Rosemount 8712EM Transmitter with HART Protocol Quick Start Guide

Document Number: 00825-0100-4445, Rev AB

Publication Date: November 2017

1 Safety

⚠️ WARNING!

⚠️ CAUTION!

2 Introduction

This document provides basic installation guidelines for the Rosemount 8712EM wall-mount transmitter.

All user documentation can be found at www.emerson.com. For more contact information see Section 2.2.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.

2.2 Emerson Flow customer service

Email:

Telephone:

North and South AmericaEurope and Middle EastAsia Pacific
United States: 800 522 6277U.K.: 0870 240 1978Australia: 800 158 727
Canada: +1 303 527 5200The Netherlands: +31 (0) 704 136 666New Zealand: 099 128 804
Mexico: +41 (0) 41 7686 111France: 0800 917 901India: 800 440 1468
Argentina: +54 11 4837 7000Germany: 0800 182 5347Pakistan: 888 550 2682
Brazil: +55 15 3413 8000Italy: 8008 77334China: +86 21 2892 9000
Venezuela: +58 26 1731 3446Central & Eastern Russia/CIS: +41 (0) 41 7686 111, +7 495 981 9811Japan: +81 3 5769 6803
Egypt: 0800 000 0015South Korea: +82 2 3438 4600
Oman: 800 70101Singapore: +65 6 777 8211
Qatar: 431 0044Thailand: 001 800 441 6426
Kuwait: 663 299 01Malaysia: 800 814 008
South Africa: 800 991 390
Saudi Arabia: 800 844 9564
UAE: 800 0444 0684

3 Pre-installation

Before installing the transmitter, there are several pre-installation steps that should be completed to make the installation process easier:

Note: Refer to the product reference manual for more detailed requirements.

Identify options and configurations

The typical transmitter installation includes a device power connection, a 4-20mA output connection, and sensor coil and electrode connections. Other applications may require one or more of the following configurations or options:

Hardware switches

The transmitter may have up to four user-selectable hardware switches. These switches set the alarm mode, internal/external analog power, internal/ external pulse power, and transmitter security. The standard configuration for these switches when shipped from the factory is as follows:

Table 3-1: Hardware switch default settings
SettingFactory configuration
Alarm modeHigh
Internal/external analog powerInternal
Internal/external pulse powerExternal
Transmitter securityOff

The analog power switch and pulse power switches are not available when ordered with intrinsically safe output, ordering code B.

In most cases, it is not necessary to change the setting of the hardware switches. If the switch settings need to be changed, refer to the product reference manual.

Mechanical considerations

The mounting site for the transmitter should provide enough room for secure mounting, easy access to conduit entries, full opening of the transmitter covers, and easy readability of the Local Operator Interface (LOI) screen (if equipped).

3.1 Dimensional Drawing

Figure 3-1: Rosemount 8712EM Dimensional Drawing

The diagram shows the physical dimensions of the Rosemount 8712EM transmitter. Key dimensions are provided in inches [millimeters].

Note: Dimensions are in inches [Millimeters].

Electrical considerations

Before making any electrical connections to the transmitter, consider national, local, and plant electrical installation requirements. Be sure to have the proper power supply, conduit, and other accessories necessary to comply with these standards.

The transmitter requires external power. Ensure access to a suitable power source.

Table 3-2: Electrical Data
Rosemount 8712EM Flow Transmitter
Power inputAC power: 90–250VAC, 0.45A, 40VA
Standard DC power: 12–42VDC, 1.2A, 15W
Low power DC: 12–30VDC, 0.25A, 3W
Pulsed circuitInternally powered (Active): Outputs up to 12VDC, 12.1mA, 73mW
Externally powered (Passive): Input up to 28VDC, 100mA, 1W
4-20mA output circuitInternally Powered (Active): Outputs up to 25mA, 24VDC, 600mW
Externally Powered (Passive): Input up to 25mA, 30VDC, 750mW
Um250V
Coil excitation output500mA, 40V max, 9W max

Environmental considerations

To ensure maximum transmitter life, avoid extreme temperatures and excessive vibration. Typical problem areas include the following:

Remote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service.

