Models:
Refrigerant: R32
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in personal injury or death.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in personal injury or death.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury or damage to the appliance. It may also be used to alert against unsafe practices.
This appliance must be installed in accordance with:
This appliance must be installed, maintained, and removed ONLY by an Authorised Person.
For continued safety, installation and maintenance must follow the manufacturer's instructions.
This appliance uses R32 refrigerant.
Warning: This appliance is heavy; use two people or a mechanical lifting device. Improper lifting may result in serious injury.
Warning: Take care when opening or unpacking this appliance. Failure to do so may result in serious injury or product failure.
DO NOT modify the electrical wiring. If control power wiring is damaged, it must be replaced by an authorised person to prevent electric shock, fire, serious injury, or product failure.
DO NOT install the air conditioner on an unstable or non-level surface, or where there is a danger of it falling. This may result in death, serious injury, or product failure.
DO NOT install the outdoor unit where noise may cause nuisance.
DO NOT install the outdoor unit where it will be exposed to sea wind (salt spray), as this will reduce durability.
IMPORTANT:
Immediately report any damage or discrepancies to the Supplier. Inspect the exterior for evidence of rough handling during shipment. Ensure the appliance is labelled correctly for the gas and electrical supply.
For safety and warranty purposes, appliances that may be damaged or incorrect MUST NOT be installed or operated. Installation of damaged or incorrect appliances may contravene local government regulations. Rinnai disclaims any liability or responsibility for the installation or operation of damaged or incorrect appliances.
Indoor Unit Components:
Outdoor Unit Components:
Diagram shows numbered components of the indoor and outdoor units.
Model | HSNCJ25B | HSNCJ35B | HSNCJ50B | HSNCJ70B | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
A | B | C | A | B | C | A | B | C | A | B | C | |
Weight Indoor (kg) | 9.5 | 12.0 | 13.0 | 14.0 | ||||||||
Outdoor (kg) | 28.0 | 28.0 | 45.0 | 47.0 | ||||||||
Indoor Dimensions (mm) | 881 | 194 | 294 | 940 | 224 | 316 | 997 | 227 | 316 | 1132 | 232 | 330 |
Outdoor Dimensions (mm) | 800 | 50 | 545 | 800 | 50 | 545 | 900 | 50 | 700 | 900 | 50 | 700 |
Diagrams show dimensions A, B, C for indoor units and D, E, F, G, H, I for outdoor units, with corresponding measurements.
Diagram illustrates minimum clearance distances around the indoor unit: 150mm (top, sides), 1000mm (front), 150mm (bottom).
Diagram illustrates minimum clearance distances around the outdoor unit: 100mm (sides), 300mm (rear), 600mm (front), 1000mm (top).
Models | Pipe Size Gas (mm) | Pipe Size Gas (inch) | Pipe Size Liquid (mm) | Pipe Size Liquid (inch) | Chargeless Length (m) | Minimum Length - X (m) | Maximum Length - X (m) | Maximum Height - Y (m) | Additional Refrigerant (g/m) |
---|---|---|---|---|---|---|---|---|---|
HSNCJ25B | Ø9.52 | 3/8 | Ø6.35 | 1/4 | 10 | 2 | 20 | 12 | 15 |
HSNCJ35B | Ø12.7 | 1/2 | Ø6.35 | 1/4 | 10 | 2 | 20 | 12 | 15 |
HSNCJ50B | Ø12.7 | 1/2 | Ø6.35 | 1/4 | 10 | 2 | 30 | 20 | 15 |
HSNCJ70B | Ø15.88 | 5/8 | Ø6.35 | 1/4 | 10 | 2 | 30 | 20 | 15 |
The outdoor unit is supplied already charged for interconnecting pipe lengths of 2 metres up to 10 metres.
IMPORTANT:
Removal of refrigerant is necessary if pipe length is less than 2 metres. Additional refrigerant will be required for pipe lengths in excess of 10 metres. Removal or addition of refrigerant must be by best practice.
Diagrams show the relationship between the indoor and outdoor units, indicating pipe length (X) and height difference (Y).
The wall or structure must be capable of supporting the weight of the appliance and associated pipe-work.
Fix the mounting plate to the wall, ensuring it is level and firmly mounted with appropriate fixings.
CAUTION: DO NOT install the unit in a place where electrical wiring or conduits are located.
Diagram shows the wall mounting plate with dimensions A, B, C, D, E, and Ø70mm hole for wall penetration. A table provides specific dimensions for each model.
