SUB-ZERO Wine Storage (400-2) Series Troubleshooting Guide
This document provides troubleshooting procedures for SUB-ZERO Wine Storage appliances, specifically focusing on temperature issues, error codes, and general operational problems. This section of the manual outlines the available troubleshooting resources: This worksheet helps identify the cause of temperature problems in a wine storage unit. Familiarity with Diagnostic Mode and Temperature Log Recall Mode is required. Note: This worksheet does not apply to temperature problems in the refrigerator section of a 427R-2. Steps to follow: Note: Refer to the Temperature Log Index Chart on the last page of section 3 for index/time correlation. Error Codes indicate problems registered by specific components. They appear before temperature readings in Diagnostic Mode. Instructions: Note: A "SERVICE" indicator will appear constant when Diagnostic Mode ends if error codes are logged. To clear them, correct the problem, ensure the unit is ON, then press and hold the bell key for 15 seconds. A short "beep" confirms clearing. MODELS 424-2, 427-2, 427R-2, 430-2 Error Codes indicate problems registered by specific components. They appear before temperature readings in Diagnostic Mode. Instructions: Note: A "SERVICE" indicator will appear constant when Diagnostic Mode ends if error codes are logged. To clear them, correct the problem, ensure the unit is ON, then press and hold the bell key for 15 seconds. A short "beep" confirms clearing. Note: If Error Codes appear with a flashing "SERVICE" annunciator prior to initiating Diagnostic Mode, the unit experienced excessive compressor run condition that may or may not be associated with the Error Codes displayed. MODEL 427R-2 Only Match the unit's complaint or problem description to the table of contents below. The left column lists the problem letter, the center column lists possible causes, and the right column provides tests and corrective actions. Note: If the complaint involves warm or cold temperatures, complete a Temperature Problem Diagnostic Worksheet first. Additional sections include: Sealed System Diagnostic Tables, Wine Storage Membrane Switch Ribbon Cable Test, and Model 427R Refrigerator Membrane Switch Ribbon Cable Test. Possible Cause: Refer to Error Code Troubleshooting Guide. The temperature/pressure table and normal operating pressures are for reference only. Actual correlations may differ due to variations in thermistor location, set-points, refrigeration cycle stage, ambient temperature, and gauge calibration. Note: Before accessing the sealed system, rule out mechanical and electrical components. Use solder-on process valves. The valve assembly (includes high-side filter-drier) must be replaced when servicing the sealed system. The membrane switch is part of the control panel assembly and provides input functions to the electronic control system. Note: To perform continuity checks, disconnect the ribbon cable from the control board. The wires are exposed at the back of the terminal housing. Use an Ohm Meter to check continuity at these exposed points/pins. Pin #1 is at the top of the terminal housing, closest to the arrow. Continuity Checks: Note: If the membrane switch fails any test, replace the control panel assembly. If all tests pass and the unit is still inoperable, replace the control board. Diagram Description: Figure 7-1 illustrates the Control Panel Assembly, showing the membrane switch keys (WINE STORAGE, COLDER, WARMER, LIGHTS ON/OFF, UNIT ON/OFF, BELL ON/OFF, SERVICE) and the ribbon cable. It also indicates Pin #1 at the top of the terminal housing and exposed points/pins on the back side of the housing. If the refrigerator control panel assembly is suspect, continuity tests should be performed at the membrane switch ribbon cable terminal housing. Remove the control panel assembly and place it on a solid surface. Disconnect the ribbon cable from the control panel PC board. How To Identify Pin 1 on Terminal Housing: 700BCI-3 Membrane Switch/Ribbon Cable Test Procedure: Note: If any of the tests show failure, replace the entire control panel assembly. Diagram Description: Figure 7-2 shows the Refrigerator Control Panel Assembly with a cut-away view to illustrate the ribbon cable and terminal housing. It highlights the location of the Membrane Switch in the Control Panel Assembly and the Terminal Housing, noting how to identify Pin 1.Troubleshooting Guides Overview
