Regiolux LOWEA 830/840 Luminaire
Model: 6089 LOAMP/325X1562
Brand: Regiolux
General Information
This luminaire contains a light source of energy efficiency class D.
Voltage: 220-240 V
Frequency: ~50/60 Hz
Impact Protection: IK 05
Safety Warnings
⚠️ Attention: Do not open the luminaire! This will result in loss of guarantee.
Installation, commissioning, and maintenance must only be performed by a qualified electrician.
Never work on the luminaire while it is live. Risk of electric shock!
Ensure electrical connection complies with all applicable standards and regulations.
Do not operate damaged luminaires.
Retain safety and mounting instructions.
No liability for damages from improper use.
Use only genuine parts for repair.
Ensure ceiling and fastening elements have adequate load-bearing capacity.
Luminaire is intended for indoor use and ambient temperatures up to 25°C, unless otherwise specified.
LEDs are sensitive to Electrostatic Discharge (ESD). Always avoid direct contact. ESD can cause total failure.
Avoid contact with chemicals (acids, bases, solvents, volatile organic compounds, oils) as they can damage LED modules.
Ensure sufficient ventilation to prevent damage from gas release.
To avoid EMC problems, do not route feed-through wiring directly along the luminaire wiring.
Connect control inputs of dimmable luminaires with standard cables suitable for mains voltage.
Luminaire Operation
Abnormal dark spots may indicate partial LED failure. Inspect regularly and replace affected luminaires.
The light source (LED) of this luminaire must not be exchanged or replaced by the user.
Exceeding permissible ambient temperature reduces luminaire lifespan and can cause premature failure.
Avoid condensation on the luminaire.
Mechanical load on LED circuit boards is not permitted.
Product Modifications
Modification, reworking, or re-marking of products can negatively impact technical properties, destroy them, and cause consequential damage. The manufacturer is not responsible for damage caused by such changes.
Installation Guide
Step 1: Prepare luminaire frame for mounting.
Step 2: Mount the luminaire to the ceiling. Ensure minimum clearance of 300mm and a mounting height of at least 1085mm (dimensions shown).
Step 3: Connect the luminaire wiring.
Step 4: Assembly (Montage) and Disassembly (Demontage). Disassembly involves a "push" action to release the luminaire.
Technical Data
Current (mA) | Luminous Flux (Im) | Power (W) |
---|---|---|
700 | 3400/3700 | 26/26 |
750 | 3700/4000 | 28/28 |
800 | 3900/4200 | 30/30 |
850 | 4200/4500 | 32/32 |
900 | 4400/4700 | 34/34 |
950 | 4600/5000 | 36/36 |
1000 | 4900/5200 | 37/38 |
1050 | 5100/5500 | 39/40 |
Note: Values for 3000K/4000K (830/840) are shown. 1000 mA is the factory setting.
Disposal
Information for service, cleaning, and disposal of luminaires.
WEEE Disposal: Follow local regulations for electronic waste. (WEEE EAR-NR. 16667402, Interzero Herst.-Nr. 80019)