |
Hail Guards | Hail Guard | HG-A2 |
Wind Baffle | Front Wind Baffle | WB-PA3 (two pieces are required) |
Mounting Pad | Condensing Unit Mounting Pad 24 x 42 x 3 | ULTRILITE2 |
Snow/Rain Diverter | Snow/Rain Diverter | SRD-5 |
Indoor Unit Dimensions: PLA-AE24NL
Diagrams illustrating the dimensions and installation clearances for the PLA-AE24NL indoor unit. Key dimensions include:
- Main Body: 840mm (33-1/16 in) width, 840mm (33-1/16 in) depth, 298mm (11-3/4 in) height.
- Air Outlet Hole: 530mm (20-7/8 in).
- Air Intake Hole: 508mm (20 in).
- Suspension Bolt Pitch: 795mm (31-5/16 in) and 860mm (33-23/32 to 35-13/16 in).
- Drain Pipe Connection: VP-25 (32mm O.D. PVC tube), max lift of 850mm (33-15/32 in).
- Fresh Air Intake Hole: 100mm (3-15/16 in) diameter.
- Branch Duct Hole: Dimensions vary based on connection type.
- Installation Space Requirements: Minimum clearances are specified for service access and airflow. For example, 1000mm (39-3/8 in) or more above the unit, 1500mm (59-1/16 in) or more in front, and adequate space around for service access.
- Refrigerant Pipe Sizes: 6.35mm (1/4F), 9.52mm (3/8F), 12.7mm (1/2F), 15.88mm (5/8F).
Notes on Installation:
- Ensure proper grille selection.
- Reinforce suspension bolts for earthquake resistance.
- Use M10 or W3/8 suspension bolts.
- Ensure adequate insulation for branch ducts to prevent condensation.
- Refer to specific installation manuals for detailed requirements, especially when using optional accessories like the multi-function casement or high-performance filter.
Outdoor Unit Dimensions: PUZ-AK24NLHZ
Diagrams illustrating the dimensions and installation requirements for the PUZ-AK24NLHZ outdoor unit. Key aspects include:
- Installation Space: Minimum clearances are specified for airflow and service access. For example, a minimum of 15mm (19/32 in) on the sides, 1000mm (39-3/8 in) in the front, and 150mm (5-29/32 in) on the rear.
- Foundation Bolts: Requires M10 (W3/8) bolts for secure mounting.
- Piping-Wiring Connections: Connections can be made from four directions: Front, Right, Rear, and Below.
- Knock-Out Holes: Various knock-out holes are provided for conduit and piping connections, with specific dimensions indicated.
- Air Intake/Discharge: Locations for air intake and discharge are shown.
- Service Space: Minimum dimensions for service access are detailed.
- Refrigerant Pipe Connections: Gas pipe: 15.88mm (5/8F); Liquid pipe: 9.52mm (3/8F).
Certifications: AHRI Certified®, ETL Listed, Intertek.
Related Documents
![]() |
Mitsubishi Electric 36,000 BTU/h Ceiling Cassette: PLA-A36EA7 & PUZ-HA36NKA Detailed specifications and features for the Mitsubishi Electric 36,000 BTU/h Ceiling Cassette air conditioning system, including the PLA-A36EA7 indoor unit and PUZ-HA36NKA outdoor unit. Covers indoor and outdoor unit features, technical specifications, and available accessories. |
![]() |
Mitsubishi Electric PKA-AK24NL & PUZ-AK24NLHZ: 24,000 BTU/H Hyper Heat Pump System Specifications and Features Detailed specifications, features, and accessories for the Mitsubishi Electric PKA-AK24NL indoor unit and PUZ-AK24NLHZ outdoor unit, a 24,000 BTU/H Hyper Heat Pump system. Includes performance data, electrical requirements, and installation dimensions. |
![]() |
Mitsubishi Electric PKA-AK30NL & PUZ-AK30NLHZ Hyper Heat Pump System Overview Detailed specifications, features, and dimensions for the Mitsubishi Electric PKA-AK30NL indoor unit and PUZ-AK30NLHZ outdoor unit, a 30,000 BTU/H Hyper Heat Pump system. |
![]() |
Mitsubishi Electric PLA-A12EA7 & PUY-A12NKA7(-BS) Ceiling Cassette Air Conditioner Specifications Detailed specifications and features for the Mitsubishi Electric PLA-A12EA7 3'x3' Ceiling Cassette Indoor Unit and PUY-A12NKA7(-BS) Outdoor Unit, a 12,000 BTU/H cooling-only system. |
![]() |
Mitsubishi Electric 24,000 BTU/H Ceiling Cassette: PLA-A24EA8 & PUZ-HA24NHA1 Detailed specifications and features for the Mitsubishi Electric 24,000 BTU/H Hyper-Heating Universal Outdoor Ceiling Cassette system, including indoor and outdoor unit features, technical specifications, and accessories. |
![]() |
Mitsubishi MLZ-KX09NL & SUZ-AA09NL 9000 BTU/H Ceiling-Mounted Heat Pump System Specifications Detailed specifications, features, and dimensions for the Mitsubishi Electric MLZ-KX09NL indoor unit and SUZ-AA09NL outdoor unit, a 9000 BTU/H single-zone heat pump system. |
![]() |
Mitsubishi Electric 15,000 BTU/H Hyper-Heating Deluxe Wall-Mounted Air Conditioner - NTXWPH15B112AA & NTXSPB15B112AA Detailed specifications and features for the Mitsubishi Electric 15,000 BTU/H Deluxe Wall-Mounted Indoor Unit (NTXWPH15B112AA) and Hyper-Heating Outdoor Unit (NTXSPB15B112AA), including performance data, dimensions, and accessories. |
![]() |
Mitsubishi Electric SVZ-KP24NA & SUZ-KA24NAHZ HVAC System Specifications Comprehensive technical specifications, features, accessories, and dimensional data for the Mitsubishi Electric SVZ-KP24NA Multi-Position Air Handler and SUZ-KA24NAHZ Hyper-Heating Universal Outdoor Unit. |