Temperature Problem Diagnostic Worksheet
Wine Storage Thermistor Location Codes
THERMISTOR LOCATION CODE Upper Evaporator UE Lower Evaporator LE Upper Compartment UP Lower Compartment LO Wine Storage Error Code Troubleshooting Guide
Wine Storage Error Code Table
CODE INDICATION 05 Upper Cabinet Thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 06 Upper Evaporator Thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 07 Lower Cabinet Thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 08 Lower Evaporator Thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 10 Upper Cabinet Warm Temperature alarm 11 Upper Cabinet Cold Temperature alarm 12 Lower Cabinet Warm Temperature alarm 13 Lower Cabinet Cold Temperature alarm 15 Sealed System Fault (evap temperature cannot drop 5° in 5 minutes, 3 consecutive valve activations) Wine Storage Thermistor Location Codes
THERMISTOR LOCATION CODE Upper Evaporator UE Lower Evaporator LE Upper Compartment UP Lower Compartment LO 427R-2 Refrigerator Error Code Troubleshooting Guide
427R-2 Refrigerator Compartment Error Code Table
CODE INDICATION 05 Refrig. cabinet thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 06 Refrig. evaporator thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp's 50 Excessive Refrigerator Compressor Run Refrigerator Thermistor Location Codes
THERMISTOR LOCATION CODE Refrigerator Compartment Γ Refrigerator Evaporator E General Troubleshooting Guide
Wine Storage Troubleshooting Guide Table of Contents
Ltr Problem Description Page # A. "SERVICE" Flashing 7-11 B. Warm Temperature in Both Wine Storage Compartments 7-11 C. Warm Temperature in Only One Wine Storage Compartment 7-12 D. Actual vs. Displayed Temperature Over 10° Different 7-13 E. Actual vs. Displayed Temperature Less Than 10° Different 7-13 F. Excessively Cold Temperatures in Both Wine Storage compartments 7-13 G. Excessively Cold Temperatures in Only One Wine Storage compartment 7-13 H. Lights Stay ON 7-13 I. No Lights 7-13 J. Control Panel Keys Malfunctioning 7-14 K. No LED's 7-14 L. All LED's Lit 7-14 M. Same LED Segments Missing from Both Display Windows 7-14 N. LED Segments Missing from Only One Display Window 7-14 O. Door / Unit Un-level 7-14 427R-2 Refrigerator Section Troubleshooting Guide Table of Contents
Ltr Problem Description Page # P. "EE" Displayed in place of Refrigerator Temperature with "SERVICE" Flashing 7-15 Q. Warm or Normal Temperatures Displayed with "SERVICE” Alone Flashing 7-15 R. Warm or Normal Temperatures Displayed with non-flashing “SERVICE" Displayed 7-15 S. Erratic Temperatures with or without “SERVICE" Flashing 7-15 T. Warm Refrigerator Temperatures, "SERVICE" not displayed or Flashing 7-15 U. Product Temperature 10° or More Colder than Displayed Temperature 7-16 V. 1. "Extremely" Cold Temperatures Displayed (1° to 7° in Refrigerator) 7-16 2. If outside US - "Extremely" Warm Temperatures Displayed (34° to 45° in Refrigerator) 7-16 W. No LCD 7-16 Χ. No Lights 7-17 Y. Lights Stay ON when Drawers Closed - (May be Accompanied by Drawer Ajar Alarm Bell) 7-17 Z. Drawers Not Able to Close Completely 7-17 AA. Drawers Uneven 7-17 General Troubleshooting Guide - Detailed Problems and Solutions
A. "SERVICE" Flashing
B. Warm Temperature in Both Wine Storage Compartments
PROBLEM POSSIBLE CAUSE TEST / ACTION B. WARM TEMPERATURE IN BOTH WINE STORAGE COMPARTMENTS Control Set Too Warm Check/adjust set-points. Adjust set-points COLDER. Unit in Showroom Mode Adjust set-points colder, listen for compressor & condenser fan operation. If they do not run, switch unit OFF, then press and hold upper COLDER & WARMER keys while pressing UNIT ON/OFF key. Unit Recently Energized Allow time for unit to pull down. Unit Recently Stocked with Wine Instruct customer. High Room Ambient Instruct Customer that unit performs best between 60°F / 16°C - 90°F / 32°C. Door Ajar a. Adjust wine rack.
b. See Door Adjustment procedure in section 2 of this manual.
c. Check hinges. Replace if defective.Condenser Air Flow / Fan Fault a. Check/clean condenser.
b. Tighten blade or move obstruction.
c. Check fan motor operation. Check fan motor electrical connections back to compressor. Check for 115V AC from fan motor to compressor. Reconnect or repair wires, or replace motor if defective.Evaporator Fan / Fan Circuit Fault a. Check fan switch electrical connections. Check for 115V AC to and from switch. Reconnect or replace switch if defective.