4 Mounting

Wall mount transmitters are shipped with mounting hardware for use on a 2-in. pipe or flat surface.

Figure 4-1: Mounting bracket

The diagram shows the mounting bracket components: A (U-bolt), B (Saddle clamp), and C (Fasteners).

4.1 Pipe mounting

  1. Attach the saddle clamp to the pipe using the U-bolt mounting hardware.
  2. Attach the transmitter to the saddle clamp assembly with appropriate fasteners.

4.2 Surface mounting

Attach the transmitter to the mounting location using customer supplied mounting screws. The installation of the transmitter shall be rated for four (4) times the weight of the transmitter or 44lbs (20kgs).

5 Wiring

5.1 Conduit entries and connections

Transmitter conduit entries ports are ½"-14NPT as standard, M20 conduit connections will use an adapter. Conduit connections should be made in accordance with national, local, and plant electrical codes. Unused conduit entries should be sealed with the appropriate certified plugs. The plastic shipping plugs do not provide ingress protection.

5.2 Conduit requirements

Figure 5-1: Best practice conduit preparation

The diagram illustrates best practices for conduit preparation, showing connections for safety ground (A), power (B), coil (C), output (D), and electrode (E) to the transmitter.

5.3 Sensor to transmitter wiring

Wiring details

Cable kits are available as individual component cables or as a combination coil/electrode cable. Remote cables can be ordered directly using the kit numbers shown in Table 5-1, Table 5-2, and Table 5-3. Equivalent Alpha cable part numbers are also provided as an alternative. To order cable, specify length as quantity desired. Equal length of component cables is required.

Examples:

Table 5-1: Component cable kits - standard temperature (-20°C to 75°C)
Cable kit #DescriptionIndividual cableAlpha p/n
08732-0065-0001 (feet)Kit, component cables, Std temp (includes Coil and Electrode)Coil
Electrode
2442C
2413C
08732-0065-0002 (meters)Kit, component cables, Std temp (includes Coil and Electrode)Coil
Electrode
2442C
2413C
08732-0065-0003 (feet)Kit, component cables, Std temp (includes Coil and I.S. Electrode)Coil
Instrinsically Safe Blue Electrode
2442C
Not available
08732-0065-0004 (meters)Kit, component cables, Std temp (includes Coil and I.S. Electrode)Coil
Instrinsically Safe Blue Electrode
2442C
Not available
Table 5-2: Component cable kits - extended temperature (-50°C to 125°C)
Cable kit #DescriptionIndividual cableAlpha p/n
08732-0065-1001 (feet)Kit, Component Cables, Ext Temp. (includes Coil and Electrode)Coil
Electrode
Not available
Not available
08732-0065-1002 (meters)Kit, Component Cables, Ext Temp. (includes Coil and Electrode)Coil
Electrode
Not available
Not available
08732-0065-1003 (feet)Kit, Component Cables, Ext Temp. (includes Coil and I.S. Electrode)Coil
Intrinsically Safe Blue Electrode
Not available
Not available
08732-0065-1004 (meters)Kit, Component Cables, Ext Temp. (includes Coil and I.S. Electrode)Coil
Intrinsically Safe Blue Electrode
Not available
Not available
Table 5-3: Combination cable kits - coil and electrode cable (-20°C to 80°C)
Cable kit #Description
08732-0065-2001 (feet)Kit, Combination Cable, Standard
08732-0065-2002 (meters)Kit, Combination Cable, Standard
08732-0065-3001 (feet)Kit, Combination Cable, Submersible (80°C dry/60°C Wet)
08732-0065-3002 (meters)Kit, Combination Cable, Submersible (80°C dry/60°C Wet) (33ft Continuous)

Cable requirements

Shielded twisted pairs or triads must be used. For installations using the individual coil drive and electrode cable, see Figure 5-2. Cable lengths should be limited to less than 500 feet (152 m). Consult factory for length between 500–1000 feet (152–304 m). Equal length cable is required for each. For installations using the combination coil drive/electrode cable, see Figure 5-3. Combination cable lengths should be limited to less than 330 feet (100 m).

