Stealth 20 Gallon Air Compressor
Product Model # SAQ-12018 | Item # 3332081
Operator's Manual
CAUTION: To Reduce The Risk Of Injury, User Must Read And Understand Operator's Manual. Save These Instructions For Future Reference.
Toll Free Helpline: 1-888-899-0146
Table of Contents
Technical Specifications
PRODUCT NUMBER | 3332081 |
RUNNING HORSEPOWER | 1.8 |
TANK SIZE(TOTAL) | 20 U.S. Gallons(75L) |
AIR DELIVERY(CFM*)@40PSI | 6.0* |
AIR DELIVERY(CFM*)@90PSI | 5.0* |
CUT-IN PRESSURE(PSI) | 120 |
CUT-OUT PRESSURE(PSI) | 150 |
PUMP DESIGN | OIL-FREE |
MOTOR | INDUCTION |
POWER | 120V, 60Hz, 12A |
WEIGHT | 121lbs(55kg) |
POWER CORD | SJT 16 AWG/72"(1.83m) |
*CFM: Cubic Feet per Minute.
*This compressor is rated in accordance with ISO 1217, displacement compressors acceptance tests.
SAVE THESE INSTRUCTIONS
This manual contains important safety and operating instructions. Read all instructions and follow them with use of this product.
Safety Guidelines
Important Safety Information
The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method, or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method, or operating technique that you choose does not render the compressor unsafe.
Safety Symbols and Meanings
- ☠ [Toxic Fumes]
- ⚡ [Electrical Shock]
- ⚠ [Warning]
- 🔥 [Fire]
- 📄 [Operator's Manual]
- 💥 [Bursting]
- 💣 [Flying Objects]
- 🔥 [Hot Surface]
The safety alert symbol indicates a potential hazard to personal injury. A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to designate a degree or level of hazard seriousness. A safety symbol may be used to represent the type of hazard. The signal word NOTICE is used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could result in minor or moderate injury.
Notice address practices not related to personal injury.
Safety Information
⚠ DO NOT OPERATE THIS UNIT UNTIL YOU READ AND UNDERSTAND THIS INSTRUCTION MANUAL FOR SAFETY, OPERATION, AND MAINTENANCE INSTRUCTIONS.
⚠ WARNING
- Risk of fire caused by sparks from motor and pressure switch could result in death or serious injury. Do not operate compressor near flammable gas or vapor. Never store flammable liquids or gases in vicinity of compressor.
- High pressure air could result in death or serious injury.
- Never operate above maximum operating pressure of the spray gun or tool. Drain water from tank after each use. Do not weld or repair tank.
- Do not operate with pressure switch or safety valve set above maximum allowable working pressure.
- Hot compressors surfaces could result in serious injury. Allow compressor to cool before touching.
- Inhalation hazard. Using compressor to supply breathing air could result in death or serious injury. Do not use compressor to supply breathing air.
⚠ WARNING
- Risk of fire could result in death or serious injury.
- Do not spray flammable materials in vicinity of any flame or ignition sources including the compressor unit.
- Do not restrict compressor ventilation openings or place objects against or on top of compressor. Operate compressor only in a clean, dry, well ventilated area.
- Do not operate unattended. Always turn off and unplug unit when not in use.
- Risk of serious eye injury. Always wear ANSI Z87.1 approved safety goggles when using air compressor. Do not spray any part of the body.
⚠ WARNING
- Shock risk could result in death or serious injury. Only connect compressor to a properly grounded receptacle. KEEP CHILDREN AWAY FROM THE AIR COMPRESSOR AT ALL TIMES.
Dust can be created when cutting, sanding, drilling or grinding materials such as wood, paint, metal, concrete, cement, or other masonry. To reduce your exposure to these chemicals, work in a well ventilated area and ALWAYS wear approved safety equipment.
⚠ WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer, birth defects or other reproductive harm. For more information go to https://www.P65Warnings.ca.gov.