b. Check for 115V AC at J3 on control board. (NOTE: Unit must be running and not in Showroom Mode) If no power, replace board.No Power from Control Board to Compressor Initiate Manual Valve Activation Mode, check for 115V AC at E2 on the control board. If no power, replace board. Compressor Fault a. Check integrity of compressor electricals. Check continuity back to control board. Check for 115V AC at E2 on control board. Correct wiring problems or replace compressor electricals if defective. If no power between at E2, replace control board.
b. Check AMP draw on compressor. If high by 15% or more, replace compressor.Sealed System Leak or Restriction SEE SEALED SYSTEM DIAGNOSTIC INFORMATION C. Warm Temperature in Only One Wine Storage Compartment
PROBLEM POSSIBLE CAUSE TEST / ACTION C. WARM TEMPERATURE IN ONLY ONE WINE STORAGE COMPARTMENT Control Set Too Warm Check/adjust set-points. Unit Recently Energized Allow time for unit to pull down. Unit Recently Stocked with Wine Instruct customer. High Room Ambient Instruct Customer that unit performs best between 60°F / 16°C - 90°F / 32°C. Door Ajar a. Adjust wine rack.
b. See Door Adjustment procedure in section 2 of this manual.
c. Check hinges. Replace if defective.Thermistor Fault a. Move to correct location.
b. Initiate Diagnostic Mode. If "EE" is displayed in place of evap temp, check electrical connections back to J2 on control board. Repair wiring or connections.
c. Check thermistor ohms = 30,000 - 33,000 at 32°F / 0°C. Replace if defective.Condenser Air Flow / Fan Fault a. Check/clean condenser.
b. Tighten blade or move obstruction.
c. Check fan motor operation. Check fan motor electrical connections back to compressor. Check for 115V AC from fan motor to compressor. Reconnect or repair wires, or replace motor if defective.Evaporator Fan / Fan Circuit Fault a. Check fan blade position. Reposition blade or move obstructions.
b. Check fan switch electrical connections. Check for 115V AC to and from switch. Reconnect or replace switch if defective.
c. Check fan motor electrical connections, and check for 115V AC to motor. Repair connections, replace motor if defective.
d. Check for 115V AC from J3 on control board. (NOTE: Unit must be running and not in Showroom Mode) If no power, replace board.Refrigerant Valve Fault a. Initiate Manual Valve Activation Mode.
1. If valve inoperative: Check electrical connections. Check solenoid resistance for 680 ± 10% ohms. Replace if defective.
2. Toggle through temp readings, if opposite evap temp drops, switch electrical connections.
b. Initiate Manual Valve Activation Mode for one side, then the other, while observing evap temps. If only one side of valve activates, replace valve.D. Actual vs. Displayed Temperature Over 10° Different
PROBLEM POSSIBLE CAUSE TEST / ACTION D. ACTUAL VS. DISPLAYED TEMPERATURE OVER 10° DIFFERENT Wrong Units of Measure Selected, (Fahrenheit - °F vs. Celsius - °C) Initiate Temperature Units Selection Mode to check units of measure (°F or °C) selected. Compartment Thermistor Fault (Misread), or Control Board Fault Check thermistor ohms = 30,000 - 33,000 at 32°F / 0°C. Replace if defective. If thermistor is OK, replace control board. E. Actual vs. Displayed Temperature Less Than 10° Different
PROBLEM POSSIBLE CAUSE TEST / ACTION E. ACTUAL VS. DISPLAYED TEMPERATURE LESS THAN 10° DIFFERENT Control Board DC Offset Out of Adjustment Contact Factory for DC Offset Adjustment Procedure. F. Excessively Cold Temperatures in Both Wine Storage Compartments
PROBLEM POSSIBLE CAUSE TEST / ACTION F. EXCESSIVELY COLD TEMPERATURES IN BOTH WINE STORAGE COMPARTMENTS Room Temperature Below Set-Point Instruct Customer. Control Set Too Cold Check set-points. Adjust set-points WARMER. Door Ajar a. Adjust wine rack.
b. See Door Adjustment procedure in section 2 of this manual.
