User Guide for Elimko models including: KY-94-1123-1 E-94 Series Universal Advanced Controller, KY-94-1123-1, E-94 Series Universal Advanced Controller, Universal Advanced Controller, Advanced Controller, Controller

E94 Quick Start Guide

Murat ARAS

[PDF] E94 Quick Start Guide - Elimkoelimko.com.tr › files

E94 Quick Start Guide

16 nov 2023 — On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves. 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC.


File Info : application/pdf, 2 Pages, 1.54MB

PDF preview unavailable. Download the PDF instead.

E94 Quick Start Guide (Version 23 and later)
KY-94-1123-1

200.0 200.0

E-94 Series Universal Advanced Controller

Quick Start Guide
Manufacturer / Technical Support :
Elimko Elektronik malat ve Kontrol Ltd. ti. ASO 2. Organize Sanayi Bölgesi Alci OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKYE Tel: +90 312 212 64 50 (Pbx) · Fax: +90 312 212 41 43 E-mail: elimko@elimko.com.tr · www.elimko.com.tr

1. DESCRIPTION
E-94 Series general purpose process controllers are industrial devices in 1/8 DIN (96x48 mm IEC/TR 60668) dimensions designed by using new generation microcontrollers with on/off, PID and other control forms. Inputs and outputs can be easily programmed by the user.
In E-94 Series controllers, set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays and general purpose inputs (T/C, R/T, mV, mA) can be programmed.

2. DIMENSIONS and PANEL CUT-OUT

10 mm

10 mm

200.0 200.0

Elimko Kontrol Edilmitir
2

100 mm

100 mm

TP

SKALA :

GR :

ÇIKI :

: E49

SER NO : 21/14798

Elimko
Tel: +90 3122126450 Fax: +90 3122124143
TÜRKYE

91 mm
+0.5 45 mm
-0.0

+0.5 92mm
-0.0

91 mm min. 10 mm

min. 35 mm Panel Cut-Out and Minimum Spacing
3. CONNECTION DIAGRAM
Operating voltage suitable for the device type shall be applied. Relay and SSR Drive Outputs

RL1 / SSR1

RL2 / SSR2

RL3

RL4

Operating Voltage RS-485

Analog Inputs

Analog Output

AO1

TRXTRX+

Valve Pot. Feedback (Note 2) 1-5 kOhm
Valve mA Feedback (Note 2) 0-20 / 4-20 mA
1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2). Controllers with RS-485 do not have a Valve Feedback input. Analog output (AO1) can be selected as either mA or 0-10 V DC.

Analog Input 1

13

13

14

14

15

15

16

16

17

17

18

18

13

13

14

14

15

15

16

16

17

17

18

18

Analog Input 2

13

13

14

14

15

15

16

16

17 V

17

18

18

Thermocouple / miliVolt 0-20 mA / 4-20 mA
Resistance Thermometer 2-Wire Transmitter Volt
External Set Input (mA)

4. WARNINGS

E-94 controller is designed for panel mounting and should be used in an industrial environment.
 The package of E-94 controller conta ns; Controller, 2 p eces of mount ng clamps, User manual and Guarantee cert f cate.
 After open ng the package, please check the contents w th the above l st. If the del vered product s wrong type, any tem s m ss ng or there are v s ble defects, contact the vendor from wh ch you purchased the product.
 Before nstall ng and operat ng the controller, please read the user manual thoroughly.
 The nstallat on and conf gurat on of the controller must only be performed by a person qual f ed n nstrumentat on.
 Keep the un t away from flamable gases, that could cause explos on.
 Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked n water t ghtly squeezed to gently w pe the outer surface of the controller.
 It s not used n med cal appl cat ons.

EU DIRECTIVE COMPLIANCE
Low Voltage D rect ve EN 61010-1 EMC D rect ve EN 61326-1

K - Q TSE-ISO-EN
9000
TS EN ISO 9001 Quality Management System Certificate

5. TYPE CODING

E-94 Series Universal Advanced Controller

E-94 - W - X - Y - Z

Relay Outputs

2 relays (RL1, RL2)

2

3 relays (RL1, RL2, RL3)

3

4 relays (RL1, RL2, RL3, RL4)

4

1 SSR (SSR1) + 1 relay (RL2)

5

1 SSR (SSR1) + 2 relays (RL2, RL3)

6

1 SSR (SSR1) + 3 relays (RL2, RL3, RL4)

7

2 SSR (SSR1, SSR2) + 1 relays (RL3)

8

2 SSR (SSR1, SSR2) + 2 relays (RL3, RL4)

9

Analog Outputs

None

0

0-20 / 4-20 mA (AO1)

1

0-10 V DC (AO1)

2

Communication *

None

0

RS-485 **

1

Operating Voltage

85-265 V AC / 85-375 V DC

0

20-60 V AC / 20-60 V DC

1

* When E-94 Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.
** Controllers with RS-485 do not have a Valve Feedback input.

