APC MGETM GalaxyTM 3000 Installation and User Manual

Document Number: 51030375EN/CC

Introduction

Thank you for selecting an APC by Schneider Electric product to protect your electrical equipment. The MGETM GalaxyTM 3000 range has been designed with the utmost care. This manual provides guidance to take full advantage of the many features of your UPS.

APC by Schneider Electric pays great attention to the environmental impact of its products. Measures that have made MGETM GalaxyTM 3000 a reference in environmental protection include:

  • The eco-design approach used in product development.
  • The elimination of harmonic disturbances reinjected into the AC source.
  • Production in an ISO 14001 certified factory.
  • Recycling of MGETM GalaxyTM 3000 at the end of its service life.

For the entire range of APC by Schneider Electric products and options for the MGETM GalaxyTM 3000 range, visit www.apc.com or contact your APC by Schneider Electric representative.

All products in the MGETM GalaxyTM 3000 range are protected by patents and implement original technology. Equipment may be modified without notice to account for evolving standards and technology. Technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric. This document may be copied only with the written consent of APC by Schneider Electric. Authorized copies must be marked "MGETM GalaxyTM 3000 Installation and User Manual n 5103037500".

Safety

Safety Rules

Safety of Persons

The UPS must be installed in a room with restricted access, accessible only to qualified personnel, according to standard EN50091-1-2. A UPS has its own internal power source (the battery). Consequently, power outlets may be energized even if the UPS is disconnected from the AC-power source.

Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. The UPS must be properly earthed.

The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, observe the following directives:

  • Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the documentation.
  • Never burn the battery (risk of explosion).
  • Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
  • Comply with all applicable regulations for the disposal of the battery.
  • Avoid contact with the cooling liquid (eyes and skin). If contact occurs, rinse well with water.

Product Safety

A protection circuit breaker must be installed upstream and be easily accessible. Never install the UPS near liquids or in an excessively damp environment. Never let a liquid or foreign body penetrate inside the UPS. Never block the ventilation grates of the UPS. Never expose the UPS to direct sunlight or a source of heat.

Special Precautions

The UPS connection instructions contained in this manual must be followed in the indicated order. Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS.

If the UPS must be stored prior to installation, storage must be in a dry place. The admissible storage temperature range is -10°C to +45°C. If the UPS remains de-energized for a long period, it is recommended to energize the UPS for 24 hours, at least once every month, to charge the battery and avoid possible irreversible damage.

The UPS is designed for normal climatic and environmental operating conditions as defined in the appendices chapter: altitude, ambient operating temperature, relative humidity, and ambient transport and storage conditions. Using the UPS within the given limits guarantees its operation but may affect the service life of certain components, particularly the battery and its autonomy. The maximum storage time of the UPS is limited due to the need to recharge its integrated battery.

Unusual operating conditions may justify special design or protection measures:

  • Harmful smoke, dust, abrasive dust.
  • Humidity, vapor, salt air, bad weather or dripping.
  • Explosive dust and gas mixture.
  • Extreme temperature variations.
  • Bad ventilation.
  • Conductive or radiant heat from other sources.
  • Cooling water containing acid or impurities which may cause scale, silt, electrolysis or corrosion of converter parts exposed to the water.
  • Strong electromagnetic fields.
  • Radioactive levels higher than those of the natural environment.
  • Fungus, insects, vermin, etc.
  • Battery operating conditions.

The UPS must always be installed in compliance with:

  • The requirements of HD 384.4.42 S1/A2 - Chapter 42: Protection from thermal effects.
  • Standard IEC 60364-4-482 - Chapter 482: Fire protection.

Foreword

Using This Document

Information may be found primarily by consulting the contents and the index.

