10 C 00 | 2 | Condenser Thermistor Open | Check ohms and verify temperature readings. |
10 C 01 | 2 | Condenser Thermistor Short | Check ohms and verify temperature readings. |
10 C 02 | 2 | Condenser Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 1 00 | 2 | Zone 1 Cabinet Thermistor Open | Check ohms and verify temperature readings. |
10 1 01 | 2 | Zone 1 Cabinet Thermistor Short | Check ohms and verify temperature readings. |
10 1 02 | 2 | Zone 1 Cabinet Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 1 10 | 2 | Zone 1 Evaporator Thermistor Open | Check ohms and verify temperature readings. |
10 1 11 | 2 | Zone 1 Evaporator Thermistor Shorted | Check ohms and verify temperature readings. |
10 1 12 | 2 | Zone 1 Evaporator Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 2 00 | 2 | Zone 2 Cabinet Thermistor Open | Check ohms and verify temperature readings. |
10 2 01 | 2 | Zone 2 Cabinet Thermistor Short | Check ohms and verify temperature readings. |
10 2 02 | 2 | Zone 2 Cabinet Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 2 10 | 2 | Zone 2 Evaporator Thermistor Open | Check ohms and verify temperature readings. |
10 2 11 | 2 | Zone 2 Evaporator Thermistor Shorted | Check ohms and verify temperature readings. |
10 2 12 | 2 | Zone 2 Evaporator Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 3 00 | 2 | Zone 3 Cabinet Thermistor Open | Check ohms and verify temperature readings. |
10 3 01 | 2 | Zone 3 Cabinet Thermistor Short | Check ohms and verify temperature readings. |
10 3 02 | 2 | Zone 3 Cabinet Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 3 10 | 2 | Zone 3 Evaporator Thermistor Open | Check ohms and verify temperature readings. |
10 3 11 | 2 | Zone 3 Evaporator Thermistor Shorted | Check ohms and verify temperature readings. |
10 3 12 | 2 | Zone 3 Evaporator Thermistor Unstable | Check for bad connections and/or damaged wires. |
10 7 00 | 1 | Ambient thermistor on control board open | Replace control board |
15 1 00 | 5 | Zone 1 compressor relay stuck open | Error is thrown if no current detected, could be no load, or open relay. Also could be the inverter or harness. Check all wiring, compressor, inverter and control board connections. Possibly issue with control board or inverter. |
15 1 01 | 5 | Zone 1 compressor relay is stuck closed. Verify and replace control board. 120V to compressor at all times. | Verify and replace control board. 120V to compressor at all times. |
15 2 00 | 5 | Zone 2 compressor relay stuck open | Error is thrown if no current detected, could be no load, or open relay. Also could be the inverter or harness. Check all wiring, compressor, inverter and control board connections. Possibly issue with control board or inverter. |
15 2 01 | 5 | Zone 2 compressor relay is stuck closed. Verify and replace control board. 120V to compressor at all times. | Verify and replace control board. 120V to compressor at all times. |
15 3 00 | 5 | Zone 3 compressor relay stuck open | Error is thrown if no current detected, could be no load, or open relay. Also could be the inverter or harness. Check all wiring, compressor, inverter and control board connections. Possibly issue with control board or inverter. |
15 3 01 | 5 | Zone 3 compressor relay is stuck closed. Verify and replace control board. 120V to compressor at all times. | Verify and replace control board. 120V to compressor at all times. |
15 4 00 | 2 | Defrost relay stuck open | Verify and replace control board. No power to defrost heater |
15 4 01 | 3 | Defrost relay stuck closed | Verify and replace control board. 120V to defrost heater at all times. |
15 C 00 | 1 | AC Condenser Fan Relay Stuck open | Verify and replace control board. No power to condenser |
15 C 01 | 1 | AC Condenser Fan Relay Stuck closed | Verify and replace control board. Power (AC or DC) to compressor at all times. |
15 U 00 | 1 | Water valve no current detected | No current change detected for a activated call for water or dispense. Possible stuck open relay, or failed valve. Check all valves and proper voltage from control output |
