GE Zoneline® Heat Pump Unit with Corrosion Protection, 230/208 Volt
Model: AZHS09DCXXA
Features & Benefits
- Cooling Capacity: 9,700/9,600 BTU
- Energy Efficiency: 12.4/12.4 EER
- Dehumidification: 2 Pints/Hour
- Heat Pump Capacity: 8,000/7,900 BTU
- Heat Pump Efficiency: 3.7/3.8 COP
- Heat Pump Down to 25°F with Reverse Cycle Defrost
- Indoor Fan CFM (High/Low): 400/290
- Electronic Touch Controls with LED Display
- Quiet Operation: Baked-On Mastic Sound Barrier, Cross Flow Blower and Two DC Fan Motors Create Less Noise to Ensure Comfort
- Corrosion Resistant: Extends Life of the Unit in Sea Coast Areas/Corrosive Environments
- SMC Base Pan and Bulkhead: No Rusting and Helps Block Noise
- Heat & Freeze Sentinels: Keeps the Room from Over-Heating or Freezing
- Electronic Temperature Limiting: Prevents Expensive Over-Cooling or Over-Heating of the Room
- Fresh Air Vent CFM (Fully Open High Fan): 40*
- Refrigerant: R 454B
- *When Using the RAKVENT1 Kit
Projected Specifications. Subject to Change Without Notice.
Dimensions and Installation Information
Electrical Wiring
All wiring, including installation of receptacle, must be made in accordance with national and local electrical codes and regulations. Note: Aluminum wiring may pose special problems – consult a qualified electrician.
Grille Options
- Stamped Aluminum Grille: RAG60 Exterior Architectural Louvers
- Durable Polycarbonate: RAG42PB (Beige), RAG42PM (Maple), RAG42PD (Dark Brown)
- Extruded Aluminum Architectural Grille: RAG42AA
Retrofit Kits
- RAK40 - Deflector Kit to adapt chassis for use with non-GE exterior louvered grilles.
Ducted Applications
AZHS, AZES, & AZVS Series without make-up air can be used with ductwork to heat or cool more than one room. RAK6053 Duct Adapter is applied to the top of case over the air discharge. RAK601B Duct Extension is applied to right or left of adapter. Locally fabricated ductwork may be added to extend to maximum recommended straight distance of 15 feet in one direction.
Electrical Connection
230/208 volt units may be plugged into a receptacle. See Architects and Engineers Design Data Manual for electrical connection information including use of sub-base for direct connected units. Installation must comply with national and local electrical codes and regulations. Power connection kits are required on all Zoneline chassis.
Diagrams and Dimensions
Wall Sleeve Dimensions
The RAB42MG* Wall Sleeve is heavy-gauge steel, 4-piece design with insulation, with dimensions A=42", B=13-3/4", C=16". It is also available in 16", 18", 20", and 24" depths. The RAB42PG Wall Sleeve is a 4-piece fiberglass reinforced polyester compound with stainless steel locking components, with dimensions A=42", B=14", C=16".
Wall Opening Dimensions
Add 1/4" to A and C dimensions for all cut-outs. Minimum wall opening dimensions are 16-1/4" Height x 42-1/4" Width.
Maximum Cord Extension
The maximum cord extension is 21 inches.
Electrical Specifications Table
Power Connection Kit | 7K/9K | 12K/15K | ||||
---|---|---|---|---|---|---|
RAK315P RAK315D* RAK204D15C* | RAK320P RAK320D* RAK204D20C* | RAK330P RAK330D* RAK204D30C* | RAK315P RAK315D* RAK204D15C* | RAK320P RAK320D* RAK204D20C* | RAK330P RAK330D* RAK204D30C* | |
Total Watts | 2410/1990 | 3420/2830 | 4830/3990 | 2430/2020 | 3450/2860 | 4860/4020 |
Heater Watts | 2400/1960 | 3400/2780 | 4800/3930 | 2400/1960 | 3400/2780 | 4800/3930 |
Heater BTU | 8100/6600 | 11600/9400 | 16300/13400 | 8100/6600 | 11600/9400 | 16300/13400 |
Total Amps (MCA) | 10.5/9.6 | 14.9/13.6 | 21.0/19.2 | 10.6/9.7 | 15.1/13.8 | 21.2/19.3 |
Recommended Protective Device (MOCP) | 15 amp Time-Delay Fuse or Breaker | 20 amp Time-Delay Fuse or Breaker | 30 amp Time-Delay Fuse or Breaker | 15 amp Time-Delay Fuse or Breaker | 20 amp Time-Delay Fuse or Breaker | 30 amp Time-Delay Fuse or Breaker |
*Per the NEC, use of this connection kit requires the purchase and use of the RAK4002D Junction Box.