APLISENS Chemical Flanged Seals with Flush Diaphragm S-Ch
Diaphragm Seal Dimensions
Acc. to DIN EN1092-1
Material of wetted parts | Version | Diaphragm diameter Dm | Contact face dia. Dp | Dia. of bolt circle Do | External diameter Dz | Thickness B | Thickness h | Diameter of holes d | Number of holes |
---|---|---|---|---|---|---|---|---|---|
Hastelloy, Nickel, Monel | DN50PN40 | 59 | 98 | 125 | 165 | 18 | 7 | 18 | 4 |
DN80PN40 | 89 | 132 | 160 | 200 | 22 | 7 | 18 | 8 | |
Titanium | DN50PN40 | 59 | 98 | 125 | 165 | 24 | 6 | 18 | 4 |
DN80PN40 | 89 | 138 | 160 | 200 | 22 | 6 | 18 | 8 | |
Tantalum | DN50PN40 | 59 | 102 | 125 | 165 | 18 | 3 | 18 | 4 |
DN80PN40 | 89 | 138 | 160 | 200 | 22 | 3 | 18 | 8 | |
Tantalum/Teflon | DN50PN16 | 59 | 102 | 125 | 165 | 18 | 8 | 18 | 4 |
DN80PN16 | 89 | 138 | 160 | 200 | 22 | 8 | 18 | 8 | |
Teflon | DN25PN16 | 35 | 68 | 85 | 115 | 18 | 2 | 14 | 4 |
DN50PN40 | 59 | 102 | 125 | 165 | 18 | 7 | 18 | 4 | |
DN80PN40 | 89 | 138 | 160 | 200 | 22 | 7 | 18 | 8 |
Acc. to ANSI ASME 16.5
Material of wetted parts | Version | Diaphragm diameter Dm | Contact face dia. Dp | Dia. of bolt circle Do | External diameter Dz | Thickness B | Thickness h | Diameter of holes d | Number of holes |
---|---|---|---|---|---|---|---|---|---|
Hastelloy, Nickel, Monel | 2" ANSI 150 | 59 | 92 | 120,5 | 150 | 18 | 7 | 20 | 4 |
3" ANSI 150 | 89 | 123 | 152,5 | 190 | 22 | 7 | 20 | 4 | |
Titanium | 2" ANSI 150 | 59 | 92 | 120,5 | 150 | 18 | 2 | 20 | 4 |
3" ANSI 150 | 89 | 127 | 152,5 | 190 | 22 | 2 | 20 | 4 | |
Tantalum | 2" ANSI 150 | 59 | 92 | 120,5 | 150 | 18 | 8 | 20 | 4 |
3" ANSI 150 | 89 | 127 | 152,5 | 190 | 22 | 8 | 20 | 4 | |
Tantalum/Teflon | 2" ANSI 150 | 59 | 92 | 120,5 | 150 | 18 | 7 | 20 | 4 |
3" ANSI 150 | 89 | 127 | 152,5 | 190 | 22 | 7 | 20 | 4 | |
Teflon | 1" ANSI 150 | 35 | 53 | 79,5 | 110 | 16 | 2 | 14 | 4 |
2" ANSI 150 | 59 | 92 | 120,5 | 150 | 18 | 7 | 20 | 4 | |
3" ANSI 150 | 89 | 123 | 152,5 | 190 | 22 | 7 | 20 | 4 |
Application
The diaphragm seal is a pressure-transmitting, diaphragm-type device. The pressure signal is transferred to the cooperating pressure measuring device (pressure transmitter, pressure gauge) through manometric liquid filling the space between the separating diaphragm of the seal and the pressure measuring device. The diaphragm seal function is to isolate the pressure measuring device from damaging impacts caused by either medium or installation:
- high corrosiveness;
- low or high temperature, increased viscosity, impurities;
- vibrations of the installation (remote diaphragm seal).