15 U 01 | 4 | Water valve current detected | After valid dispense or ice maker fill, current is still detected for a water call. Check for shorted relay. Replace control board. |
20 2 00 | 2 | Defrost Bi-metal stuck open | Verify the bi-metal is open circuit below 40F. Replace if necessary. |
20 2 01 | 2 | Defrost Bi-metal stuck closed | Verify the bi-metal is closed above 70F. Replace if necessary. |
20 2 05 | 1 | Defrost Bi-metal Mis-wire w/ normal temps | Normal defrost temps, but inappropriate response from bi-metal. Check wiring and bi-metal mounting. |
20 2 06 | 2 | Defrost Bi-metal Mis-wire w/ overheat | High temps during defrost, and inappropriate response from bi-metal. Check wiring and bi-metal mounting. |
20 2 50 | 2 | Defrost heater open / Check Ohms | Verify wiring and heater. Check heater ohms. Replace heater if necessary. |
30 8 05 | 1 | Icemaker no water valve in signal | No signal from icemaker for fill. Check wiring and power to ice maker. |
35 1 00 | 2 | Zone 1 Evap Fan Open | Check Control Board and Fan |
35 1 33 | 1 | Zone 1 Fan Speed Set Too Low | Verify fan not shorted - the fan is running faster than it's setting |
35 1 34 | 1 | Zone 1 Fan Speed Set too High | Check fan for obstructions that could cause too not be able to achieve full speed |
35 2 00 | 2 | Zone 2 Evap Fan Open | Check Control Board and Fan |
35 2 33 | 1 | Zone 2 Fan Speed Set Too Low | Verify fan not shorted - the fan is running faster than it's setting |
35 2 34 | 1 | Zone 2 Fan Speed Set too High | Check fan for obstructions that could cause too not be able to achieve full speed |
35 3 00 | 2 | Zone 3 Evap Fan Open | Check Control Board and Fan |
35 3 33 | 1 | Zone 3 Fan Speed Set Too Low | Verify fan not shorted - the fan is running faster than it's setting |
35 3 34 | 1 | Zone 3 Fan Speed Set too High | Check fan for obstructions that could cause too not be able to achieve full speed |
35 A 00 | 1 | Air Filter Fan Open | Check Control Board and Fan |
35 C 00 | 1 | DC Condenser Fan open | Check wiring and power to condenser fan. |
35 C 33 | 1 | DC Condenser Fan Set Too Low | Verify fan not shorted - the fan is running faster than it's setting |
35 C 34 | 1 | DC Condenser Fan Set too High | Check fan for obstructions that could cause too not be able to achieve full speed |
40 1 00 | 1 | Zone 1 Stepper Current Fault | No current detected |
40 1 40 | 3 | Zone 1 Excessive runtime | Verify performance of unit and check for door leaks, door ajar, proper charge in system, and icing of evap. |
40 1 87 | 1 | Zone 1 Stepper Cooling Fault | No cooling Detected |
40 2 00 | 1 | Zone 2 Stepper Current Fault | No current detected |
40 2 40 | 3 | Zone 2 Excessive runtime | Verify performance of unit and check for door leaks, door ajar, proper charge in system, and icing of evap. |
40 2 87 | 1 | Zone 2 Stepper Cooling Fault | No cooling Detected |
40 3 40 | 3 | Zone 3 Excessive runtime | Verify performance of unit and check for door leaks, door ajar, proper charge in system, and icing of evap. |
40 9 40 | 1 | Dispenser Max Time | Dispenser active for maximum fill time. Verify no stuck keys or flooding. Reset after 30 days, allows service time to review if any issues occurred / usage. |
40 b 00 | 1 | Baffle current fault | Baffle Stepper current fault. |
40 b 87 | 1 | Baffle Cooling Fault | Baffle Cooling / position fault |
45 1 00 | 1 | Lights open circuit | Main lights relay open |
45 1 01 | 1 | Lights short circuit | Main lights relay closed |
45 2 00 | 1 | Lights open circuit | Main lights relay open |
45 2 01 | 1 | Lights short circuit | Main lights relay closed |
90 5 80 | 1 | No UIM communications | Check wiring and key performance of User Interface Module. |
90 H 80 | 2 | High voltage micro (CCM) no communication | Communications problems on main board. Replace board. |
90 H 82 | 1 | high voltage micro (CCM) partial comm | Intermittent communications on main board. |
90 H 83 | 2 | HV Micro bad (CCM) comm | Communications problems on main board. Replace board. |
90 H 84 | 2 | HV Micro (CMM) initialization | Initialization fault. Power cycle unit and verify if code remains active. |