Pictograms

The following pictograms are used in this document:

  • Important instructions that must always be followed.
  • ℹ️ Information, advice, help.
  • LED OFF
  • ? LED ON
  • ? LED flashing
  • ? Earth cables
  • ? Other cables

Graphical Display Symbols:

  • 8.8.8.8: Vertical selection
  • 8.8.8.8: Other selection
  • 8.8.8.8: Enter / Confirm
  • 8.8.8.8: Details
  • 8.8.8.8: Circular menu
  • 8.8.8.8: Graphical display
  • 8.8.8.8: Digital display
  • 8.8.8.8: Return to previous display
  • 8.8.8.8: Delete
  • 8.8.8.8: Access to measurements
  • 8.8.8.8: Access to mimic diagrams

Contents

The document is structured into the following main sections:

  • 1. Presentation
  • 2. Installation
  • 3. Final Checks
  • 4. Operation
  • 5. Maintenance
  • 6. Environment
  • 7. Appendices

1. Presentation

1.1 MGETM GalaxyTM 3000

Details on UPS cubicle and external battery cabinet dimensions, weights, and backup times are provided in the following tables:

UPS Cubicle Dimensions and Weights

UPS power rating (kVA)Dimensions in mm (H x W x D)Weight in kg (UPS with built-in batteries)Backup time (5-year batteries)Backup time (10-year batteries)
0 min10 min15 min7 min12 min
10/151420 x 610 x 565210330384381381
20/301600 x 640 x 685240472572572572

External Battery Cabinet / Auxiliary Cabinet Dimensions and Weights

UPS power rating (kVA)Dimensions (H x W x D) in mmWeight in kg (cabinet alone)Backup time (5-year batteries)Backup time (10-year batteries)
0 min15 min30 min60 min15 min30 min60 min
101600 x 850 x 6851603953954405573004492x389
151606826828402x4404495692x569
201602x5765047522x624
301602x7656612x6003x660

1.2 Access to Connections

Accessing connection points requires removing cover panels. The process involves:

  1. Pulling the bottom of each panel out and away from the UPS.
  2. Lifting the panel to free the top part.
  3. Removing screws securing wave-shaped cover panels (if present).
  4. Unclipping the wave-shaped cover panels.
  5. Breaking transport tabs.

Key connection areas include:

  • Man-machine interface (30-38)
  • Communications rack (5)
  • AC input switch and battery circuit breaker (6, 18, 19)
  • Manual bypass switch (7, 22)
  • Terminal blocks (8, 23, 24, 25, 28, 47)
  • Relay communications card slot (15)

1.3 Connection Section

Different connection configurations are detailed:

  • Version with common Normal and Bypass AC inputs: Features RJ45 for external synchronization (9), RJ12 for exchange currents (10), external bypass connector (11), RJ45 for data exchange (12), CAN communication LED (13), EPO terminal block (14), relay communications card slot (15), optional card slots (16), battery circuit breaker control terminal (17), Normal AC input switch (18), battery circuit breaker (19), after-sales support circuit breaker (20), circuit breaker cover (21), manual bypass switch (22), Normal AC source input terminal block (23), output terminal block (25), main earthing connector (26), and secondary earthing connector (27).
  • Version with external battery: Includes terminal block for battery circuit breaker control wiring (17) and terminal block for external battery cabinets (28).
  • Version with separate Normal and Bypass AC inputs: Features Normal AC source input terminal block (23), Bypass AC source input terminal block (24), output terminal block (25), common neutral terminal (47), and accessory terminal for second neutral conductor (29).

1.4 Man-Machine Interface

The man-machine interface consists of a graphical display (30), menu key (31), function keys (32), help key (33), load protected LED (34), minor fault LED (35), major fault LED (36), ON button (37), and OFF button (38).

1.5 Relay Communications Card

The relay communications card (installed in slot 15) provides status information via output terminal blocks (43) and can receive input signals via input terminal blocks (44). It is secured by cover screws (39) and card screw holes (40).

2. Installation

2.1 Location

Ensure adequate clearances around the UPS cubicle: greater than 250 mm at the front and greater than 700 mm at the back. Proper clearances prevent abnormal temperature rise and facilitate maintenance. The UPS must be installed in a room with restricted access, for qualified personnel only.

