Smart Meter USER MANUAL
Kun Lun Shan Road 189, Suzhou, Jiangsu, China 215000 | service@goodwe.com | www.goodwe.com
01 INTRODUCTION
GoodWe Smart Meter is designed with high precision, small dimensions, convenient operation and installation. It is available for both single-phase and three-phase grid system connection to detect voltage, current, power and energy, for working with inverters including SEMS systems for the purpose energy management.
Any fault or damage caused by misoperation or disobeyal against the rules on manual is beyond GoodWe warranty cover range.
PACKING LIST
- 1* Smart Meter
- 1* CT (Current Transformer)
- 1* Screw Driver
- 4* Cable Connection Terminals
- 1* USB Seal
- 1* RJ45-to-Pin Cable
NOTE:
- [1] A three-phase Meter will contain 3 CT clamps. Specifications are subject to the physical product.
- [2] Only suitable for RS485 cable connection on RJ45 port of GoodWe hybrid inverters.
02 OVERVIEW
2.1 SMART METER OVERVIEW
The Smart Meter has the following components:
- ① Power LED
- ② Energy Consumption LED
- ③ Communications LED
- ④ Reset Switch
- ⑤ USB Port
Diagram showing the front and side view of the Smart Meter with dimensions (36mm width, 85mm height, 66.5mm depth).
2.2 CT OVERVIEW
Diagram showing the Current Transformer (CT) with dimensions (inner diameter 32mm, outer diameter 45mm, length 16mm) and cable entry points.
03 INSTALLATION INSTRUCTION
3.1 INSTALLATION ENVIRONMENT
Protection Class: IP20 (for indoor use)
Operating Temperature: -20~60 ℃
3.2 INSTALLATION (with DIN track)
- Pull to release the retaining clip.
- Mount the Meter on the track and push the retaining clip up (a click sound indicates it is installed well).
Diagram illustrating the steps for mounting the meter on a DIN track.
3.3 WIRING CONNECTION
3.3.1 WIRING FOR SINGLE-PHASE METER
Diagram showing the wiring for a single-phase meter, including connections for Grid, Load, Inverter, RS485, and CT. It indicates the correct direction for the CT: House (K)→Grid (L).
Note: Incorrect connection or direction will cause incorrect data.
3.3.2 WIRING FOR THREE-PHASE METER
Diagram showing the wiring for a three-phase meter, including connections for Grid, Load, Inverter, RS485, and 3 CTs. It indicates the correct direction for the CT: House (K)→Grid (L).
Note:
- Correct direction of CT: House (K)→Grid (L).
- Ensure CT and corresponding supply cable are connected to the same phase.
- Incorrect connection or direction will cause incorrect data and may damage the meter.
04 ELECTRICAL DATA
MODEL | GM1000 | GM3000 |
---|---|---|
APPLICATION | Single-phase | Three-phase |
Nominal Voltage | 230Vac | 3L+N/400Vac |
Voltage Range | 0.7~1.2Un | 0.7~1.2Un |
Frequency | 50Hz/60Hz | |
Nominal Current | CT in: 120A/40mA | |
Current Range | 0.48A~120A | |
Self-Consumption | 3W max | |
Data Detection | Voltage/Current/Active Power/Reactive Power/Power Factor/Frequency | |
Energy Calculation | Active/Reactive Power Energy | |
Precision | Voltage/Current: Class I Active Power: Class I Reactive Power: Class 2 |
|
Comm. | With Inverter | |
RS485 (Bund Rate 9600 / ModBus Protocol / communication cable max. length 100m) |
05 INTERFACE
5.1 INDICATORS
- Power LED: Normal operation: ON
- Energy Consumption LED: Consuming: On; Generating: Blinking
- Communication LED: Transmitting data: Blinking; Resetting: Blink 5 times
5.3 USB PORT
For after-sales maintenance