Installing and Testing a GFCI Receptacle

Brand: Eaton

Document Reference: EIS-0018-E (REV. B)

Please read this leaflet completely before getting started.

Visit: www.eaton.com | www.cooperwiringdevices.com

Should You Install It?

Installing a GFCI receptacle can be more complicated than installing a conventional receptacle. Ensure you:

⚠️ CAUTION

1. What is a GFCI?

A GFCI (Ground Fault Circuit Interrupter) receptacle differs from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.

Definition of a ground fault: Electricity passes through a person's body to reach the ground, instead of following its normal safe path. A defective appliance can cause a ground fault.

A GFCI receptacle does not protect against circuit overloads, short circuits, or shocks. For example, you can still be shocked if you touch bare wires while standing on a non-conducting surface (e.g., a wood floor).

2. The GFCI's Features

Front View Description:

The front of the GFCI receptacle features two outlets, a "TEST" button, a "RESET" button, and a "correct wiring/trip indicator" light. It also includes a mounting bracket.

Back View Description:

The back of the GFCI receptacle has several terminals:

Terminal Screw Colors: Green = grounding terminal, Silver = white terminals, Brass = hot terminals.

A yellow sticker covers the LOAD terminals; do not remove it until instructed.

4. LINE vs. LOAD

A cable typically consists of 2 or 3 wires (hot, neutral, and sometimes ground).

LINE cable: Delivers power from the service panel (breaker panel or fuse box) to the GFCI. If only one cable enters the electrical box, it is the LINE cable. This cable connects to the GFCI's LINE terminals only.

LOAD cable: Delivers power from the GFCI to other receptacles in the circuit. This cable connects to the GFCI's LOAD terminals only (initially covered by the yellow sticker).

5. Turn the Power OFF

Plug an electrical device (e.g., a lamp or radio) into the receptacle you are working on and turn it ON. Go to the service panel, find the breaker or fuse protecting that receptacle, and turn it OFF or remove the fuse. The device must turn OFF.

Next, plug in and turn ON the device at the receptacle's other outlet to confirm power is OFF at both outlets. If power is not OFF, stop and call an electrician.

6. Identify Cables/Wires

Important: Do not install the GFCI receptacle in an electrical box containing more than 4 wires (excluding ground wires) or cables with more than two wires (excluding ground wire). Contact a qualified electrician if these conditions apply.

If replacing an old receptacle, pull it out without disconnecting wires.

Procedure for a box with two cables (4-6 wires):

  1. Detach one cable's white and hot wires from the old receptacle and cap them separately with wire connectors. Ensure they belong to the same cable.
  2. Re-install the old receptacle in the box, attach the faceplate, and turn the power ON at the service panel.
  3. Determine if power is flowing to the receptacle. If yes, the capped wires are the LOAD wires. If no, the capped wires are the LINE wires.
  4. Turn the power OFF at the service panel, label the LINE and LOAD wires, and remove the receptacle.
  5. Proceed to Step 7B.

Placement in Circuit Diagram Description:

The GFCI's position in the circuit determines which receptacles it protects. Placing the GFCI in position A (where the LINE cable connects to LINE and the LOAD cable connects to LOAD) will also protect downstream receptacles B and C. Placing the GFCI in position C (where only the LINE cable connects to LINE) will not provide protection to receptacles A or B. Receptacles A, B, and C can be in different rooms.

7. Connect the Wires

(Choose A or B, only after reading the other side completely)

A: One cable (2 or 3 wires) entering the box

Diagram shows an electrical box with one cable entering. The cable has Hot (black), White (neutral), and Ground (bare copper/green) wires. The GFCI receptacle is shown with LINE terminals and a Ground terminal.

Connections:

Wire Connection Methods:

Complete the installation:

B: Two cables (4 or 6 wires) entering the box

Diagram shows an electrical box with two cables entering. One cable is the LINE (power in), the other is the LOAD (power out to other receptacles). Both cables have Hot, White, and Ground wires. The GFCI receptacle is shown with LINE and LOAD terminals, and a Ground terminal. The yellow sticker is visible over the LOAD terminals.

Connections:

Wire Connection Methods:

Complete the installation:

8. Test Your Work

Why perform this test? If you miswire the GFCI, it may not prevent personal injury or death due to a ground fault (electric shock).

Upon initial installation, if LINE wires are mistakenly connected to LOAD terminals, this Eaton GFCI will not reset and will not provide power to its receptacle face or load terminals.

Procedure:

  1. Turn the power ON at the service panel. Press the RESET button fully. Plug a lamp or radio into the GFCI and leave it plugged in to verify power is ON. If there is no power, refer to Troubleshooting.
  2. Press the TEST button to trip the device. This should stop the flow of electricity, turning OFF the radio or lamp and activating the yellow Correct Wiring/Trip Indicator. To restore power, press the RESET button.
  3. If you installed using Step 7B (two cables), plug a lamp or radio into surrounding receptacles to see which ones also lost power when you pressed the TEST button. Do not plug life-saving devices into receptacles that lost power. Place a "GFCI Protected" sticker on every receptacle that lost power.
  4. Press the TEST button (then RESET button) every month to ensure proper operation.
  5. Note that this Eaton GFCI is shipped in the Tripped state and cannot be reset until it is wired correctly and powered from its LINE terminals.
  6. The RESET button will pop out. If the power goes OFF and the correct wiring/trip indicator stays ON, you have installed the GFCI receptacle correctly.
  7. LINE/LOAD reversal will be indicated by the RESET button not staying in after being pressed. This reversal will also be indicated by the Correct Wiring/Trip Indicator failing to be ON while the GFCI is tripped.