Model | HINCJ25B | HINCJ35B | HINCJ50B | HINCJ70B | ||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | A | B | C | D | E | A | B | C | D | E | A | B | C | D | E | |
Wall Mounting Plate Positioning Dimensions (mm) | 294 | 881 | 228 | 84 | 43 | 316 | 940 | 218 | 54 | 41 | 316 | 997 | 217 | 43 | 38 | 330 | 1132 | 236 | 56 | 39 |
Drill a Ø70mm wall penetration through the wall with a 2° to 4° fall to the outside wall.
Diagram shows a cross-section of a wall with a hole drilled at a 2° to 4° angle, labelled "INSIDE" and "OUTSIDE".
Diagram shows the drain pipe connection to the indoor unit and the application of insulation tape.
WARNING: Must be installed, maintained, and removed by authorised persons in accordance with AS/NZS 3000 and all other relevant local regulations and municipal building codes including OH&S requirements. Ensure electric wiring is installed properly. Improper installation may cause malfunction, fire, or electric shock.
The unit must be earthed following local electrical codes.
Diagram shows the indoor unit's internal wiring access, cable clip, and terminal connections.
CAUTION: Ensure that there is no leakage from the drain pipe connection and that the drain pipe has a continuous fall to the outside. Ensure that all wall penetrations are sufficiently weatherproofed.
Diagram illustrates the process of mounting the indoor unit onto the wall bracket, showing the hooks engaging.
WARNING: Must be installed, maintained, and removed by authorised persons in accordance with AS/NZS 3000 and to all other relevant local regulations and municipal building codes including OH&S requirements. Ensure electric wiring is installed properly. Improper installation may cause malfunction, fire, or electric shock.
The unit must be earthed following local electrical codes.
Diagram shows the outdoor unit's wiring cover, cable clip, and terminal connections for mains power and indoor unit communication.
This appliance is supplied with a DRED interface, providing two connection methods: a four-wire terminal connection or an RJ45 socket.
WARNING: Must be installed, maintained, and removed by authorised persons in accordance with AS/NZS 3000 and to all other relevant local regulations and municipal building codes including OH&S requirements. Ensure electric wiring is installed properly. Improper installation may cause malfunction, fire, or electric shock.
Diagram shows the DRED interface connections, including terminal blocks (L, N, S) and an RJ45 socket, for connecting to power and the indoor unit.
IMPORTANT:
The main cause for refrigerant leakage is due to defects with the flaring work.
The installer must ensure that all piping used complies with both:
All pipework and fittings should be thoroughly examined for cleanliness and suitability for the system and refrigerant prior to assembling.
All unsealed tubing must be thoroughly inspected and, if necessary, cleaned before assembly to remove any copper residue and/or scale particles such as dirt or metal.
Metal filings must not be left in pipework after cutting as they can cause damage to the compressor (i.e. shaft seals, bearings, etc.).
Prior to assembly, refrigeration pipes must be clean and burr-free. They must not be crushed or kinked.
For flare connections, a suitable lubricant must be used between the back of the flare and the nut to avoid tearing the flare when tightening the nut.
CAUTION: To prevent heat loss and wet floors due to dripping of condensation, both pipes must be properly insulated.
Pipe Dimensions (Ø) Metric | Pipe Dimensions (Ø) Imperial | Torque Wrench Setting |
---|---|---|
Ø6.35 mm | Ø 1/4" | 18 Nm |
Ø9.52 mm | Ø 3/8" | 42 Nm |
Ø12.7 mm | Ø 1/2" | 55 Nm |
Ø15.88 mm | Ø 5/8" | 75 Nm |
Diagram shows the connection of vapour and liquid pipes to the indoor and outdoor units, illustrating the use of a wrench and torque wrench on the flare nut.
CAUTION: Ensure the joint nut is tightened firmly to avoid leakage. Ensure that both the connections and the refrigerant pipes are wrapped with insulation material.
WARNING: DO NOT mix any substance other than the specified refrigerant (R32) into the refrigerant system. When refrigerant gas leaks occur, ventilate the room immediately. R32, as well as other refrigerants, should always be recovered and never be released directly into the environment. Use a vacuum pump for R32 exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
CAUTION: It is necessary to purge air and check for gas leakage after piping work is completed. If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant. Use a hex socket (3/16") to operate the service valves. All refrigerant pipe joints to be tightened with a torque wrench at the specified torque.
IMPORTANT: Both the vapour and liquid valve caps MUST BE on tight.
The system is now ready to run.
Diagram illustrates the evacuation process using a vacuum pump, manifold gauge set, and hoses connected to the unit's service valves.
Additional refrigerant for longer piping runs can be added either at the time of evacuation of the new installation or whilst the unit is operating. Refer to "Pipe Length & Elevation Limits" on page 8.
CAUTION: It is very easy to overcharge; take caution in charging refrigerant liquid and keep your eye on the scales to avoid overcharging the unit.
