Specflex® Bracket for Hat Furring Channels

Installation Instructions

NFP240624 Figure Number

WARNING

You must read and understand all instructions and warnings before attempting to install any Specflex® sprinkler drop system components.

Failure to follow these instructions can lead to improper operation, resulting in serious injury, death or property damage.

We recommend wearing safety glasses or goggles, a hard hat and shoes with foot protection during installation.

Required System Parts

Required Tools

Installation Steps

  1. Inspect the Specflex® sprinkler drop system components for any sign of physical damage. Make sure all components are included and in the proper order.
  2. Disconnect the inlet nipple and outlet reducer from the flexible hose and check that each sealing gasket is in place properly. Reconnect outlet reducer to the flexible hose.
  3. Ensure that both end threads are clean without any damage. Apply PTFE tape to the inlet nipple threads. Use a pipe wrench to connect the inlet nipple to the branch line.
  4. Use a pipe wrench to connect the flexible hose to the inlet nipple. Torque range should be a minimum of 50 to a maximum of 58 ft-lbs.
    DO NOT USE PTFE TAPE ON THE INLET NIPPLE THREAD TO CONNECT TO THE FLEXIBLE HOSE.
  5. Loosely assemble the adjustable end bracket based on the distance between the hat furring channels. Attach the NFP240624 bracket to the hat furring channels. Ensure the leg of each end bracket is properly engaged to the hat furring channels.
  6. Tighten the wing bolts to secure the end brackets onto the hat furring channels. The recommended torque is 1.40-1.48 ft-lbs (190-200 cN • m).
    DO NOT OVERTIGHTEN THE WING BOLT WITH TOOLS. THIS MAY CAUSE DAMAGE TO THE WING BOLT.
  7. Latch down the lever and tighten the top wing bolt on the adjustable end bracket to secure it onto the stock bar. The recommended torque is 1.40–1.48 ft-lbs (190-200 cN • m).
  8. Tighten two sheet metal screws on each end of the bracket, making sure to fully penetrate the hat furring channel. The recommended torque is 1.40-1.48 ft-lbs (190-200 cN • m). Ensure the bottom wing bolts on both ends of the bracket are fully tightened.
  9. Press the release pin and open the center bracket. Load the flex hose on the proper height position in accordance with the type of sprinkler head being used. Close the gate of the center bracket from the left to right and firmly push the lever toward the stock bar until it clicks to secure the outlet reducer.
  10. Verify the location marking on the outlet reducer and match the outlet location for the remaining head installations.

FERGUSON.COM/NFP

Models: NFP240624 Specflex Bracket For Hat Furring Channels, NFP240624, Specflex Bracket For Hat Furring Channels, Bracket For Hat Furring Channels, Furring Channels

File Info : application/pdf, 4 Pages, 1.84MB

PDF preview unavailable. Download the PDF instead.

10100038 15658501 installation

References

Adobe PDF Library 17.0 Adobe InDesign 20.3 (Macintosh)

Related Documents

Preview SPECflex™ SHP Performance Sprinkler Drops - National Fire Products Technical Specification
Detailed technical specifications for National Fire Products' SPECflex™ SHP Performance Sprinkler Drops, including features, standards, technical data, friction loss, and ordering information.
Preview SPECflex™ SHP Performance Sprinkler Drops - National Fire Products
Detailed specifications and technical data for National Fire Products' SPECflex™ SHP Performance Sprinkler Drops, including features, standards, materials, and ordering information.
Preview National Fire Products Low-Profile Specflex Bracket
Details on the National Fire Products Low-Profile Specflex Bracket, including features, technical data, and installation information. This bracket is designed for low-profile applications and is made from zinc-plated steel.
Preview Specflex T-Bar Bracket Installation and Technical Data
Detailed information on the Specflex T-Bar Bracket, including features, technical specifications, and installation guidelines. Available in 24" and 48" lengths for fire sprinkler systems.
Preview Specflex SH Sprinkler Drops - National Fire Products
Technical specifications and installation guidelines for Specflex SH Sprinkler Drops by National Fire Products, including features, standards, technical data, and ordering information.
Preview Three-Way Brass Valve | National Fire Products NFP1102B
Technical specifications and installation guide for the National Fire Products Three-Way Brass Valve (NFP1102B). Features include 1/4" IPS size, 300 WOG working pressure, and NPT threads, suitable for sprinkler system pressure gauge installation. Includes dimensions and material breakdown.
Preview National Fire Products NFP130101G Sight Glass - Technical Specifications and Installation
Detailed technical specifications, features, benefits, and installation guide for the National Fire Products NFP130101G Sight Glass. Includes material chart and dimensions.