c. Check hinges. Replace if defective.Compartment Thermistor Fault (Misread), or Control Board Fault Check thermistor ohms = 30,000 - 33,000 at 32°F / 0°C. Replace if defective. If thermistor is OK, replace control board. G. Excessively Cold Temperatures in Only One Wine Storage Compartment
PROBLEM POSSIBLE CAUSE TEST / ACTION G. EXCESSIVELY COLD TEMPERATURES IN ONLY ONE WINE STORAGE COMPARTMENT Room Temperature Below Set-Point Instruct Customer. Control Set Too Cold Check set-point. Adjust set-points WARMER. Door Ajar a. Adjust wine rack.
b. See Door Adjustment procedure in section 2 of this manual.
c. Check hinges. Replace if defective.Refrigerant Valve Stuck Initiate Manual Valve Activation Mode for one side, then the other, while observing evap temps. If only one side of valve activates, replace valve. H. Lights Stay ON
PROBLEM POSSIBLE CAUSE TEST / ACTION H. LIGHTS STAY ON Display Lighting Activated (ON 100%) Press & release LIGHTS ON/OFF key. Fan & Light Switch Wiring Crossed Check wiring at fan & light switch, and at control board. Rewire if incorrect. Light Switch Malfunction Press & release LIGHTS ON/OFF key, then depress light switch. Repeat steps. If no effect, replace switch. I. No Lights
PROBLEM POSSIBLE CAUSE TEST / ACTION I. NO LIGHTS Unit in Sabbath Mode Press & release UNIT ON/OFF key. Light Switch Disconnected or Malfunctioning Check switch operation and electrical connections. Check for 115V AC to and from switch. Reconnect wires or replace switch if defective. Light Strip Burned-out If power from switch, replace light strip. No Power from Control Board Check for 115V AC at E3 of control board. If no power, replace board. J. Control Panel Keys Malfunctioning
PROBLEM POSSIBLE CAUSE TEST / ACTION J. CONTROL PANEL KEYS MALFUNCTIONING Control Panel Ribbon Cable Plugged in Wrong Check control panel ribbon cable at control panel (silver area of terminal away from control board). Plug in correctly if incorrect. Control Panel or Ribbon Cable Defective (OR) No Signal Read at Control Board SEE CONTROL PANEL TEST PROCEDURE AT BACK OF TROUBLESHOOTING GUIDE SECTION. K. No LED's
PROBLEM POSSIBLE CAUSE TEST / ACTION K. NO LED's Unit Switched OFF Press UNIT ON/OFF key. LED Ribbon Cable Plugged in Wrong Check LED ribbon cable. Plug in correctly if incorrect. No Data from Control Board Replace Control Board. L. All LED's Lit
PROBLEM POSSIBLE CAUSE TEST / ACTION L. ALL LED's LIT Bad Data from Control Board Replace Control Board. M. Same LED Segments Missing from Both Display Windows
PROBLEM POSSIBLE CAUSE TEST / ACTION M. SAME LED SEGMENTS MISSING FROM BOTH DISPLAY WINDOWS Bad Data from Control Board Replace Control Board. N. LED Segments Missing from Only One Display Window
PROBLEM POSSIBLE CAUSE TEST / ACTION N. LED SEGMENTS MISSING FROM ONLY ONE DISPLAY WINDOWS Bad LED Board in Control Panel Replace Control Panel Assembly. O. Door / Unit Un-level
PROBLEM POSSIBLE CAUSE TEST / ACTION O. DOOR / UNIT UN-LEVEL SEE SECTION 2 OF THIS MANUAL SEE SECTION 2 OF THIS MANUAL P. "EE" Displayed in place of Refrigerator Temperature with "SERVICE" Flashing
PROBLEM POSSIBLE CAUSE TEST / ACTION P. "EE" Displayed in place of Refrigerator Temperature with "SERVICE" Flashing Refrigerator Compartment Thermistor Disconnected, Shorted, or misread Check refrigerator compartment thermistor electrical connections from thermistor to control board. Reconnect / repair connections. Check resistance of refrigerator compartment thermistor for 30,000 to 33,000 ohms at 32°F. Replace if defective. Excessive Compressor Run Initiate Diagnostic Mode and see Error Code Troubleshooting Guide. Q. Warm or Normal Temperatures Displayed with "SERVICE" Alone Flashing