Take care not to discharge refrigerant into the atmosphere during installation, re-installation, repair or service.
IMPORTANT: The checklist is ONLY to be completed by an Authorised Person.
Check Item | What can happen if not checked |
---|---|
Is the indoor unit installed securely? | Falling, vibration, noise |
Has an inspection been made to check for gas leakage? | No cooling or heating |
Has all thermal insulation been completed (vapour pipes, liquid pipes, indoor portions of the drain hose extension)? | Condensation |
Is the drainage secure? | Water leakage |
Are the electric wires installed correctly? | No cooling or heating, may cause electrical shock or electrical fire. |
Is the wiring in accordance within the specifications? | Operation failure, electrical fire |
Are all inlets / outlets of the indoor and outdoor units free of any obstructions? | No cooling or heating |
Are the stop valves open? | No cooling or heating |
Are the pipes designed for use with R32? | Pipe or pipe connection leakage |
Has a leak test been carried out for the pipe connections? | Pipe connection leakage |
Has air purging been carried out? | No cooling or heating |
Has the appliance been tested for correct operation? | No cooling or heating |
Is the end user fully aware of the operating procedure? | Incorrect operation |
If you have answered no to any of the above, you must check and correct before appliance hand-over to customer.
Rinnai Australia Pty Ltd
ABN 74 005 138 769 | AU45204
100 Atlantic Drive, Keysborough, Victoria 3173
P.O. Box 460, Braeside, Victoria 3195
Tel: (03) 9271 6625 | Fax: (03) 9271 6622
National Help Line Tel: 1300 555 545* Fax: 1300 555 655
Monday to Friday, 8:00 am to 5:00 pm EST.
*Cost of a local call higher from mobile or public phones.
For further information visit www.rinnai.com.au or email enquiry@rinnai.com.au
Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance. If your appliance requires service, please call our National Help Line.
Rinnai recommends that this appliance be serviced every 3 years.
With our policy of continuous improvement, we reserve the right to change, or discontinue at any time, specifications or designs without notice.
File Info : application/pdf, 16 Pages, 2.30MB
DocumentDocument![]() |
Rinnai PB Series Split Type Wall Mounted Air Conditioner Installation Manual Comprehensive installation guide for Rinnai PB Series split type wall-mounted air conditioners, covering indoor and outdoor unit installation, refrigerant piping, air evacuation, electrical connections, and testing. Includes model specifications and safety warnings. |
![]() |
Rinnai J Series Split Type Air Conditioner Installation Manual This Rinnai J Series Split Type Wall Mounted Air Conditioner Installation Manual provides essential guidance for installing models HSNRJ25B through HSNRJ80B. It covers critical safety procedures, electrical connections, refrigerant handling (R32), and best practices for optimal performance, ensuring compliance with Australian and New Zealand standards. |
![]() |
Rinnai CJ1 Series Split Type Wall Mounted Air Conditioner Operation Manual This comprehensive operation manual provides detailed instructions for the Rinnai CJ1 Series Split Type Wall Mounted Air Conditioner. Learn about its features, modes, controls, safety precautions, installation guidelines, maintenance, and warranty information for optimal performance and user satisfaction. |
![]() |
Rinnai T Series Wi-Fi Air Conditioner Operation Manual - Setup & Control Comprehensive guide to operating your Rinnai T Series Split Type Wall Mounted Air Conditioner via Wi-Fi using the AC Freedom App. Learn setup, controls, modes, timers, and voice assistant integration. |
![]() |
Rinnai CJ1 Series Split Type Air Conditioner Installation Manual Comprehensive installation manual for the Rinnai CJ1 Series Split Type Wall Mounted Air Conditioner. Covers safety, installation procedures, electrical connections, refrigerant handling, and troubleshooting for models HSNCJ26B1, HSNCJ35B1, HSNCJ52B1, and HSNCJ70B1. |
![]() |
Rinnai T Series Split Type Wall Mounted Air Conditioner Installation Manual Comprehensive installation guide for Rinnai T Series split type wall-mounted air conditioners, covering safety, components, location, electrical connections, refrigerant piping, and final checks. Features R32 refrigerant. |
![]() |
Rinnai Pro Series High Wall Split Heat Pump / Air Conditioner Installation Guide Comprehensive installation guide for Rinnai Pro Series High Wall Split Heat Pump and Air Conditioner models. Covers safety, positioning, installation steps, refrigerant handling, evacuation, electrical and gas leak checks, test run, and error code summaries. |
![]() |
Rinnai Multi Split Type Air Conditioner Installation Manual Comprehensive installation manual for Rinnai Multi Split Type Air Conditioners, covering outdoor and indoor unit installation, refrigerant piping, electrical connections, testing, and commissioning. Includes detailed specifications and safety precautions. |