Instruction Manual for EMERSON models including: Supervisory and E2E Controller Weather ADF and DSC Weather Extension Module, Weather Extension Module

4186R1 WeatherADF Supervisor and E2

Supervisory and E2E Controller Weather ADF and DSC ...

2022-08-27 — Installing the Weather Extension Module - ADF (Supervisory Controllers). An ADF is an Application Description File. Contact your Sales representative or ...


File Info : application/pdf, 9 Pages, 1.13MB

PDF preview unavailable. Download the PDF instead.

026-4186-supervisory-e2e-controller-weather-adf-dsc-installation-en-8496892
Supervisory and E2E Controller Weather ADF and DSC Installation Instructions
Instruction Guide

Overview
This document explains how to install the Weather Extension Module onto Supervisory and E2E controllers.
Weather ADF and DSC Versions

ADF and DSC Names 531-0300.adf 527-0901.dsc
Connect+ API Deployment

Controller Type E3/Site Supervisor E2E

Supported Versions 2.16F02 and later 4.01 and later

Document Part # 026-4186 Rev 1

Page 1 of 9

©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.

Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Installing the Weather Extension Module - ADF (Supervisory Controllers)
An ADF is an Application Description File. Contact your Sales representative or Customer Service to obtain the Weather ADF. This can be uploaded on a Supervisory controller using the File Management screen. A license key is NOT required to activate the single instance application after the ADF has been uploaded. Email: Solutions.CustomerService@Emerson.com
Prerequisites
You will need the following:
1. The Weather Extension Module built for your version of Supervisory controller firmware.

Installation Steps Step 1 ­ Obtain ADF and License
Obtain the correct ADF for the Supervisory controller firmware version on the target unit.

Step 2 ­ Installing ADF

Install the Weather Extension Module ADF onto the Supervisory controller using the Install ADF File button and upload the features of the Supervisory controller.

1. First, go to the gear icon

> Configure System> File Management & Licensing> Install ADF File button.

2. Click Install ADF File then click Select.

Step 3 ­ Browsing for the ADF on PC 1. Select the ADF on your PC. (For this example, Indigo_Ice.adf is used).
Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 2 of 9

2. Click Install then confirm OK.
Step 4 ­ Loading the ADF
1. Once the ADF loads, click Reset then OK to reset system.

Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 3 of 9

Installing the Weather Extension Module - DSC (E2E Controllers)
A DSC is an Description File. Contact your Sales representative or Customer Service to obtain the Weather DSC. The DSC can be uploaded on an E2E controller using UltraSite. A license key IS required to activate the single instance application after the DSC has been uploaded. Email: Solutions.CustomerService@Emerson.com or contact Emerson Customer Service.
Prerequisites
You will need the following: 1. The Weather Extension Module built for your version of Supervisory controller firmware.
Installation Steps Step 1 ­ Obtain DSC and License
Obtain the correct DSC for the Supervisory controller firmware version on the target unit. STEP 2: Upload the Description (.dsc) File (xxx-xxxx) to the E2E Controller
1. Select the controller in UltraSite. 2. Right-click the controller and select Upload Description File:

Figure 1 - Upload .dsc File
Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 4 of 9

3. Select Browse to go to location where the description (.dsc) file was saved:
Figure 2 - Locate .dsc File 4. Select the desired description (.dsc) file and click Open:

Figure 3 - Select .dsc File and Import
Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 5 of 9

5. Right-click the controller. Under Service Actions, select Reset Unit to reboot. The controller must be rebooted to see the description (.dsc) file: Figure 4 - Reboot the Controller

Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 6 of 9

6. After the controller reboots, in the navigation tree, go to Device Setup>Network Board Setup to add the device:

Figure 5 - Network/Board Setup 7. Select Add Ctr/IO to add a device:

Figure 6 - Adding the Device
Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 7 of 9

8. Select the ECT Devices tab and select the desired device. Enter the number of devices and set up the Com port address and commission the devices as usual:

Figure 7 - ECT Tab - Add Number of Devices

License Key Installation When licensed products are purchased from Emerson, the customer provides Emerson with (1) the types of features to be purchased, (2) the quantity of features to be purchased, and (3) the unique MAC address of each controller in which the features will be enabled. Emerson then returns the customer a report that contains a set of 16-character license keys and if necessary one or more description files that must be loaded into the E2 to allow the selected devices to communicate with the E2.

Installation Steps

License keys must be entered from the front panel of the E2, or by using UltraSite32 or Connect+ in Terminal Mode.

1. Press  and enter your username and password. You
must be level 4 or above to enter a license key.

2. After logging in, press + and check that the MAC
Address field on the TCP/IP screen (Figure 1) matches the MAC address in the report given to you from Emerson. The license key will not work unless the MAC address matches exactly. If the MAC address matches, go to step 3.

Figure 1 - MAC Address Screen

Document Part # 026-4186 Rev 1 ©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use. Visit our website at www.climate.emerson.com for the latest technical documentation and updates.

Page 8 of 9

3. Press ,, to access the License Manager Screen
(Figure 2).
4. Press  to access the Activate Feature box.
5. Enter the 16-character license key in the blanks provided. 6. If entered correctly, the message at the bottom of the Add
Feature box should read Feature Activated. Press  to
exit and save. If the key is incorrect, the message will read Feature Unknown or Invalid Key" -- double-check that the key was entered correctly and the MAC address matches the one specified in the report.
Repeat steps 1 through 6 for each license key to be entered for this E2.
Rebooting to Complete License Key Activation When all license keys have been entered for the E2, you must reboot the E2 unit to complete the license key activation process. Press the RESET button on the E2 processor board. When the E2 is finished rebooting, login again and press
,,, and verify the features are listed as enabled. They
will be shown in this screen along with the license key(s) you entered to enable them (Figure 3).

Figure 2 - Add License Screen

Figure 3 - Viewing Licenses

Document Part # 026-4186 Rev 1

Page 9 of 9

This document may be photocopied for personal use. Visit our website at http://www.climate.emerson.com for the latest technical documentation and updates.
Join Emerson Technical Support on Facebook. http://on.fb.me/WUQRnt For Technical Support call 833-409-7505 or email ColdChain.TechnicalServices@Emerson.com The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson reserves the right to modify the designs or specifications of such products at any time without notice. Responsibility for proper selection, use and maintenance of any product remains solely with the
purchaser and end-user. ©2022 Emerson is a trademark of Emerson Electric Co.



References

Adobe PDF Library 15.0