Figure 5-2: Individual component cables

This diagram illustrates the construction of individual component cables. Diagram A shows the Coil drive cable with conductors Red (1), Blue (2), and Drain (3). Diagram B shows the Electrode cable with conductors Yellow (18), White (19), and Drain (17). Labels E and F describe the cable's overlapping foil shield and outer jacket.

Figure 5-3: Combination coil and electrode cable

This diagram shows the construction of the combination coil and electrode cable. Labels A, B, and C describe the Electrode shield drain, Overlapping foil shield, and Outer jacket, respectively. The conductors are identified by color and number: Red (1), Blue (2), Drain (3), Black (17), Yellow (18), and White (19).

Cable preparation

Prepare the ends of the coil drive and electrode cables as shown in Figure 5-4. Remove only enough insulation so that the exposed conductor fits completely under the terminal connection. Best practice is to limit the unshielded length (D) of each conductor to less than one inch. Excessive removal of insulation may result in an unwanted electrical short to the transmitter housing or other terminal connections. Excessive unshielded length, or failure to connect cable shields properly, may also expose the unit to electrical noise, resulting in an unstable meter reading.

Figure 5-4: Cable ends

This diagram shows prepared cable ends for Coil (A), Electrode (B), and Combination (C) cables, highlighting the unshielded length (D).

⚠️ WARNING! Shock hazard! Potential shock hazard across remote junction box terminals 1 and 2 (40V).

⚠️ WARNING! Explosion hazard! Electrodes exposed to process. Use only compatible transmitter and approved installation practices. For process temperatures greater than 284°F (140°C), use a wire rated for 257°F (125°C).

Remote junction box terminal blocks

Figure 5-5: Remote junction box views

The diagram shows the remote junction box views, illustrating connections between the Sensor (A) and the Transmitter (B).

Table 5-4: Sensor/transmitter wiring
Wire colorSensor terminalTransmitter terminal
Red11
Blue22
Shield3 or Float3
Black1717
Yellow1818
White1919

Note: For hazardous locations, refer to the product reference manual.

5.4 Wiring diagrams

Figure 5-6: Wiring 8712EM using component cable

This diagram illustrates the wiring of the Rosemount 8712EM transmitter using component cables, showing connections from sensor to transmitter.

Figure 5-7: Wiring 8712EM using combination cable

This diagram illustrates the wiring of the Rosemount 8712EM transmitter using combination cables, showing connections from sensor to transmitter.

5.5 Power and I/O terminal blocks

Open the bottom cover of the transmitter to access the terminal block.

Note: To connect pulse output and/or discrete input/output, and for installations with intrinsically safe outputs, refer to the product reference manual.

Figure 5-8: 8712EM Terminal blocks

The diagram shows the 8712EM Terminal blocks layout.

Table 5-5: 8712EM Power and I/O terminals
Terminal numberAC versionDC version
1Coil PositiveCoil Positive
2Coil NegativeCoil Negative
3Coil ShieldCoil Shield
5+ Pulse+ Pulse
6– Pulse– Pulse
7(1)Analog HARTAnalog HART
8(1)Analog HARTAnalog HART
9(2)+ Discrete In/Out 2+ Discrete In/Out 2
10(2)– Discrete In/Out 2– Discrete In/Out 2
11(2)+ Discrete In/Out 1+ Discrete In/Out 1
12(2)– Discrete In/Out 1– Discrete In/Out 1
17Electrode ReferenceElectrode Reference
18Electrode NegativeElectrode Negative
19Electrode PositiveElectrode Positive
NAC (Neutral)/L2DC (–)
L1AC L1DC (+)

(1) Note Polarity: Internally Powered, Terminal 7 (–) Analog HART, Terminal 8 (+) Analog HART. Externally Powered, Terminal 7 (+) Analog HART, Terminal 8 (–) Analog HART

(2) Only available with ordering code AX.