Troubleshooting

Turn the power OFF and check wire connections against the appropriate wiring diagram in Step 7A or 7B. Ensure there are no loose wires or connections.

It is possible that you reversed the LINE and LOAD connections. Reverse them if necessary. Restart the test from the beginning of Step 8 if you rewired any connections.

NOTE: If this EATON GFCI has tripped and can no longer be reset, it has reached its "End of Life" and will no longer provide power. Replace with the same model EATON GFCI to continue providing ground fault protection.

GFCI Ratings

General Information: Eaton's Limited 2 Year Warranty

EATON warrants its Ground Fault Circuit Interrupter (GFCI) to be free of defects in materials and workmanship in normal use and service for a period of two years from the date of original purchase.

This warranty is in lieu of all other warranties, obligations, or liabilities, expressed or implied, including any implied warranty of merchantability or fitness for a particular purpose that exceeds two years from the date of original consumer purchase. No agent, representative, or employee of Eaton has authority to increase or alter Eaton's obligations under this warranty.

To obtain warranty service for a properly installed Eaton GFCI that proves defective in normal use, send the defective GFCI prepaid and insured to: Quality Control Dept., EATON, 203 Cooper Circle, Peachtree City, GA 30269.

Eaton will repair or replace the defective unit at its option. Eaton is not responsible under this warranty if examination shows the defect was caused by misuse, abuse, improper installation, alteration, improper maintenance, or damage in shipment to Eaton.

Eaton shall have no responsibility for the installation of the GFCI, or for any personal injury, property damage, or any special, incidental, contingent, or consequential damages of any kind resulting from defects in the GFCI or its failure to function in the event of a ground fault on its protected circuit, or for breach of any express or implied warranty on this product.

The exclusive remedy for breach of this limited warranty is the repair or replacement of the defective product at Eaton's option. Implied warranties (if any), including but not limited to implied warranties of fitness for a particular purpose and merchantability, are limited in duration to two years from the date of original consumer purchase. In no case shall Eaton's liability under any other remedy prescribed by law exceed the purchase price.

Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Read enclosed instructions carefully.

PDF preview unavailable. Download the PDF instead.

GFCI-Wiring-Instructions-Eaton Adobe PDF Library 15.0

Related Documents

Preview Installing and Testing an Eaton GFCI Receptacle
A guide on how to install and test a Ground Fault Circuit Interrupter (GFCI) receptacle, including wiring instructions, LINE vs. LOAD identification, and troubleshooting tips. Learn about GFCI features and safety precautions.
Preview Eaton HF GFCI Breakers: Enhancing Safety and Interoperability
This white paper from Eaton discusses High-Frequency (HF) GFCI breakers, detailing their proposed enhancements to standards for high-frequency applications, improved safety, interoperability, and unique implementation by Eaton.
Preview Eaton Series NRX Drawout Cassette Interphase Barrier Installation and Removal Instructions
Comprehensive installation and removal instructions for Eaton Series NRX drawout cassette interphase barriers (Type RF Frame IEC, IZMX40). Includes essential safety warnings and step-by-step procedures for proper installation and maintenance.
Preview Eaton E-VAC HV Vacuum Circuit Breaker Installation and Operating Instructions
This guide provides essential installation, operation, maintenance, and technical details for the Eaton E-VAC Enclosed Indoor High Voltage Vacuum Circuit Breaker (Model IL550-0501001E), ensuring safe and efficient use in industrial and power grid applications.
Preview Eaton Wiring Manual 2011: Electrical Systems, Automation, and Power Management
Comprehensive 2011 Wiring Manual from Eaton, detailing the Moeller series for electrical systems, automation, motor control, and power management. Includes technical guides, product information, and safety standards.
Preview Eaton Series NRX Type NF Bus Extension Kit for 65 kA Fixed Front Connect Breaker Installation Instructions
Detailed installation instructions for the Eaton Series NRX Type NF bus extension kit, designed for 65 kA fixed front connect circuit breakers. It includes essential safety warnings, general information about the product, step-by-step assembly procedures, and technical specifications for cable terminals and kits. The instructions cover the proper attachment of bus conductor extensions and cable terminals to the breaker bus adapters, emphasizing correct torque values and safety precautions.
Preview Eaton DILM & XTCEX Wiring Kits: Installation Instructions and Safety Guide
Comprehensive installation leaflet for Eaton DILM and XTCEX series contactors and wiring kits, including essential safety warnings, wiring diagrams, and technical specifications for motor control applications.
Preview Installation Instructions for Eaton Series NRX Breaker and Trip Unit Remote Mount CAM Module Adapter
This document provides installation instructions for the Eaton Series NRX Breaker and Trip Unit Remote Mount CAM Module Adapter (IL019001EN). It details kit contents, connection procedures to the NRX circuit breaker and CAM module, and includes descriptions of diagrams illustrating the setup. Essential for proper remote mounting of CAM modules with Series NRX breakers.