PROBLEM POSSIBLE CAUSE TEST / ACTION Q. Warm or Normal Temperatures Displayed with "SERVICE" Alone Flashing Evaporator Thermistor Disconnected, Shorted, or misread Check evaporator thermistor electrical connections from thermistor to control board. Reconnect / repair connections. Check resistance of evaporator thermistor for 30,000 to 33,000 ohms at 32°F. Replace if defective. R. Warm or Normal Temperatures Displayed with non-flashing "SERVICE" Displayed
PROBLEM POSSIBLE CAUSE TEST / ACTION R. Warm or Normal Temperatures Displayed with non-flashing "SERVICE" Displayed Error Codes Observed in Diagnostic Mode, but not Cleared from Memory Enter diagnostic mode to observe error codes. See Error Code Troubleshooting Guide. Verify unit was repaired for error codes displayed. Press and hold alarm key for 15 seconds to clear error codes. S. Erratic Temperatures with or without "SERVICE" Flashing
PROBLEM POSSIBLE CAUSE TEST / ACTION S. Erratic Temperatures with or without "SERVICE" Flashing Control Board Configured for Wrong Model Initiate Manual Model Configuration Mode and reconfigure to correct model. T. Warm Refrigerator Temperatures, "SERVICE" not displayed or Flashing
PROBLEM POSSIBLE CAUSE TEST / ACTION T. Warm Refrigerator Temperatures, "SERVICE" not displayed or Flashing No Power to Unit Check power to unit, plug unit in or switch supply circuit breaker ON. Unit Switched OFF Check for "OFF" displayed at LCD. If off, press UNIT ON/OFF key. Unit in Show Room Mode Press UNIT ON/OFF key to OFF, then press and hold WARMER & COLDER keys, and press UNIT ON/OFF key. Control Set Too High Check set-point. If high, adjust. Warm Food Load Check contents of freezer for warm food load. Instruct customer. High Room Ambient Instruct customer unit performs best between 60°F(16°C) and 90°F(32°C). Drawer Ajar a. Move obstruction.
b. Trip drawer closer forward.Faulty Light Switch Check operation of light switches, lights off when switch is depressed. Replace switch if defective. (NOTE: Two light switches in unit) Refrigerator Compartment Fan Fault a. Move obstruction or reposition blade.
b. Check electrical connections & continuity from control board to motor. Reconnect / repair, use conduits.
c. Check for 115V AC from control board to fan motor. Replace control board if defective, or Replace motor if defective.Compartment Thermistor Disconnected, Shorted, or misread Check refrigerator evaporator thermistor electrical connections from thermistor to control board. Reconnect / repair connec- tions. Check resistance of refrigerator evaporator thermistor for 30,000 to 33,000 ohms at 32°F. Replace if defective. U. Product Temperature 10° or More Colder than Displayed Temperature
PROBLEM POSSIBLE CAUSE TEST / ACTION U. Product Temperature 10° or More Colder than Displayed Temperature Compartment Thermistor Misread Check resistance of compartment thermistor for 30,000 to 33,000 ohms at 32°F. Replace if defective. V. "Extremely" Cold Temperatures Displayed
PROBLEM POSSIBLE CAUSE TEST / ACTION V. 1. "Extremely" Cold Temperatures Displayed (1° to 7° in Refrigerator) Control Set to Display Celsius 1. Change temperature units of measure to Fahrenheit. Switch unit OFF, then ON, then press & hold Bell key and UNIT ON/OFF key for 10 seconds. 2. If outside US - Control Set to Display Fahrenheit 2. If Outside US - Change temperature units of measure to Celsius. Switch unit OFF, then ON, then press & hold Bell key and UNIT ON/OFF key for 10 seconds. W. No LCD
PROBLEM POSSIBLE CAUSE TEST / ACTION W. No LCD Unit in Sabbath Mode Exit Sabbath Mode, press UNIT ON/OFF key. Display Wire Harness Disconnected or Faulty Check display wire harness and connections, including wires behind refrigerator duct cover. Reconnect, repair, replace bad wiring. Control Panel Assembly Defective (OR) No Signal Read at Control Board See Membrane Switch/Ribbon Cable Test Procedures. If membrane switch fails any test, replace entire control panel assembly. If switch passes all tests, replace control board. X. No Lights