Key Parts Diagram
The diagram shows the main components of the air compressor. The labels are as follows:
- A. Electrical Motor
- B. Air Compressor Pump
- C. Safety Valve
- D. ON/OFF Switch
- E. Air Pressure Regulator
- F. Tank Pressure Gauge
- G. Outlet Pressure Gauge
- H. Quick Coupler
- I. Drain Valve
- J. Air Tank
- K. Power Cord
Parts Description
- A. Electric Motor
- The motor is used to power the pump. It is equipped with a thermal overload protector. If the motor overheats for any reason, the thermal overload protector will shut it down in order to prevent the motor from being damaged.
- B. Air Compressor Pump
- The pump compresses the air and discharges it into the tank via the piston that moves up and down in the cylinder.
- C. Safety Valve
- This valve is used to prevent the compressor from building too much pressure. If the pressure reaches the preset level of the motor, it will automatically pop open. You can also pull the ring on the valve to open manually.
- D. ON/OFF Switch
- This switch turns on the compressor and is operated manually. When in the ON position, it allows the compressor to start up or shut down automatically, without warning, upon air demand. ALWAYS set this switch to OFF when the compressor is not being used and before unplugging the compressor.
- E. Air Pressure Regulator
- The regulator is used to adjust the pressure inside the line to the tool that is being used. Turn the knob clockwise to increase the pressure and counter-clockwise to decrease the pressure.
- F. Tank Pressure Gauge
- The gauge measures the pressure level of the air that is stored in the tank. It cannot be adjusted by the operator and it does not indicate the pressure inside the line.
- G. Outlet Pressure Gauge
- The gauge measures the regulated outlet pressure.
- H. Quick Coupler
- The outlet is connected to a quick connector which is connecting to air hose.
- I. Air Tank Drain Valve
- The drain valve is used to remove moisture from the air tank after the compressor is shut off.
- J. Air Tank
- The tank is where the compressed air is stored.
- K. Power Cord
- This product is for use on a nominal 120-volt circuit and should be grounded. A cord with a grounding plug as illustrated must be used. Make sure that the product is connected to an outlet that has the same configuration as the plug (see Figure 1). No adapter should be used with this product. Check with a licensed electrician if the grounding instructions are not understood or there is doubt as to whether the product is properly grounded. Do not modify the plug provided. If it will not fit the outlet, have the proper outlet installed by a licensed electrician.
DANGER Improper installation of the grounding plug will result in a risk of electric shock. If repair or replacement of the cord or plug is necessary, do not connect the grounding wire to either flat blade terminal. The grounding wire is in the green outer surface.
Figure 1: Diagram showing a grounded electrical outlet, a plug with three prongs (hot, neutral, ground), and a grounding pin. The grounding wire is shown connected to the green screw on the outlet and the grounding pin on the plug.
Assembly Instructions
Before assembly, unpack the air compressor unit and inspect it for damage. If damaged, contact the retailer immediately. Check the unit's identification label to ensure it is the intended model and has the required pressure rating.
The carton should contain:
- Air compressor
- Owner's manual
Positioning of the air compressor
- Position the air compressor near an electrical outlet.
- The compressor must be at least 12" (31cm) from any wall or obstruction, in a clean, well-ventilated area to ensure sufficient air flow and cooling. (See Figure A)
- Place the air compressor on the floor or a hard, level surface. The compressor must be level to ensure proper drainage of moisture from the tank.
Figure A: Diagram illustrating the required clearance of 12" (31cm) from a wall.
Connect air hose to compressor
- Connect the air hose to the compressor's air outlet with the quick connector. (See Figure B)
Note: Air hose and quick connector are not provided and need to be purchased separately. Apply plumber's tape on all threads to prevent air leakage.
Figure B: Diagram showing the connection of an air hose to the compressor's air outlet using a quick connector.
⚠ WARNING High pressure air could result in death or serious injury. Never operate above maximum operating pressure of the spray gun or tool.
⚠ WARNING Hot compressor surfaces could result in serious injury. Allow compressor to cool before touching.
Notice If the pump has been transported or turned upside down (even partially), allow the pump to sit in a normal, upright position for approximately 10 minutes before starting.
⚠ WARNING Risk of serious eye injury from moisture and debris. Always wear ANSI Z87.1 safety goggles when opening drain valve.
⚠ WARNING High pressure air could result in death or serious injury. Shut off unit, unplug and release air pressure prior to servicing.
⚠ CAUTION High pressure air containing water condensation could result in minor or moderate injury. Do not spray at any person.