2.2 Layout of Additional Cabinets

When installing additional battery cabinets, follow these steps:

  1. Position the UPS.
  2. Block the front casters.
  3. Remove lateral front panels and battery protection side panels.
  4. Remove foam protection strips and cardboard caps from battery elements.
  5. Cut and remove strapping around battery elements.

Do not place anything on top of the UPS to ensure easy maintenance.

2.3 Required Protective Devices and Cable Cross-Sections

Recommended Upstream Protection

UPS power rating (kVA)Upstream circuit-breaker
10 - 15 kVAC60H-C-40A
20 - 30 kVANC100H-D-80A

Curve H for the upstream circuit breaker may be replaced by curve N or L, depending on the installation.

Recommended Downstream Protection

UPS power rating (kVA)Downstream circuit breakerFuse URGB or URC
10 - 15 kVAC60L-Z-10A12A
20 kVAC60L-C-4A, C60L-Z-10A14A
30 kVAC60L-C-6A, C60L-Z-16A16A

Curve L for the downstream circuit breaker may be replaced by curve N or H, depending on the installation. These protections ensure discrimination for each output circuit. Failure to follow these recommendations can lead to longer power breaks on other output circuits during a short-circuit.

Required Cable Cross-Sections

UPS power rating (kVA)Copper cable cross-sections (Normal AC source, Bypass AC source and Load circuits <100m)Battery circuits (<15m)
10 kVA6 mm²10 mm²
15 kVA10 mm²16 mm²
20 kVA16 mm²25 mm²
30 kVA25 mm²35 mm²

Terminal-block cable capacity: 16 to 35 mm². Capacity for earthing conductor: 6 mm².

2.4 Installation Depending on System Earthing Arrangement (SEA)

Diagrams illustrate installation for various SEA configurations:

  • Single UPS unit with common Normal and Bypass AC inputs: Applicable for TT, TN, and IT systems with neutral distributed or not distributed. Diagrams show connections to Main Low-Voltage Switchboard (MLVS) and load.
  • Single UPS unit with separate Normal and Bypass AC inputs: Applicable for TT, TN, or IT systems with neutral distributed on one or both inputs, or neutral not distributed. Diagrams show connections from MLVS 1 and MLVS 2.
  • Single UPS unit with separate Normal and Bypass AC inputs, supplied by separate sources: Similar to the above but emphasizes separate MLVS sources.
  • Frequency converter (without Bypass AC input): For TT, TN, or IT systems with neutral distributed or not distributed.
  • Parallel configuration without external bypass cubicle: For common or separate AC inputs (max two units in parallel). Notes that a residual-current earth-leakage protection system must be installed upstream.
  • Parallel configuration with external bypass cubicle: For common or separate AC inputs (max four units in parallel). Diagrams show connections via the bypass cubicle.

2.5 Connection of Power Cables in a Single UPS Unit

Detailed connection procedures are provided for:

  • UPS with common Normal and Bypass AC inputs: Connect earthing conductors to connectors 26 and 27, Normal AC source to terminal block 23, and load conductors to terminal block 25. Fit cable ties 46.
  • UPS with separate Normal and Bypass AC inputs: Connect earthing conductors to 26 and 27. Connect neutral conductors to common terminal 47 (using accessory terminal 29 if cross-section > 10 mm²). Connect Normal AC source phases to 23, Bypass AC source phases to 24, and load conductors to 25. Fit cable ties 46.
  • Frequency converter: Connect earthing conductors to 26 and 27. Connect the neutral conductor of the Normal AC source to 47. Connect Normal AC source phases to 23, and load conductors to 25. Fit cable ties 46. Do not connect anything to the Bypass AC source input terminal block 24.

2.6 Connection of Power Cables for Parallel UPS Units

Procedures are detailed for:

  • Redundant parallel configuration (max two UPS units): For common or separate AC inputs, showing connections to AC source and load terminal blocks in each UPS unit. Accessory terminals 29 are noted for load conductors if cross-section > 10 mm².
  • Parallel configuration for increased capacity (max four UPS units): This configuration requires an external bypass cubicle. Diagrams show connections from UPS units to the bypass cubicle's terminals (48, 49, 50, 51) for AC sources and loads.