5.6 Powering the transmitter

The transmitter is available in three models. The AC powered transmitter is designed to be powered by 90–250VAC (50/60Hz). The DC powered transmitter is designed to be powered by 12–42VDC. The low power transmitter is designed to be powered by 12-30VDC. Before connecting power to the transmitter, be sure to have the proper power supply, conduit, and other accessories. Wire the transmitter according to national, local, and plant electrical requirements for the supply voltage.

If installing in a hazardous location, verify that the meter has the appropriate hazardous area approval. Each meter has a hazardous area approval tag attached to the side of the transmitter housing.

AC power supply requirements

Units powered by 90 - 250VAC have the following power requirements. Peak inrush is 35.7A at 250VAC supply, lasting approximately 1ms. Inrush for other supply voltages can be estimated with: Inrush (Amps) = Supply (Volts) / 7.0

Figure 5-9: AC current requirements

This graph shows the relationship between Supply Current (amps) on the Y-axis and Power Supply (VAC) on the X-axis.

Apparent power

Figure 5-10: Apparent power

This graph shows Apparent Power (VA) on the Y-axis versus Power Supply (VAC) on the X-axis.

DC power supply requirements

Standard DC units powered by 12VDC power supply may draw up to 1.2A of current steady state. Low power DC units may draw up to 0.25A of current steady state. Peak inrush is 42A at 42VDC supply, lasting approximately 1ms. Inrush for other supply voltages can be estimated with: Inrush (Amps) = Supply (Volts) / 1.0

Figure 5-11: DC current requirements

This graph shows the Supply Current (amps) on the Y-axis versus Power Supply (VDC) on the X-axis for standard DC units.

Figure 5-12: Low power DC current requirements

This graph shows the Supply Current (amps) on the Y-axis versus Power Supply (VDC) on the X-axis for low power DC units.

Supply wire requirements

Use 10–18 AWG wire rated for the proper temperature of the application. For wire 10–14 AWG use lugs or other appropriate connectors. For connections in ambient temperatures above 122 °F (50 °C), use a wire rated for 194 °F (90 °C). For DC powered transmitters with extended cable lengths, verify that there is a minimum of 12VDC at the terminals of the transmitter with the device under load.

Electrical disconnect requirements

Connect the device through an external disconnect or circuit breaker per national and local electrical code.

Installation category

The installation category for the transmitter is OVERVOLTAGE CAT II.

Overcurrent protection

The transmitter requires overcurrent protection of the supply lines. Fuse rating and compatible fuses are shown in Table 5-6.

Table 5-6: Fuse requirements
Power systemPower supplyFuse ratingManufacturer
AC power90–250VAC2 Amp quick actingBussman AGC2 or equivalent
DC power12–42VDC3 Amp quick actingBussman AGC3 or equivalent
Table 5-6: Fuse requirements (continued)
Power systemPower supplyFuse ratingManufacturer
DC low power12–30VDC3 Amp quick actingBussman AGC3 or equivalent

Power terminals

For AC powered transmitter (90–250VAC, 50/60 Hz):

For DC powered transmitter:

Covers

Use the transmitter lower door screw to secure the terminal compartment after the instrument has been wired and powered up. Follow these steps to ensure the housing is properly sealed to meet ingress protection requirements:

  1. Ensure all wiring is complete and close the lower door.
  2. Tighten the lower door screw until the lower door is tight against the housing. Metal to metal contact of the screw bosses is required to ensure a proper seal.