PROBLEM POSSIBLE CAUSE TEST / ACTION X. No Lights No power to unit Check / correct power supply to unit. Unit switched OFF Switch unit ON, press UNIT ON/OFF key. Unit in Sabbath Mode Exit Sabbath Mode, press UNIT ON/OFF key. Defective or loose light bulb(s) Install a known good light bulb. Light Switch Disconnected or Defective Check wire connections at light switch. Reconnect/repair. Check for 115V AC to and from light switch. Replace switch if defective. Lighting System Wiring Disconnected or Defective Check continuity from light sockets to switch. Reconnect/repair or replace defective components. No Power From Control Board Check for 115V AC from control board. Replace board if defective. (NOTE: See Unit in Sabbath Mode above.) Y. Lights Stay ON when Drawers Closed
PROBLEM POSSIBLE CAUSE TEST / ACTION Y. Lights Stay ON when Drawers Closed - (May be Accompanied by /Drawer Ajar Alarm Bell) Door or Drawer Ajar a. Food product obstruction
b. Drawer closer tripped backwardsFaulty Light Switch Check operation of light switches, lights off when switch is depressed. Replace switch if defective. (NOTE: Two light switches in unit) Z. Drawers Not Able to Close Completely
PROBLEM POSSIBLE CAUSE TEST / ACTION Z. Drawers Not Able to Close Completely Food Product Obstruction Move obstruction. Drawer Closer Tripped Backwards Trip drawer closer forward. AA. Drawers Uneven
PROBLEM POSSIBLE CAUSE TEST / ACTION AA. Drawers Uneven Improper Drawer Panel Installation The drawers are non-adjustable. Instead, the drawer panels must be adjusted if there is an alignment problem. Refer to the Installation Manual and/or installation video for panel installation and adjustment. Unit Not Level Check levelness of unit. If un-level, turn front leveling legs counterclockwise to raise front or clockwise to lower it. Rear levelers are adjusted from front of base by turning adjusting screw clockwise to raise rear or counterclockwise to lower it. Refer to the Installation Manual and/or installation video for complete installation and leveling instructions. Sealed System Diagnostic Information
Temperature / Low-Side Pressure Correlation
Temperature Pressure -30°F / -34°C 10" Vac / -.69 Bar -25°F / -32°C 7" Vac / -.48 Bar -20°F / -29°C 4" Vac / -.28 Bar -15°F / -26°C 0" Vac / 0 Bar -10°F / -23°C 2 Psi/.14 Bar -5°F / -21°C 4 Psi/.28 Bar 0°F / -18°C 7 Psi/.48 Bar 5°F / -15°C 9 Psi /.62 Bar 10°F / -12°C 12 Psi/.83 Bar 15°F / -9°C 15 Psi/ 1.03 Bar 20°F / -7°C 18 Psi / 1.24 Bar 25°F / -4°C 22 Psi / 1.51 Bar 30°F / -1°C 26 Psi / 1.79 Bar 35°F / 2°C 30 Psi / 2.07 Bar 40°F / 4°C 35 Psi / 2.41 Bar 45°F / 7°C 40 Psi / 2.76 Bar 50°F / 10°C 45 Psi / 3.10 Bar 55°F / 13°C 51 Psi / 3.52 Bar 60°F / 16°C 57 Psi / 3.93 Bar 65°F / 18°C 64 Psi / 4.41 Bar 70°F / 21°C 71 Psi / 4.90 Bar 75°F / 24°C 78 Psi / 5.38 Bar Normal Operating Pressures (70°F/21°C Ambient / 38°F/ 3°C Set-Point)
Model Normal Low Side Pressures Normal High Side Pressures 424-2 0-12 PSI to 30-45 PSI 75 psi to 120 psi 427-2 0-12 PSI to 30-45 PSI 75 psi to 120 psi 427R-2 (Wine) 0-12 PSI to 30-45 PSI 75 psi to 120 psi 427R-2 (Ref) 0-12 PSI to 30-45 PSI 75 psi to 120 psi 430-2 0-12 PSI to 30-45 PSI 75 psi to 120 psi Pressure Indications
If low side pressure is & high side pressure is possible problem is NORMAL NORMAL MECHANICAL (see General Troubleshooting Guide) LOW LOW LEAK LOW HIGH RESTRICTION HIGH LOW INEFFICIENT COMPRESSOR HIGH HIGH OVER CHARGE Membrane Switch / Ribbon Cable Test Procedures
Model 427R-2 Refrigerator Membrane Switch / Ribbon Cable Test Procedure