2.7 Auxiliary Interconnections Between UPS Units in Parallel Configurations

Details on connecting UPS units in parallel for redundancy or increased capacity:

  • Redundant parallel configuration (max two UPS units): Describes linking exchange-current connectors (XMS02, XMS03) and CAN // interconnections (XMS05, XMS06) between UPS units, including plug usage (blue/red).
  • Parallel configuration for increased capacity (max four UPS units): Describes creating loops for exchange-current interconnections (XMS02, XMS03) and daisy-chaining for CAN // interconnections (XMS05, XMS06), including plug usage. Also details interconnections with an external bypass cubicle, including fitting jumpers and creating loops for auxiliary terminal blocks.

Fitting the protection cover for auxiliary interconnection cables: Instructions are given to fit the plastic protection cover to protect users and secure cables. Caution is advised against reversing RJ12 and RJ45 connectors.

2.8 Connection of the Emergency Power Off Terminal Block

To connect the Emergency Power Off (EPO) function:

  1. Remove the jumper from terminal block 14.
  2. Connect the emergency power off NC contact to terminals 1 and 2.
  3. Tie the cable down.

In parallel configurations, a single EPO button with a separate contact for each UPS unit is required, which must also open upstream protection circuit-breakers.

2.9 Connection of the Relay Communications Card

To connect the relay communications card:

  1. Isolate and lock out all power sources for the card.
  2. Remove the card cover (41) secured by screws (39).
  3. Run communication cables through entry holes (42).
  4. Connect conductors to input (44) and output (43) terminal blocks.
  5. Replace the cover and secure cables with screws (45).
  6. Label power source locations.
  7. Insert the card into its slot and secure it with screws (40).

Characteristics of the contacts: Details are provided for output contacts (permissible voltage/current) and input contacts (switched voltage/consumption). Cable specifications are also listed.

Communications card connection example: Illustrates a connection setup, emphasizing isolation of VLSV sources.

2.10 Securing the Control/Communications Cables

  • Single UPS unit: Separate control and communication cables from power cables. Run them together in front of protection panels and tie them down.
  • Parallel UPS units: Fit a clip-on ferrite for EMC compliance. Secure cables with ties and clamping rings.

2.11 Power Connections for an External Battery Cabinet

Use only battery cables supplied by APC by Schneider Electric to ensure EMC compliance.

2.12 Assembly and Connection of an Empty Battery Cabinet

Mounting the battery circuit breaker kit: Secure the base plate (52), connector XR1, and temperature sensor. Attach the front plate after connecting batteries to the circuit breaker. Only one circuit breaker is needed for multiple cabinets.

Mounting the shelves and the battery cells: Install shelves at even distances. Ensure minimum clearance between battery cells and shelves. Secure shelves, place battery cells, secure them, and interconnect them. Interconnect all shelves and connect the assembly to the battery circuit breaker. This assembly must be carried out by certified personnel.

2.13 Control Connections for an External Battery Cabinet

Connect wires for the XR1 connector and temperature sensor to specific UPS connectors (17 and XMD3 53). Route cables behind the communications rack (5) and through troughs.

2.14 Connection of an Input Isolating Transformer

Diagrams show connections for input transformers for common AC sources (A), separate Bypass AC sources (B), and separate Normal AC sources (C).

2.15 Connection of an Output Isolating Transformer

Diagram shows connection of an output isolating transformer to the load.

3. Final Checks

3.1 Check on the Position of the Stop on the Manual Bypass Switch

The position of the stop on the manual bypass switch (22) is critical for correct operation and safety:

  • Single UPS: The stop must be positioned to the right to block switching to the TEST ISO position.
  • Parallel UPS (with or without external bypass cubicle): The stop must be positioned to the left to block switching to the TEST BP position.