Note: Application of excessive torque may strip the threads or break the screw.

  1. Verify the lower door is secure.

5.7 Analog output

The analog output signal is a 4-20mA current loop. Depending on the IS output option, the loop can be powered internally or externally via a hardware switch located on the front of the electronics stack. The switch is set to internal power when shipped from the factory. Intrinsically safe analog output requires a shielded twisted pair cable. For HART communication, a minimum resistance of 250 ohms is required. It is recommended to use individually shielded twisted pair cable. The minimum conductor size is 24 AWG (0.51mm) diameter for cable runs less than 5,000 feet (1,500m) and 20 AWG (0.81mm) diameter for longer distances.

Note: For more information about the analog output characteristics, refer to the product reference manual.

Internal Power

Figure 5-13: Analog output wiring, internal power

The diagram shows the internal power wiring for the 4-20mA analog output. It indicates connecting the negative signal (A) to Terminal #7 and the positive signal (B) to Terminal #8.

Note: Terminal polarity for the analog output is reversed between internally and externally powered.

External power

Figure 5-14: Analog output wiring, external power

The diagram shows the external power wiring for the 4-20mA analog output. It shows connecting the positive power supply (A) to Terminal #7 and the negative power supply to Terminal #8.

Note: Terminal polarity for the analog output is reversed between internally and externally powered.

Figure 5-15: Analog loop load limitations

This graph illustrates the analog loop load limitations. The Y-axis shows Load (ohms), and the X-axis shows Power supply (volts). The operating region (C) is defined by the formulas:

6 Basic Configuration

Once the magnetic flowmeter is installed and power has been supplied, the transmitter must be configured through the basic setup. These parameters can be configured through either an LOI or a HART communication device. Configuration settings are saved in nonvolatile memory within the transmitter. Descriptions of more advanced functions are included in the product reference manual.

6.1 Basic Setup

Tag

Tag is the quickest and shortest way of identifying and distinguishing between transmitters. Transmitters can be tagged according to the requirements of your application. The tag may be up to eight characters long as standard, or 32 characters long when ordered with HART 7.

Flow units (PV)

The flow units variable specifies the format in which the flow rate will be displayed. Units should be selected to meet your particular metering needs.

Line size

The line size (sensor size) must be set to match the actual sensor connected to the transmitter. The size must be specified in inches.

Upper range value (URV)

The URV sets the 20 mA point for the analog output. This value is typically set to full-scale flow. The units that appear will be the same as those selected under the flow units parameter. The URV may be set between –39.3 ft/s to 39.3 ft/s (–12 m/s to 12m/s). There must be at least 1 ft/s (0.3 m/s) span between the URV and LRV.

Lower range value (LRV)

The LRV sets the 4 mA point for the analog output. This value is typically set to zero flow. The units that appear will be the same as those selected under the flow units parameter. The LRV may be set between –39.3 ft/s to 39.3 ft/s (–12 m/s to 12m/s). There must be at least 1 ft/s (0.3 m/s) span between the URV and LRV.

Calibration number

The sensor calibration number is a 16-digit number generated at the factory during flow calibration, is unique to each sensor, and is located on the sensor tag.

6.2 Local operator interface (LOI)

To access the transmitter menu, press the XMTR MENU key. Use the UP, DOWN, LEFT(E), and RIGHT arrows to navigate the menu structure. A complete map of the LOI menu structure is shown in the product reference manual.

The display can be locked to prevent unintentional configuration changes. The display lock can be activated through a HART communication device, or by holding the UP arrow for three seconds and then following the on-screen instructions.

When the display lock is activated, a lock symbol will appear in the lower right hand corner of the display. To deactivate the display lock, hold the UP arrow for three seconds and follow the on-screen instructions. Once deactivated, the lock symbol will no longer appear in the lower right hand corner of the display.

6.3 Field Communicator interface

Use the menu paths to configure basic setup of the transmitter using a field communicator.