Operating Instructions
Break in the pump
- Set the ON/OFF switch to the OFF position. (See Figure C)
- Open tank drain valve by turning it counter-clockwise to permit air to escape and prevent air pressure build-up in the air tank during the break-in period. (See Figure D)
- Turn the air pressure regulator knob clockwise until it stops. (See Figure E)
Figure C: Illustration of the ON/OFF switch in the OFF position.
Figure D: Illustration of the tank drain valve.
Figure E: Illustration of the air pressure regulator knob.
Plug in the power cord
- Use a dedicated circuit. The compressor will use the full capacity of a typical 15A household circuit. If any other electrical devices are drawing from the compressor's circuit, the air compressor may fail to start or an overload circuit can result in sluggish starting that causes the motor overload protection system or circuit breaker to trip, especially in cold conditions.
- Disconnect the power cord only after the break-in process has been completed, otherwise the motor might get damaged.
- Set the ON/OFF switch to the ON position. The compressor will start. Run the compressor for 30 minutes. If it fails, turn it off immediately and call the toll-free helpline at: 1-888-899-0146. Please note that breaking-in the unit is only required prior to first use. (See Figure F)
- After 30 minutes, turn off the ON/OFF switch.
- Close the tank drain valve by turning it clockwise. (See Figure G)
- Set the ON/OFF switch to the ON position. The air receiver will fill to "cut-out" pressure and then the compressor's motor will stop. The compressor is now ready for use.
Figure F: Illustration of the ON/OFF switch in the ON position.
Figure G: Illustration of the tank drain valve.
Before each start-up
- Set the ON/OFF switch to the OFF position. (See Figure H)
- Turn the air pressure regulator knob counter-clockwise until it stops. (See Figure I)
- Attach hose and accessories. (Hose and accessories need to be purchased separately.) (See Figure J)
Figure H: Illustration of the ON/OFF switch in the OFF position.
Figure I: Illustration of the air pressure regulator knob.
Figure J: Diagram showing hose and accessories connection.
How to start
- Close the tank drain valve. (See Figure K)
- Plug-in the power cord. (See Figure H)
- Set the ON/OFF switch to the ON position and allow the tank pressure to build. Motor will stop when tank pressure reaches cut-out pressure.
- Turn the air pressure regulator knob clockwise until desired pressure is reached.
- The compressor is ready for use.
Figure K: Illustration of the tank drain valve.
How to shut down
- Set the ON/OFF switch to the OFF position.
- Unplug the power cord.
- Reduce the pressure in the tank through the outlet hose. Pulling the safety valve ring and keeping it open will also reduce the pressure in the tank. (See Figure L)
- Set the tank drain valve to ON to ensure tank is drained.
Figure L: Illustration showing how to pull the safety valve ring to release pressure.
Maintenance
ITEM | DESCRIPTION / REASON | SERVICE INTERVAL |
---|---|---|
Drain the tank | Through normal operation of your air compressor, condensation of water will accumulate in the tank. To prevent corrosion of the tank from the inside, condensation must be drained at the end of every workday. Be sure to wear protective goggles. Relieve the air pressure in the system then open the drain valve on the bottom of the tank to drain. Under cold conditions it is especially important to drain the tank after each use to reduce the chance of problems resulting from the freezing of condensation water. NOTE: Refer to instructions on how to drain tank (page 11). | Daily |
Check the valve | Pull the safety valve daily to ensure that it is operating properly and to clear the valve of any possible obstructions. | Daily |
Test for leaks | Check that all connections are tight. Small leaks in the tank, hoses, connections or transfer tubes will substantially reduce the air compressor and tool performance. Spray a small amount of soapy water around the area of suspected leaks with a spray bottle. If bubbles appear, repair, replace or reseal the faulty component. Do not over-tighten any connections. | Monthly |
Clean the air filter | A dirty air filter will reduce air compressor performance and life. To avoid contaminating the pump, the filter should be cleaned frequently and replaced on a regular basis. Clean the cartridge filter by blowing on it with a blow gun (page 11). | Weekly |
Storage | Before storing the air compressor:
|
Prior to storing |
Check Safety Valve
Before starting the compressor, pull the ring on the safety valve to make sure that the safety valve operates freely. If the valve is stuck or does not operate smoothly, contact a trained service technician.