Diagrams illustrate the switch positions and display messages for static switch status.

4. Operation

All system start-up and compliance operations must be carried out by trained and certified personnel.

4.1 Shutting Down a Single UPS

  1. Press the OFF button (38).
  2. Confirm by pressing the function key (32) marked ?. The load is supplied via the bypass.
  3. Set the battery circuit breaker (19) to OFF.
  4. Set the Normal AC input switch (18) to OFF.

4.2 Restarting Single UPS

  1. Ensure the bypass switch (22) is in the Normal position.
  2. Set the Normal AC source input switch (18) to ON.
  3. Wait 10 seconds for initialization.
  4. Set the battery circuit breaker (19) to ON. The UPS starts automatically.

If the load protected LED (34) does not light up, press the ON button (37). If fault LEDs (35 or 36) are on, consult section 5.1.

4.3 Shutting Down a Parallel Configuration

  1. Press the OFF button (38) on each UPS unit.
  2. Confirm by pressing the function key (32) marked ?. The load is supplied via the bypass.
  3. Set the battery circuit breaker (19) in each unit to OFF.
  4. Set the input switch (18) in each unit to OFF.

4.4 Restarting a Parallel Configuration

  1. Check bypass switch (22) is in Normal position.
  2. Verify bypass cubicle switches (Q4S, Q5N, Q3BP) are in correct positions.
  3. On each UPS unit: Set Normal AC source input switch (18) to ON.
  4. Wait 10 seconds.
  5. Set battery circuit breaker (19) to ON. UPS units start automatically.

If LED (34) remains OFF, press the ON button (37). If fault LEDs (35 or 36) are on, consult section 5.1.

4.5 Operating Modes

  • Normal (double conversion) mode: The default mode.
    • Normal AC source available: LED (34) ON. Load protected by UPS.
    • Normal AC source not available: LED (34) flashing, LED (35) ON, buzzer sounds. Load supplied by battery.
  • ECO mode (single UPS only): Reduces power consumption.
    • Bypass AC source available: LED (34) ON. Load supplied in ECO mode.
    • Bypass AC source not available: LED (34) ON, buzzer sounds. Load supplied in Normal mode.
    • Both AC sources unavailable or out of tolerance: LED (34) flashing, LED (35) ON, buzzer sounds. Load supplied by battery.

4.6 Operation on Battery Power

  • Transfer to battery power: LED (34) flashing, LED (35) ON, buzzer sounds. Load supplied by battery.
  • Low battery warning: LED (34) flashing, LED (35) ON, buzzer sounds. Low battery backup time remaining; close applications.
  • End of battery power: LED (35) ON, buzzer sounds. Load transferred to AC BYPASS if available.

4.7 Return of Normal AC Source

The UPS restarts automatically when AC power is restored, unless this function is disabled.

4.8 Restart on Battery Power

The UPS can start without Normal AC power. LED (34) flashing, LED (35) ON, buzzer sounds. This function is unavailable if the UPS has been completely de-energized.

4.9 UPS Personalization

Personalization requires the manual bypass switch (22) in the TEST BP position. Access settings via the menu key (31) and function keys (32). A password is required.

Personalization Options:

FunctionFactory SettingOptions
UPS operating modeNormalECO
UPS automatic startDisabledEnabled
Authorised number of starts41 to 255
Delay before reset of number of executed automatic starts4 seconds1 to 60 seconds
Frequency50 Hz ± 8%60 Hz ± 0.5 - 1 - 2 - 4 %
Tolerance for Bypass AC source1 Hz / s2 Hz / s
Rate of synchronisation with Bypass AC sourceDisabledEnabled
External frequency synch.DisabledEnabled
Transfer to bypassEnabledDisabled
Transfer to bypass with Bypass AC source out of toleranceEnabledDisabled
Low battery warning threshold (monitor inactive)40% remaining backup time20 - 60 - 80% remaining backup time
Low battery warning threshold (monitor active)4 minutes of battery backup time1 to X minutes of battery backup time
Interval between two battery tests30 daysevery 1 to 3 months
Deep dischargeNot allowedAllowed
Automatic parameter identificationEnabledDisabled