Table 6-1: Basic setup menu paths
FunctionMenu path
Basic SetupConfigure > Manual Setup > Basic Setup
Flow UnitsConfigure > Manual Setup > Basic Setup > Flow Units
PV Upper Range Value (URV)Configure > Manual Setup > Basic Setup > AO > URV
PV Lower Range Value (LRV)Configure > Manual Setup > Basic Setup > AO > LRV
Calibration NumberConfigure > Manual Setup > Basic Setup > Setup > Calibration number
Line SizeConfigure > Manual Setup > Basic Setup > Setup > Line Size
TagConfigure > Manual Setup > Device Info > Identification > Tag
Long TagConfigure > Manual Setup > Device Info > Identification > Long Tag
OverviewOverview

Contact Information

Emerson Automation Solutions USA
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com

Emerson Automation Solutions Europe
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.micromotion.nl

Emerson Automation Solutions Asia
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6777-8211
F +65 6770-8003

Emerson Automation Solutions Japan
1-2-5, Higashi Shinagawa
Shinagawa-ku
Tokyo 140-0002 Japan
T +81 3 5769-6803
F +81 3 5769-6844

Emerson Automation Solutions United Kingdom
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181

©2017 Rosemount, Inc. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount, 8600, 8700, 8800 marks are marks of one of the Emerson Automation Solutions family of companies. All other marks are property of their respective owners.

PDF preview unavailable. Download the PDF instead.

quick-start-guide-8712em-hart-rosemount-en-1730786 AH XSL Formatter V6.3 R1a for Windows (x64) : 6.3.1.23560 (2016/02/09 11:02JST) Antenna House PDF Output Library 6.3.752 (Windows (x64))

Related Documents

Preview Rosemount 8732EM Transmitter with HART Protocol Quick Start Guide
This document provides basic installation guidelines for the Rosemount 8732EM field-mount transmitter, covering safety, mounting, wiring, and basic configuration.
Preview Rosemount 3144P Temperature Transmitter Quick Start Guide
This guide provides essential information for the installation and initial setup of the Rosemount 3144P Temperature Transmitter, featuring HART Protocol and Rosemount X-well Technology. It covers system readiness, configuration, mounting, wiring, power application, loop testing, and safety certifications.
Preview Rosemount 8800D Series Vortex Flow Meter Quick Start Guide
This Quick Start Guide provides essential information for the installation and basic configuration of the Rosemount 8800D Series Vortex Flow Meter, covering pre-installation planning, mounting, wiring, and setup for industrial applications.
Preview Rosemount 3051S Series of Instrumentation | Emerson Pressure, Flow, Level Transmitters
Explore the Rosemount 3051S Series of Instrumentation from Emerson, offering advanced pressure, flow, and level measurement solutions for industrial applications. This data sheet details key features, specifications, and model selection.
Preview Rosemount 2051 Pressure Transmitter Product Data Sheet
Emerson's Rosemount 2051 series offers advanced pressure transmitters, flow meters, and liquid level transmitters, known for their accuracy, reliability, and integration capabilities. This data sheet details product offerings, specifications, and ordering information for industrial applications.
Preview Rosemount 8800D Series Vortex Flow Meter Reference Manual
A comprehensive guide detailing the installation, configuration, troubleshooting, and specifications of the Rosemount 8800D Series Vortex Flow Meter, designed for accurate flow measurement in industrial applications.
Preview Rosemount 520 Level Transmitter Quick Start Guide
This guide provides essential information for the Rosemount 520 Level Transmitter, covering installation, wiring, configuration, and product certifications. Learn about HART communication, mounting options, and safety guidelines.
Preview Rosemount G1 Welding Mandrel Quick Start Guide
Provides essential instructions for mounting the Rosemount G1 Welding Mandrel (part number FB-6041), including safety precautions and step-by-step procedures for installation.