6. TECHNICAL SPECIFICATIONS

Parameter

Description

Control Type

On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves

Operating Voltage

20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC

Relays / SSR

4 x SPST - NO 250 V AC 5 A relays or 24 V DC 25 mA (SSR) drives

Dimensions (mm)

96 (Lenght) x 48 (Height) x 100 (Width)

Panel Cut-Out (mm) 92 (Lenght) X 45 (Height)

Analog Output

0..20 / 4..20 mA or 0..10 V DC optional

Analog Input

Universal (Note 1), 1 x External set point (mA)

Communication (RS-485) Available (Note 2)

Digital Input

None

Valve Feedback

Available (Note 2)

Transmitter Supply

Available

Weight

220 g

Power Consumption Max. 7 W (10 VA)

Operating Temperature - 10 °C ... 55 °C

Storage Temperature - 25 °C ... 65 °C

Memory

Max. 100.000 write

Protection Class

IP-65 Front Panel, IP-20 Rear Case

Notes:

(1) Universal Input :

Thermocouple

: B, E, J, K, L, N, R, S, T, U

Resistance Thermometer : Pt-100

Current

: 0-20 mA, 4-20 mA (Linear)

Voltage

: 0-50 mV, 0-1 V, 0.2- 1 V (Linear), 0-10 V DC, must be specified in the order.

Resolution Accuracy

: 16 bit : Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
Resistance Thermometer, Max. ±0.5 °C

(Conversion and wire resistance compensation) Linear Input, Max. % 0.1

(2) Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order. Controllers with RS-485 do not have a Valve Feedback input.

INPUT SETTINGS
gcnf

CONTROL SET SETTINGS
SETP

ALARM SETTINGS
ACNF

7. PARAMETER TABLE
Description INP1 Analog Input 1 Type
DP Decimal Point SCLO Analog Input 1 Linear Scale Lower Value SCHI Analog Input 1 Linear Scale Upper Value UNIT Temperature Unit OFST Analog Input 1 Offset Value FLTR Analog Input 1 Filter SNBR Analog Input 1 Sensor Broken Behaviour INP2 Analog Input 2 Type S2LO Analog Input 2 Linear Scale Lower Value S2HI Analog Input 2 Linear Scale Upper Value S2BR Analog Input 2 Sensor Broken Behaviour ADRS Modbus Adress BAUD Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] PRTY Modbus Parity [None, ODD, Even]

SPSR Control Set Point Source SPLL Control Set Point Lower Limit SPHL Control Set Point Upper Limit SPRR Control Set Point Ramping Rate S-1 1. Step Set Value T-1 1. Step Time S-2 2. Step Set Value T-2 2. Step Time S-3 3. Step Set Value T-3 3. Step Time

A1TP Alarm 1 Type
A1SP Alarm 1 Set Point A1HY Alarm 1 Hysteresis A1LT Alarm 1 Lock A2TP Alarm 2 Type A2SP Alarm 2 Set Point A2HY Alarm 2 Hysteresis A2LT Alarm 2 Lock A3TP Alarm 3 Type A3SP Alarm 3 Set Point A3HY Alarm 3 Hysteresis A3LT Alarm 3 Lock A4TP Alarm 4 Type
A4SP Alarm 4 Set Point A4HY Alarm 4 Hysteresis A4LT Alarm 4 Lock

CTYP CFRM CPRD MNPR TRTM DBND OLL OHL OMR PONC TRLL TRHL RL1D RL2D RL3D RL4D AO1D AO1R SRVL SRVH

Control Type Control Form [DIR, REV] Control Period Manual Mode Selection Floating Control Valve Travel Time Dead Band Control Output Lower Limit Control Output Upper Limit Control Output Manual Reset PID Power On Behaviour Retransmission Scale Lower Value Retransmission Scale Upper Value
Relay 1 Function Relay 2 Function Relay 3 Function Relay 4 Function Analog Output 1 Function Analog Output 1 Type Feedback Valve Fully-Closed Position Feedback Valve Fully-Open Position