Recommended minimum measuring range
Depending on the type of the set: pressure measuring device - diaphragm seal
Pressure measuring device | Diaphragm seal type | Diaphragm seal version | ||
---|---|---|---|---|
DN25/1"ANSI | DN50/2"ANSI | DN80/3"ANSI | ||
Transmitter | direct | 1 bar | 0,4 bar | 0,1 bar |
remote | X | 1 bar | 0,4 bar | |
Gauge Ø100 | direct | 6 bar | 1 bar | 1 bar |
remote | X | 2,5 bar | 2,5 bar |
Available chemical-resistant materials
Diaphragm material | Contact face material | Over pressure limit |
---|---|---|
Monel | Monel | 40 bar |
Hastelloy | Hastelloy | 40 bar |
Nickel | Nickel | 40 bar |
Tantalum | Tantalum | 40 bar |
Tantalum | Teflon | 16 bar |
Titanium | Titanium | 40 bar |
Teflon | Teflon | 40 bar (10 bar for DN25 and 1") |
Gold | Gold | 40 bar |
Teflon/Teflon diaphragm seals not applicable with Exia transmitters
Zero error from ambient temperature change
Absolute zero error per 10°C for the diaphragm seal
Diaphragm seal type | DN25/1"ANSI | DN50/2"ANSI | DN80/3"ANSI |
---|---|---|---|
direct | 20 mbar | 5 mbar | 2 mbar |
remote (2 m capillary) | X | 10 mbar | 4 mbar |
An additional zero error, resulting from temperature fluctuations in a medium, depends on the temperature gradient in the oil-based diaphragm sealing system. The error value is, in any case, significantly smaller than the error value shown in the table.
Medium temperature range
- -30...180°C for remote diaphragm seal
- special versions up to 250°C
- -30...150°C for diaphragm seal
Special versions
- Filling liquid - FLUOROLUBE
- Direct diaphragm seal for a medium temp. over 150°C
- Gold plated wetted parts material - after consulting with Aplisens.
Important:
- standard outlet capillary from flange: direct mounted diaphragm seal - axial
- remote mounted diaphragm seal - axial
- other configuration available on request
Ordering procedure
direct diaphragm seal: pressure measuring device / S-Ch — DN..... / spec. ver. - description
remote diaphragm seal: pressure measuring device / S-ChK — DN..... / K = ..... m / spec. ver. - description
Transmitter or gauge - see the code in the appropriate catalogue sheet | Material of diaphragm and contact face | Diaphragm seal version | Capillary length | Mounting of capillary: AX - axial (standard version) RD - radial (on request) |
---|---|---|---|---|
When ordering a diaphragm seal please state the type of medium and the expected ranges of concentration and temperature.
Related Documents
![]() |
APLISENS Diaphragm Seals User Manual This user manual from APLISENS provides comprehensive information on diaphragm seals, covering identification, technical specifications, installation guidelines, specific product data, and maintenance procedures for various models used with pressure and differential pressure transmitters. |
![]() |
APLISENS MS-100 Pressure Gauge with Diaphragm Seal - Technical Specifications Comprehensive technical data, features, and ordering information for the APLISENS MS-100 pressure gauge, designed for reliable industrial pressure measurement with diaphragm seals. |
![]() |
APLISENS S.A. - Śródroczne Skrócone Jednostkowe Sprawozdanie Finansowe (1.01.2025 - 30.06.2025) Niniejsze śródroczne skrócone jednostkowe sprawozdanie finansowe APLISENS S.A. przedstawia wyniki finansowe za okres od 1 stycznia do 30 czerwca 2025 roku, sporządzone zgodnie z Międzynarodowymi Standardami Sprawozdawczości Finansowej. |
![]() |
APLISENS PEM-1000 Electromagnetic Flowmeter Pulse Output Interfacing Guide Comprehensive user's manual for APLISENS PEM-1000 electromagnetic flowmeter, covering pulse output interfacing, electrical connections, configuration settings, and troubleshooting with detailed diagrams and specifications. |
![]() |
APLISENS APC-2000ALW Smart Pressure Transmitter Datasheet Detailed technical specifications and features of the APLISENS APC-2000ALW Smart Pressure Transmitter, including HART protocol compatibility, safety certifications, and various measuring ranges. |
![]() |
APLISENS PCE-28, PRE-28, PCE-28P User's Manual Comprehensive user's manual for APLISENS PCE-28 pressure transmitters, PRE-28 differential pressure transmitters, and PCE-28P hydrostatic level probes, covering installation, operation, safety, and Ex versions. |