ISD 840/950 KB-P (c/w Plug fan & EEV) Ducted Split System Indoor Units

Installation & Maintenance

Fig.1 Dimensions (mm)

Diagram showing unit dimensions, clearances, and connection points. Not to scale.

Corner Loads (kg)
MODELWXYZ
ISD 840KB-P1931184168
ISD 950KB-P5884156155
MODELAB
ISD 840K1070960
ISD 950K12801165

Key features indicated in the diagram include: FILTER ACCESS EITHER SIDE, ELECTRICAL BOX, REFRIGERANT CONNECTIONS, ACCESS PANEL, MOUNTING CENTRES.

Clearance requirements: 500 MIN. CLEARANCE, 1000 MIN. CLEARANCE.

Note: The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.

Net Weight
ISD 840KB-P402 kg
ISD 950KB-P453 kg

General

These ISD indoor units are designed to be coupled with their respective OSA outdoor units. Units must be installed in accordance with all national and local safety codes.

There are two versions available:

Combinations

Examples of unit combinations:

Option: Filters

Installation

Unpacking

The unit's supply air spigot has been secured inside the unit for ease of shipping. Remove the spigot and secure it in place using the existing screws.

Positioning & Mounting

Provide sufficient clearance to the access panels. Mount on a suitable level platform using vibration isolators. Access to fixing centres beneath the return air spigot can be made via the removable bungs in the spigot's base.

Condensate Drain

The unit has an internal sloping condensate drain tray. The trap should have a vertical height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain tray (refer Fig.2).

For long condensate pipe runs, fit a vent pipe near the drain trap. The top of the vent pipe must be at least 100 mm above the ISD unit's drain tray.

It is essential that the drainage system for the evaporator is checked by pouring water in the drain tray and seeing that it discharges at the end of the drain and does not overflow the drain tray.

Diagram Fig. 2 illustrates the condensate drain setup, showing a 'U' TRAP, VENT PIPE FOR LONG CONDENSATE DRAIN RUNS, and MINIMUM SLOPE 20 mm PER m (1 IN 50).

Indoor-Outdoor Unit Connections

Refer to the relevant OSA Outdoor Unit 'Installation & Maintenance' pamphlet for piping instructions. For wiring connections, refer to the Outdoor Unit wiring diagram.

Refrigeration Piping

Pipe Connection Sizes & Type

The ISD is shipped from the factory with a pressurised holding charge of nitrogen. Immediately before removing any brazed pipe connection's seal, reduce holding charge to atmospheric pressure. Warning: failure to do so may cause injury.

Refer to the Outdoor Unit 'Installation & Maintenance' pamphlet for evacuation procedure and piping requirements.

Electrical Wiring

The electrical supply required (via the Outdoor Unit) is specified on the Outdoor Unit's wiring diagram.

Electrical work must be carried out by a qualified electrician in accordance with local supply authority regulations and the wiring diagram.

In a free blow or low resistance application, beware of exceeding the fan motor's full load amp limit (refer Outdoor Unit's wiring diagram).

To make the indoor fan switch off during de-ice cycle, refer to the Outdoor Unit wiring diagram for the appropriate changes.

Indoor Fan Speed

The fan speed is continuously variable via the 0-10V DC control signal applied between terminals 'FAN GND' and '0-10V'.

Once the maximum design air flow has been set (refer Commissioning), the fan speed can be controlled as follows:

1. ON/OFF

2. Variable Speed

Apply an external variable 0-10V DC control voltage to '0-10V' terminal. Connect 0V reference to 'FAN GND'.

Commissioning

Indoor Unit

  1. Check that the thermostat is correctly wired and set at the desired temperature.
  2. Link terminals 'FAN 10V' to '0-10V'. Adjust the 'POT' to deliver your maximum design air flow. Remove link 'FAN 10V' to '0-10V' when fan speed has been set.
  3. Check that any air filter (if fitted) is clean.
  4. Check that the fan runs freely without vibration.
  5. Check the airflow at each air outlet (diffuser) and adjust if necessary.
  6. Check condensate drain for free drainage.
  7. Run the unit in cooling mode and heating mode.