How To Drain Tank
- Set the ON/OFF switch to the O (OFF) position.
- Unplug the power cord.
- Turn air pressure regulator knob counter-clockwise to set the outlet pressure to zero.
- Pull and hold ring on safety valve, allowing air to bleed from the tank until air pressure is minimized.
- Place suitable container under unit to catch water.
- Slightly tilt unit and turn drain valve counter-clockwise to open.
- After the water has been drained, close the drain valve (clockwise). The air compressor can now be stored.
How to Clean The Air Filter
A dirty filter will reduce the unit's performance and life. To avoid any contamination inside the pump, the filter should be cleaned weekly and replaced on a regular basis. The cartridge filter should be cleaned with blow gun.
Troubleshooting
PROBLEM | POSSIBLE CAUSE | SOLUTIONS |
---|---|---|
The motor will not run or start | The power cord is not plugged in. | Plug the power cord into a grounded outlet. |
The on/off switch is in the O (OFF) position. | Set the on/off switch to the ON position. | |
The extension cord is the wrong wire gauge or is too long. | Check extension cord information (page 7) for the proper wire gauge and cord length. | |
The motor's thermal overload protection has tripped. | Turn the air compressor off, unplug the power cord and wait until the motor has cooled down. Plug in the power cord only after the motor has cooled down, and wait at least 5 minutes to make sure the thermal overload protector has recovered. | |
A fuse has blown or a circuit breaker has been tripped. | Replace the fuse or reset the circuit breaker. Verify that the fuse has the proper amperage. Check for low voltage conditions. | |
The motor runs continuously when the ON/OFF switch is in the ON position. | The air tank pressure exceeds the preset pressure switch limit. | The motor will start automatically when the tank pressure drops below the cut-in pressure. |
The safety valve is stuck open. | Clean or replace the safety valve. | |
Electrical connections are loose. | Contact an authorized service center, or call 1-888-899-0146. | |
The motor, capacitor or safety valve is defective. | Contact an authorized service center, or call 1-888-899-0146. | |
The ON/OFF switch does not shut off the motor when the air compressor reaches the cut-out pressure and the safety valve activates. | Set the ON/OFF switch to the OFF position. If the motor does not shut off, unplug the air compressor. If the pressure switch is defective, replace it. | |
The compressor's capacity is not enough. | Check the air requirements of the accessory that is being used. If it is higher than the CFM (Cubic Feet per Minute) and pressure supplied by the compressor (page 18), a larger capacity air compressor is needed. Most accessories are rated at 25% of actual CFM while running continuously. | |
The regulator does not regulate the pressure. | The regulator or its internal parts are dirty or damaged. | Replace the regulator. |
The pressure is low or there is not enough air. | There is a leak at one of the fittings. | Check the fittings with soapy water. Tighten or reseal leaking fittings (apply plumber's tape on threads). Do not over tighten. |
The tank drain valve is open. | Close the drain valve. | |
The air intake is restricted. | Clean or replace the air filter element. | |
Prolonged excessive use of air. | Decrease the amount of air used. | |
There is a hole in the air hose. | Check the air hose and replace it if necessary. | |
The tank leaks. | Replace the tank immediately. Do not attempt to repair it. | |
The valve is leaking. | Check for worn parts and replace them if necessary. | |
There is moisture in the discharge air. | There is condensation in the air tank caused by a high level of atmospheric humidity or because the air compressor has not been running long enough. | Drain the air tank after each use. Drain the air tank more often in humid weather and use an air-line filter. |
The ventilation is inadequate. | Relocate the compressor to an area with cool, dry and well-circulated air. | |
Cooling surfaces are dirty. | Clean all cooling surfaces on the pump and the motor thoroughly. | |
The compressor overheats. | The valve is leaking. | Replace worn parts and reassemble using new plumber's tape. |
Exploded View
The exploded view diagram shows all the components of the air compressor disassembled. The parts are numbered for reference in the Parts List.
(Note: A visual representation of the exploded view cannot be provided here. The following is a list of the numbered parts as indicated in the diagram.)
