Shinko KS2011.001E1: Instruction Manual Addendum

This document provides an addendum to the Shinko WCL-13A instruction manual, detailing key operation flowcharts and added functions.

******* To Our Valued Customers *******

The following functions marked with (*) have been added to Section “4. Key operation flowchart” of the Quick Reference [WCL-13A (No. WCL11JE3)]. Please read this sheet along with our Quick Reference [WCL-13A (No. WCL11JE3)].

4. Key Operation Flowchart

(*): Added functions and their setting items

CH1 Parameter Group

(CH2 is the same as CH1.)

[Display: P.1.d.1]
CH1 parameter group
[SET/RESET]
[Display: A.1.0]
Alarm 1 value
Setting range: (Table 4-6)
[SET/RESET]
[Display: (*) A.2.0]
Alarm 2 value
Setting range: (Table 4-6)
[SET/RESET]
[Display: (*) A.3.0]
Alarm 3 value
Setting range: (Table 4-6)
[SET/RESET]
[Display: (*) A.4.0]
Alarm 4 value
Setting range: (Table 4-6)
[SET/RESET]
[Display: H.0.0]
Heater burnout alarm 1
20A: 0.0 to 20.0A
100A: 0.0 to 100.0A
Setting items to be continued

CH1 Function Group

(CH2 is the same as CH1.)

[Display: F.n.c. 1]
CH1 function group
[SET/RESET]
[Display: A.1.F.n]
Alarm 1 type
Selection item: (Table 4-3)
[SET/RESET]
[Display: (*) A.2.F.n]
Alarm 2 type
Selection item: (Table 4-3)
[SET/RESET]
[Display: (*) A.3.F.n]
Alarm 3 type
Selection item: (Table 4-3)
[SET/RESET]
[Display: (*) A.4.F.n]
Alarm 4 type
Selection item: (Table 4-3)
[SET/RESET]
[Display: A.1.H.Y]
Alarm 1 hysteresis
0.1 to 100.0°C (°F)
1 to 1000 (DC input)
[SET/RESET]
[Display: (*) A.2.H.Y]
Alarm 2 hysteresis
0.1 to 100.0°C (°F)
1 to 1000 (DC input)
[SET/RESET]
[Display: (*) A.3.H.Y]
Alarm 3 hysteresis
0.1 to 100.0°C (°F)
1 to 1000 (DC input)
[SET/RESET]
[Display: (*) A.4.H.Y]
Alarm 4 hysteresis
0.1 to 100.0°C (°F)
1 to 1000 (DC input)
[SET/RESET]
[Display: A.1.d.Y]
Alarm 1 action delay timer
0 to 9999 sec
[SET/RESET]
[Display: (*) A.2.d.Y]
Alarm 2 action delay timer
0 to 9999 sec
[SET/RESET]
[Display: (*) A.3.d.Y]
Alarm 3 action delay timer
0 to 9999 sec
[SET/RESET]
[Display: (*) A.4.d.Y]
Alarm 4 action delay timer
0 to 9999 sec
[SET/RESET]

Event Output 1

  • Alarm
  • Loop break alarm
  • Loop break alarm + Alarm

Event Output 2

  • Alarm
  • Loop break alarm
  • Loop break alarm + Alarm
  • Heater burnout alarm
  • Heater burnout alarm + Alarm
  • Heater burnout alarm + Loop break alarm
  • Heater burnout alarm + Alarm + Loop break alarm

SV Rise Rate

[Display: r.F.U]
SV rise rate
0 to 9999°C/min (°F/min)
0.0 to 999.9°C/min (°F/min)
0 to 9999/min (DC input)
[SET/RESET]
Setting items to be continued

Special Function Group

[Display: P.1.d.1]
Special function group
[SET/RESET]
[Display: Lock]
Set value lock
  • : Unlock
  • : Lock 1
  • : Lock 2
  • : Lock 3
Setting items to be continued

PDF preview unavailable. Download the PDF instead.

KS2011 001E1 WCL-13A KS2011.001E1 WCL-13A 英文挿入用紙 DocuCom PDF Driver 9.00 for NT

Related Documents

Preview Shinko WCL-13A: 2ch デジタル指示調節計 取扱説明書
プラグイン形 2チャンネル デジタル指示調節計 WCL-13A の設置、操作、仕様、トラブルシューティングに関する包括的な取扱説明書。Shinko Technos 株式会社製。
Preview Shinko ACS2 Digital Indicating Controller Instruction Manual
Comprehensive instruction manual for the Shinko ACS2 Digital Indicating Controller, covering installation, functions, operation, wiring, and safety precautions. Learn about safe usage and optimal performance.
Preview Shinko QMC1-C Communication Expansion Module Instruction Manual
Comprehensive instruction manual for the Shinko QMC1-C Communication Expansion Module, detailing installation, wiring, operation, MODBUS RTU and SIF communication protocols, and system configuration for industrial automation.
Preview Shinko QAM1-4 Analog I/O Module Instruction Manual
This instruction manual provides comprehensive guidance for the Shinko QAM1-4, a 4-point analog I/O module from Shinko Technos Co., Ltd., designed for industrial automation and measurement systems. It details installation, operation, safety, and communication protocols like MODBUS RTU and CUnet.
Preview Shinko DCL-33A DIN Rail Mounted Indicating Controller Instruction Manual
Instruction manual for the Shinko DCL-33A DIN Rail Mounted Indicating Controller, detailing safety precautions, specifications, functions, terminal arrangement, operation, and wiring.
Preview Shinko AER-101-ORP Digital Indicating ORP Meter Instruction Manual
This manual provides comprehensive instructions for the Shinko AER-101-ORP Digital Indicating ORP Meter, covering mounting, functions, operations, and safety precautions. Learn how to safely and correctly use this advanced ORP meter.
Preview Shinko HR-700シリーズ ハイブリッド記録計:コンパクト、高視認性産業用データロガー
Shinko HR-700シリーズハイブリッド記録計の仕様、特徴、寸法。コンパクト設計、大型LED表示、IP65準拠、産業オートメーション向けの多様な入力オプションを特長としています。
Preview Shinko QTC1 Control Module: Mounting and Wiring Instructions
Detailed mounting and wiring instructions for the Shinko QTC1 series control module, covering safety precautions, installation, communication settings, and technical specifications for industrial automation.