Maintenance

Weekly For First Four Weeks

Monthly

Six Monthly

Warning

This unit is designed for use ONLY with the refrigerant HFC-410A (R410A). The use of other refrigerants is NOT authorised or approved by the manufacturer and may cause operational problems such as poor performance and efficiency, loss of capacity, degradation of materials and refrigerant leaks.

The use of flammable or explosive materials as a refrigerant creates the additional risks of fire and explosion which may result in property damage, personal injury or death.

Note: The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.

Wiring Schematic

The wiring schematic details the connections for the ISD 950KBV-P SP EEV unit, illustrating the electrical layout for indoor fan motors, control signals, and optional components.

Key Components and Connections:

Control Notes:

Options available:

Manufacturer & Drawing Details:

Further wiring diagrams can be found at www.temperzone.biz.

Models: ISD 840KB-P Ducted Split System Indoor Units, ISD 840KB-P, Ducted Split System Indoor Units, Split System Indoor Units, System Indoor Units, Indoor Units

PDF preview unavailable. Download the PDF instead.

ISD 840950KB-P EEV IM 1020 Adobe PDF Library 17.0 Adobe InDesign 18.3 (Macintosh)

Related Documents

Preview Temperzone Econex Ducted Split Units: High Efficiency Air Conditioning
Explore Temperzone's Econex range of air-cooled ducted split air conditioning units, featuring R32 refrigerant for lower GWP, advanced inverter technology, and high performance for commercial and industrial applications. Discover features, specifications, and control options.
Preview Temperzone ISD 135K, 160K, 200K, 230K Ducted Split System Installation and Maintenance Guide
This guide provides installation and maintenance instructions for Temperzone ISD Ducted Split System R410A Indoor Units, including models ISD 135K, 160K, 200K, and 230K. It covers unit dimensions, mounting options, condensate drain, electrical wiring, and application considerations for optimal performance and noise reduction.
Preview Temperzone ISD 230K / OSA 230RKTH Ducted Split System Air Conditioner Technical Data
Technical data and specifications for the Temperzone ISD 230K / OSA 230RKTH Ducted Split System Air Conditioner, including performance data, dimensions, and safety features.
Preview Temperzone OSA 670RKTBQ R410A Split System Outdoor Unit Installation and Maintenance Guide
Comprehensive installation and maintenance guide for the Temperzone OSA 670RKTBQ Reverse Cycle R410A Split System Outdoor Unit, including general information, installation procedures, piping, electrical requirements, system checks, startup procedures, and maintenance schedules.
Preview Temperzone IMDL Series Ducted Fan Coil Units: Installation and Maintenance Guide
Comprehensive guide for the installation and maintenance of Temperzone IMDL 40Y, 60Y, 90Y, and 130Y ducted fan coil units, covering electrical wiring, fan control, and general installation procedures.
Preview Temperzone and Hitachi Air Conditioner Warranty Australia
Official warranty terms and conditions for Temperzone and Hitachi air conditioning systems in Australia, covering product ranges, warranty periods, claim procedures, and maintenance guidelines.
Preview Temperzone IMD Series Ducted Fan Coil Units: Installation and Maintenance
Comprehensive guide for the installation and maintenance of Temperzone IMD Series Ducted Fan Coil Units (models IMD 95Y, 135Y, 170Y, 210Y, 280Y) with EC motors, covering dimensions, electrical wiring, fan control, and commissioning.
Preview Temperzone ISD 324KYX OSA 324RKTFV Air Conditioner Specifications and Dimensions
Comprehensive technical specifications, dimensional data, and wiring schematics for the Temperzone ISD 324KYX Indoor Unit and OSA 324RKTFV Outdoor Unit air conditioning system. Features include cooling/heating capacity, electrical inputs, refrigerant details, and installation guidance.