Transformers

Normal AC input transformerBypass AC input transformerOutput transformer
Factory settingNoneNoneNone
OptionsPresentPresentPresent

4.10 Relay Contacts (Communications Card)

The relay communications card provides status signals:

  • Inputs: UPS ON (1.A), UPS OFF (1.B). Options include room temperature fault, transfer to bypass disabled, etc.
  • Outputs: General alarm (1.1), Battery fault (1.2), Load on UPS (1.3), Load on automatic bypass (1.4), Load on battery power (1.5), Low battery warning (1.6). Many other options are available for all contacts.

Contacts are Normally Open (NO). The general alarm can be tested by opening the battery circuit breaker.

4.11 Display Functions

The man-machine interface provides various functions:

  • Welcome screen: Displays load status and basic information.
  • Main menu: Access to Measurements, Mimic diagrams, Status, Settings, and Controls.
  • Measurements: Detailed electrical measurements (Power, Current, Voltage, Frequency, Ratios).
  • Status: Timestamped statistics and history of events.
  • Settings: Configuration options including Language, Date/Time, Display contrast, Buzzer volume, Personalization, Output voltage, Password, and Relay-contact settings.
  • Controls: Functions like Clear fault, Equalize battery, Forced transfer to UPS/Bypass, Resynchronization, Lamp test, and Buzzer OFF.
  • Start-up: Options for starting the UPS, shutdown, and transfer to manual bypass.

5. Maintenance

5.1 Identification of Alarms

Alarms are indicated by LEDs (34, 35, 36) and the buzzer. Detailed information, causes, and required actions are displayed on the screen. Select the alarm, then hold the function key to view details.

  • LED 34 (off), LED 35 (intermittent): Normal AC source not available.
  • LED 34 (off), LED 35 (intermittent): UPS shut down following end of battery power.
  • LED 34 (off), LED 35 (intermittent): UPS shut down on fault requiring servicing.

5.2 Life Cycle Monitoring (LCM)

The LCM function provides maintenance advice:

  • “End of warranty check recommended”
  • “Technical check recommended”
  • “Battery check required”

These messages are accompanied by minor fault LED (35) and buzzer. They can be cleared by pressing a function key.

5.3 UPS Isolation

Procedures for isolating the UPS for maintenance are detailed for various configurations:

  • Single UPS: Shut down UPS, turn manual bypass switch (22) from NORMAL to TEST BP, then to BYPASS. Set battery circuit breaker (19) and input circuit breaker (18) to OFF.
  • Frequency converter: Shut down UPS, set battery (19) and input (18) circuit breakers to OFF, turn manual bypass switch (22) from Normal to Bypass.
  • UPS operating in ECO mode: If supplied by Bypass, turn bypass switch (22) from NORMAL to TEST BP, then to BYPASS. Set battery (19) and input (18) breakers to OFF. If supplied by UPS, shut down UPS, turn bypass switch (22) from NORMAL to TEST BP, then to BYPASS. Set battery (19) and input (18) breakers to OFF.
  • Parallel UPS configuration without external bypass cubicle: For isolating one UPS, shut down, turn bypass switch (22) to TEST ISO, then ISOLATED. Set battery (19) and input (18) breakers to OFF. For isolating the second unit, follow similar steps but use TEST BP and BYPASS positions.
  • Parallel UPS configuration with external bypass cubicle: To isolate one UPS, shut down, turn bypass switch (22) to TEST ISO, then ISOLATED. Set battery (19) and input (18) breakers to OFF. To isolate all UPS units, shut down each, set bypass cubicle switches (Q3BP, Q5N, Q4S) appropriately, turn each UPS bypass switch (22) to TEST ISO, then ISOLATED, and set battery (19) and input (18) breakers to OFF.