Min Maks Unit

Table 1

0

3

-199.9 999.9 EU

-199.9 999.9 EU *C *F

-100.0 100.0 EU 1 15 s
LO HI

0-20 4-20

-199.9 999.9 EU -199.9 999.9 EU
LO HI

1 127 4.8 38.4

Table 2 -199.9 SPHL EU SPLL 999.9 EU
OFF 60.0 EU/min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min

Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB

Table 4

DIR REV

1 250 s

DSB ENB

10 2500 s

0.1 25.0 %

0.0 OHL %

OLL 100.0 %

OLL OHL %

0

4

-199.9 TRHL EU

TRLL 999.9 EU

Table 5

Table 5

Table 5

Table 5

Table 6

Table 7.1 ve Table 7.2

AT PID PB-1 PB-2 ITH ITC DTH DTC HYS

PID Auto Tune PID Parameter Type Proportional Band + Proportional Band Integral Time + Integral Time Derivative Time + Derivative Time Hysteresis

OFF ON
STD ADV
0.1 999.9 EU 0.1 999.9 EU OFF 9999 s OFF 9999 s OFF 2500 s OFF 2500 s 0.0 999.9 EU

SCOD DPRL APRL FCST

Security Code Parameter Access Level Parameter Setting Level Factory Settings [OFF, LOAD, SAVE, DFLT]

0 9999

0

9

0

9

8. ACCESSING PARAMETERS

STEP 1:

STEP 2:

Security Code Configuration

Entry Page Selection

(Default: 10) and Entry

STEP 3: Parameter Selection and Configuration

Process Screen
199.8
200.0

Selected Page

 

 SCOD
0

 PAGE
GCNF

  Parameters . . .







Adjustment

Enter

Return

Menu Access


9. APPLICATION EXAMPLES
1) Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output inp1 a1tp a1sp a2tp a2sp ctyp rl1D rl2D ao1D ao1r pt lo 50.0 hi 55.0 sco al-1 al-2 co-1 4-20
2) Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High inp1 a2tp a2sp ctyp rl1D rl2D
j hi 350.0 sco Do-1 al-2
3) Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
inp1 spsr s-1 t-1 s-2 t-2 ctyp trll trhl rl1D rl2D ao1D ao1r k prfl 400 10.0 400 60.0 sco 0 1200 co-1 al-2 pvtr 4-20
4) Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relay1: Valve Open, Relay2: Valve Close
inp1 sclo schi inp2 s2lo s2hi ctyp trtm rl1D rl2D 4-20 0.0 600.0 4-20 0.0 600.0 bnD 30 co-1 co-2

Table 1. Input Type Options b Type B Thermocouple e Type E Thermocouple j Type J Thermocouple k Type K Thermocouple l Type L Thermocouple n Type N Thermocouple r Type R Thermocouple s Type S Thermocouple t Type T Thermocouple u Type U Thermocouple pt Pt-100
0-20 0-20 mA 4-20 4-20 mA 0-50 0-50 mV 0.0-1 0-1 V 0.2-1 0.2-1 V 0-10 0-10 V (*) 2-10 2-10 V (*) (*) Custom specified volt input
Table 2. Control Set Options int Internal adjustment with
keys prfl With Profile Control e/t External adjustment with
AIN2 external input
Table 3. Alarm Options off Off lo Low Alarm hi High Alarm loD Low Deviation hiD High Deviation lob Band Alarm (In) hib Band Alarm (Out)

Table 4. Control Type Options off No Control sco Single (Heat) Dco Double (Heat/Cool) bnD Floating Control of Valve pfb Feedback Control of Valve
Tablo 5. Relay Output Options co-1 PID + (Heating) co-2 PID - (Cooling) Do-1 On-Off + (Heating) Do-2 On-Off - (Cooling) al-1 Alarm 1 al-2 Alarm 2 al-3 Alarm 3 al-4 Alarm 4
Table 6. Analog Output Options co-1 PID + (Heating) co-2 PID - (Cooling) pvtr Process Value sptr Control Set Value
Table 7.1. Analog Output Range 0-20 0-20 mA 20-0 20-0 mA 4-20 4-20 mA 20-4 20-4 mA
Table 7.2. Analog Output Range 0-10 0-10 V 10-0 10-0 V 2-10 2-10 V 10-2 10-2 V

For detailed information, you can access the comprehensive user manual of the device under the heading "User Manuals" at www.elimko.com.tr. You can also use the QR Code on the front for this.

OUTPUT SETTINGS
OCNF

PID SETTINGS
tUNE

SECURITY
PRTC

Elimko Elektronik malat ve Kontrol Ticaret Ltd. ti. Ankara Sanayi Odasi 2. Organize Sanayi Bölgesi Alci OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKYE