ISD 840/950 KB-P (c/w Plug fan & EEV) Ducted Split System Indoor Units
Installation & Maintenance
Fig.1 Dimensions (mm)
Diagram showing unit dimensions, clearances, and connection points. Not to scale.
MODEL | W | X | Y | Z |
---|---|---|---|---|
ISD 840KB-P | 19 | 31 | 184 | 168 |
ISD 950KB-P | 58 | 84 | 156 | 155 |
MODEL | A | B |
---|---|---|
ISD 840K | 1070 | 960 |
ISD 950K | 1280 | 1165 |
Key features indicated in the diagram include: FILTER ACCESS EITHER SIDE, ELECTRICAL BOX, REFRIGERANT CONNECTIONS, ACCESS PANEL, MOUNTING CENTRES.
Clearance requirements: 500 MIN. CLEARANCE, 1000 MIN. CLEARANCE.
Note: The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.
ISD 840KB-P | 402 kg |
ISD 950KB-P | 453 kg |
General
These ISD indoor units are designed to be coupled with their respective OSA outdoor units. Units must be installed in accordance with all national and local safety codes.
There are two versions available:
- 1. Horizontal discharge (H)
- 2. Vertical discharge (V)
Combinations
Examples of unit combinations:
- One ISD 840KBH-P with one OSA 840RKTBG
- One ISD 950KBV-P with one OSA 950RKTBG
Option: Filters
Installation
Unpacking
The unit's supply air spigot has been secured inside the unit for ease of shipping. Remove the spigot and secure it in place using the existing screws.
Positioning & Mounting
Provide sufficient clearance to the access panels. Mount on a suitable level platform using vibration isolators. Access to fixing centres beneath the return air spigot can be made via the removable bungs in the spigot's base.
Condensate Drain
The unit has an internal sloping condensate drain tray. The trap should have a vertical height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain tray (refer Fig.2).
For long condensate pipe runs, fit a vent pipe near the drain trap. The top of the vent pipe must be at least 100 mm above the ISD unit's drain tray.
It is essential that the drainage system for the evaporator is checked by pouring water in the drain tray and seeing that it discharges at the end of the drain and does not overflow the drain tray.
Diagram Fig. 2 illustrates the condensate drain setup, showing a 'U' TRAP, VENT PIPE FOR LONG CONDENSATE DRAIN RUNS, and MINIMUM SLOPE 20 mm PER m (1 IN 50).
Indoor-Outdoor Unit Connections
Refer to the relevant OSA Outdoor Unit 'Installation & Maintenance' pamphlet for piping instructions. For wiring connections, refer to the Outdoor Unit wiring diagram.
Refrigeration Piping
Pipe Connection Sizes & Type
- Liquid: 16 mm OD (5\/8") sweat
- Suction: 35 mm OD (11\/8") sweat
The ISD is shipped from the factory with a pressurised holding charge of nitrogen. Immediately before removing any brazed pipe connection's seal, reduce holding charge to atmospheric pressure. Warning: failure to do so may cause injury.
Refer to the Outdoor Unit 'Installation & Maintenance' pamphlet for evacuation procedure and piping requirements.
Electrical Wiring
The electrical supply required (via the Outdoor Unit) is specified on the Outdoor Unit's wiring diagram.
Electrical work must be carried out by a qualified electrician in accordance with local supply authority regulations and the wiring diagram.
In a free blow or low resistance application, beware of exceeding the fan motor's full load amp limit (refer Outdoor Unit's wiring diagram).
To make the indoor fan switch off during de-ice cycle, refer to the Outdoor Unit wiring diagram for the appropriate changes.
Indoor Fan Speed
The fan speed is continuously variable via the 0-10V DC control signal applied between terminals 'FAN GND' and '0-10V'.
Once the maximum design air flow has been set (refer Commissioning), the fan speed can be controlled as follows:
1. ON/OFF
- a.) Connect 24V a.c. control signal to either 'LOW 24', 'MED 24V' or 'HIGH 24V', and 'COM 24V', or
- b) Wire a N/O control relay contact (or switch) between 'FAN 10V' and '0-10V'.
2. Variable Speed
Apply an external variable 0-10V DC control voltage to '0-10V' terminal. Connect 0V reference to 'FAN GND'.
Commissioning
Indoor Unit
- Check that the thermostat is correctly wired and set at the desired temperature.
- Link terminals 'FAN 10V' to '0-10V'. Adjust the 'POT' to deliver your maximum design air flow. Remove link 'FAN 10V' to '0-10V' when fan speed has been set.
- Check that any air filter (if fitted) is clean.
- Check that the fan runs freely without vibration.
- Check the airflow at each air outlet (diffuser) and adjust if necessary.
- Check condensate drain for free drainage.
- Run the unit in cooling mode and heating mode.
Maintenance
Weekly For First Four Weeks
- 1. Check air filter (if fitted); vacuum clean as necessary.
- 2. Check condensate drain for free drainage.
Monthly
- Check air filter (if fitted); vacuum clean as necessary.
Six Monthly
- 1. Check condensate drain for free drainage.
- 2. Check heat exchanger coil; vacuum or brush clean as necessary.
- 3. Check the tightness of the fan motor mountings.
- 4. Check that fan motor is free running.
- 5. Check tightness of electrical connections.
- 6. Check air supply at diffuser outlets.
Warning
This unit is designed for use ONLY with the refrigerant HFC-410A (R410A). The use of other refrigerants is NOT authorised or approved by the manufacturer and may cause operational problems such as poor performance and efficiency, loss of capacity, degradation of materials and refrigerant leaks.
The use of flammable or explosive materials as a refrigerant creates the additional risks of fire and explosion which may result in property damage, personal injury or death.
Note: The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.
Wiring Schematic
The wiring schematic details the connections for the ISD 950KBV-P SP EEV unit, illustrating the electrical layout for indoor fan motors, control signals, and optional components.
Key Components and Connections:
- Power In: Input power terminals for the unit.
- Indoor Fan Motor (IFM1, IFM2): Connections for the fan motors, including terminals for 24V, COM, COMP1, HEAT, LOW, MED, HIGH, E1, and GND.
- FR (Fan Relay), FRC (Fan Relay Coil): Components managing fan operation.
- POT (Potentiometer): A control for setting the maximum fan speed.
- 0-10V Terminal: Input for variable speed control signal.
- FAN GND: Ground reference terminal for fan speed control.
- EEV1, EEV2: Terminals for the Electronic Expansion Valve (EEV) option.
- EVAP OUTLET SENSOR 1/2: Connections for evaporator outlet sensors.
Control Notes:
- For external '0-10V' control, connect the control signal to the '0-10V' terminal and the 0V reference to 'FAN GND'.
- The POT is used to set the maximum fan revolutions required, typically when the FR is closed or 10V is applied to the 0-10V terminal.
Options available:
- 1. Electronic Expansion Valve
- 2. EC Plug Fan
Manufacturer & Drawing Details:
- Manufacturer: temperzone Itd
- Model: ISD 950-P
- Voltage In: 380\/415 V
- IFM Amps (max): 11.4 A
- Drawing Number: 291-044-687-ENG
- Revision: A
Further wiring diagrams can be found at www.temperzone.biz.