5.4 Return to the Normal Position

Procedures for returning UPS units to normal operation after maintenance:

  • Single UPS: Turn bypass switch (22) from BYPASS to TEST BP, then to NORMAL. Set input (18) and battery (19) circuit breakers to ON.
  • Frequency converter: Turn bypass switch (22) from BYPASS to NORMAL. Set input (18) and battery (19) circuit breakers to ON. Press ON button (37).
  • Parallel UPS configuration without external bypass cubicle: For a UPS with bypass switch in BYPASS position, turn switch (22) from BYPASS to TEST BP, then TEMP BP, then NORMAL. Set input (18) and battery (19) breakers to ON. For a UPS with switch in ISOLATED position, turn switch (22) from ISOLATED to TEST ISO, then NORMAL. Set input (18) and battery (19) breakers to ON. Refit the stop on the manual bypass switch.
  • Parallel UPS configuration with external bypass cubicle: Ensure bypass switches (22) are in NORMAL. Set bypass cubicle switches (Q4S, Q5N, Q3BP) as required. Set input (18) and battery (19) circuit breakers to ON. UPS units start automatically.

5.5 Training Center

APC by Schneider Electric offers technical training courses in English and French at centers in France, the United States, Singapore, and China. Details and online registration are available at http://powerlearning.apc.com.

6. Environment

This product is designed with environmental respect. It does not contain CFCs or HCFCs and is manufactured in an ISO 14001 certified factory. APC by Schneider Electric undertakes to recycle UPS products at the end of their service life through certified companies. Packing materials must also be recycled.

Warning: This product contains lead-acid batteries. Lead is a dangerous substance for the environment if not recycled correctly. The cooling liquid (propylene glycol base) is environment-friendly. Do not dump cooling liquid or residues in sewage systems or outdoors; use suitable recipients for disposal according to regulations.

For further information, consult www.apc.com.

7. Appendices

7.1 Technical Sheets

Electrical Characteristics

Selection of Protection Devices

Diagrams illustrate protection device placement for common/separate AC inputs and input/output fuses. Time/current curves for UPS input and output fuses are provided.

Line Current Values

UPS power rating (kVA)Continuous input current at U = 361 V and overload = 1.05 InContinuous input current at overload = 1.25 In (limited to 10 minutes)Continuous input current at overload = 1.5 In (limited to 1 minute)Input/output fuse ratings
10 kVA22 A23 A23 A32 A
15 kVA31 A33 A33 A32 A
20 kVA42 A46 A46 A63 A
30 kVA60 A67 A67 A63 A

Input / Output Characteristics

  • Normal AC source: 250 to 440 V, 45 to 65 Hz.
  • Bypass AC source: 380 V, 400 V, 415 V, 50 Hz - 60 Hz, with tolerances (+10% / -8% for voltage, ±8% for frequency).
  • Load output: 380 V, 400 V, 415 V, with tolerances (+5% / -0% for voltage).
  • UPS with backfeed protection: 335 to 440 V, 45 to 65 Hz.

Power supplied as a function of input voltage: A graph shows power derating at lower input voltages.

Permissible UPS overloads as a function of time: A graph illustrates overload capacity over time.

Derating in 400 V 50 Hz UPS installations with a power factor other than 0.8: Tables show derating values for different power factors and UPS units.

Maximum Allowable Power for Parallel UPS Units

  • Without external bypass cubicle: 1 x Pn per unit.
  • With external bypass cubicle: Up to 2 x Pn for two units, up to 3 x Pn for three or four units. The maximum allowable power for 4 parallel UPS units is limited to 3 x Pn.

Restrictions to Parallel Operation

RestrictionSingle UPSParallel UPS
EMC LevelClass BClass A
ECO ModeYesNo
Frequency converterYesNo
Compatibility with synchronisation moduleYesNo
Placing out of service via Solution-Pac / Wan or AS4i (*)Yes (if UPS technical level >10)No
System shutdown followed by UPS shutdown if autonomy via APC by Schneider Electric communication products (*)Yes (if UPS technical level >10)No
Stop / start time programming via a Personal Solution-Pac supervisor or Solution-Pac / Wan (*)Yes (if UPS technical level >10)No

(*) except in ECO mode or Bypass mode.