- 1. Handgrip
- 2. Rubber Hose
- 3. Pressure Gauge
- 4. Pressure Regulator
- 5. Screw M5x12
- 6. Quick Coupler
- 7. Pressure Regulator Knob
- 8. Screw M4x10
- 9. Control Panel
- 10. Flange Nut M5
- 11. Aluminum Tube
- 12. Check Valve
- 13. Pressure Switch
- 14. End Cap
- 15. Power Cord
- 16. Safety Valve
- 17. O-Ring
- 18. Metal Tube
- 19. Elbow Fitting
- 20. Retainer
- 21. Self-Tapping Screw ST3.9x16F
- 22. Pump Cover
- 23. Motor Pump Assembly
- 24. Air Filter
- 25. Capacitor Shroud
- 26. Capacitance Plug
- 27. Capacitor
- 28. Crimp Cap
- 29. Cushion Pad
- 30. Mount Plate
- 31. Screw M4x12
- 32. Cord Clamp
- 33. Flange Nut M8
- 34. Screw M8x40
- 35. Bonnet
- 36. Wheel
- 37. Flange Nut M10
- 38. Washer Ø10
- 39. Rubber Foot
- 40. Bolt M10x25
- 41. Drain Valve
- 42. Tank
Parts List
No. | Description | Qty. | No. | Description | Qty. |
---|---|---|---|---|---|
01 | Handgrip | 1 | 23 | Motor Pump Assembly | 1 |
02 | Rubber Hose | 1 | 24 | Air Filter | 2 |
03 | Pressure Gauge | 2 | 25 | Capacitor Shroud | 1 |
04 | Pressure Regulator | 1 | 26 | Capacitance Plug | 1 |
05 | Screw M5x12 | 9 | 27 | Capacitor | 1 |
06 | Quick Coupler | 2 | 28 | Crimp Cap | 2 |
07 | Pressure Regulator Knob | 1 | 29 | Cushion Pad | 4 |
08 | Screw M4x10 | 1 | 30 | Mount Plate | 1 |
09 | Control Panel | 1 | 31 | Screw M4x12 | 2 |
10 | Flange Nut M5 | 7 | 32 | Cord Clamp | 1 |
11 | Aluminum Tube | 1 | 33 | Flange Nut M8 | 8 |
12 | Check Valve | 1 | 34 | Screw M8x40 | 4 |
13 | Pressure Switch | 1 | 35 | Bonnet | 2 |
14 | End Cap | 1 | 36 | Wheel | 2 |
15 | Power Cord | 1 | 37 | Flange Nut M10 | 2 |
16 | Safety Valve | 1 | 38 | Washer Ø10 | 2 |
17 | O-Ring | 2 | 39 | Rubber Foot | 2 |
18 | Metal Tube | 1 | 40 | Bolt M10x25 | 2 |
19 | Elbow Fitting | 1 | 41 | Drain Valve | 1 |
20 | Retainer | 1 | 42 | Tank | 1 |
21 | Self-Tapping Screw ST3.9x16F | 2 | |||
22 | Pump Cover | 1 |
Warranty
LIMITED LIFETIME WARRANTY
This warranty covers any defects in materials or workmanship of the enclosed product. Alton Industry Ltd. Group will repair or replace any defective materials due to craftsmanship of the product. This warranty does not cover any problem caused by misuse, abuse, accidents or acts of God, such as floods or hurricanes. Consequential and incidental damages are not covered under this warranty. Coverage terminates if you sell or otherwise transfer the ownership. If you feel you have a defective product, please submit a copy of your receipt to the address below and call 1-888-899-0146 for instructions prior returning this item to the store or sending back to:
Alton Industry Ltd. Group
1031 North Raddant Rd
Batavia, Illinois 60510
We will inspect the product and contact you within 72 hours to give you the results of our inspection. We reserve the right to repair or replace the product at our discretion. However, we may replace the product with one of similar but not exact features.
Parts and Service Information available call Alton Industry at 1-888-899-0146.
This warranty gives you specific legal rights. You may have other rights which vary from state to state.
Register online at: https://www.StealthCompressors.com/Register
SAVE YOUR RECEIPTS
THIS WARRANTY IS VOID WITHOUT THEM