7.2 Glossary

  • Backup time: Time that connected loads can operate on battery power.
  • Bypass AC source: Source supplying the bypass line, used for overload, maintenance, or malfunction.
  • ECO mode: Load supplied directly by AC source if within tolerances, reducing power consumption.
  • External synchronisation port: Input used to synchronize the UPS to an external signal.
  • Load: Devices or systems connected to the UPS output.
  • Manual bypass: User-controlled switch to connect loads directly to the AC source, enabling UPS maintenance without interruption.
  • Normal (double conversion) mode: Conventional UPS mode where AC source supplies the UPS, which then supplies loads after electronic double conversion.
  • Normal AC source: Primary source of power for the UPS.
  • Relay contacts: Contacts providing status signals to the user.
  • UPS (ASI): Uninterruptible Power Supply.

7.3 Index

An index is provided for quick reference to specific topics within the manual.

PDF preview unavailable. Download the PDF instead.

DCHN-78GLXH R1 EN Acrobat Distiller 6.0 (Windows)

Related Documents

Preview APC Galaxy 7000 Unitary Specification Guide
This specification guide details the design, manufacture, and testing requirements for the APC Galaxy 7000 Single UPS, three-phase, with capacities ranging from 160 to 500 kVA. It covers operating principles, electrical and mechanical characteristics, protection features, battery management, user interface, communication, maintainability, standards, and services.
Preview APC Smart-UPS RT 5-10 kVA 230V Guide Specification
Detailed guide specification for APC Smart-UPS RT Uninterruptible Power Supply models ranging from 5 kVA to 10 kVA with 230V output. Covers general, references, standards, system description, modes of operation, power stages, display, controls, battery management, accessories, and maintenance.
Preview APC Smart-UPS Operation Manual: SMT700X167 & SMT2200R2X167
This document provides comprehensive operational information for APC Smart-UPS models SMT700X167 and SMT2200R2X167, covering safety instructions, installation, configuration, operation, specifications, battery replacement, troubleshooting, and warranty information for these uninterruptible power supplies.
Preview APC Smart-UPS Ultra Uninterruptible Power Supply User Manual
User manual for APC Smart-UPS Ultra Uninterruptible Power Supply (UPS) models SRTL3KRM1UC, SRTL3KRM1UNC, SRTL2K2RM1UC, and SRTL2K2RM1UNC. Covers safety instructions, specifications, installation, operation, configuration, troubleshooting, and warranty information.
Preview APC Easy UPS On-Line User Manual: SRV1KUXI-IN, SRV2KUXI-IN, SRV3KUXI-IN
This user manual provides detailed information on the installation, operation, safety guidelines, and specifications for the APC Easy UPS On-Line models SRV1KUXI-IN, SRV2KUXI-IN, and SRV3KUXI-IN. Discover how APC by Schneider Electric's UPS solutions protect your equipment from power disturbances.
Preview APC Easy UPS On-Line SRV Series User Manual
User manual for the APC Easy UPS On-Line SRV Series, covering models 1000VA, 2000VA, and 3000VA. Provides safety information, installation, operation, specifications, and troubleshooting.
Preview APC Smart-UPS User Manual: Installation, Operation & Troubleshooting | APC by Schneider Electric
This user manual from APC by Schneider Electric details the installation, operation, configuration, and troubleshooting of APC Smart-UPS models. It provides essential guidance for professional business applications requiring reliable uninterruptible power supply and protection against power disturbances.
Preview APC Smart-UPS 1500VA LCD 120V SMT1500CX413 Specifications | Schneider Electric ENERGY STAR
Detailed technical specifications for the APC Smart-UPS 1500VA LCD 120V (Model: SMT1500CX413) by Schneider Electric. Features include 1000W/1440VA capacity, Line Interactive topology, 8 outlets, and ENERGY STAR certification.