As of February 2023, Reclaim Energy launched the next generation of heat pump with substantial improvements. Unless specified below, all other parameters/specifications are the same between V1 and V2 models. The key changes are summarised in Table A and Table B.
Status | V1 (Discontinued from 2023) | V2 (Available from 2023) |
---|---|---|
Model Name | EHPE-4540P | EHPE-4550P-A |
Max rated power input (kW) | 2.3 | 2.5 |
Compressing volume (cm³) | 3.80 | 4.5 |
Refrigeration Capacity (W) | 3470 | 4900 |
Communications with the controller | RJ45 cable | Modbus |
Connectivity to controllers | V1 & V1.1 models ONLY | V1, V1.1, V2 models |
Figure A: Images of three controllers: V1 (Discontinued) with a green display and buttons; V1.1 with a white display and buttons; V2 with a white display and touch-sensitive buttons.
Status | V1 (Discontinued from 2023) | V1.1 (Available from February 2023) | V2 (Soft Launch from April 2023) |
---|---|---|---|
Connectivity to heat pump | RJ45 cable | RJ45 cable | Modbus |
Connectivity to PV inverters and home management systems | Not available | Not available | Dry Contact |
Connectivity to Reclaim Mobile app using house Wi-Fi | Not available | Available | Available |
Option 1 | 24/7 time-block | 24/7 time-block | 24/7 time-block |
Option 2 | 10 pm - 7 am | 10 pm - 7 am | 10 pm - 7 am |
Option 3 | Midnight - 6 am | Midnight - 6 am | Midnight - 6 am |
Option 4 | 10 am - 4 pm | 10 am - 4 pm | 10 am - 4 pm |
Option 5 | Two time-blocks - first must be set for a minimum of 6 hours and second can be set as little as 0 hours! | Two time-blocks - first must be set for a minimum of 3 hours and second can be set as little as 0 hours! | Two time-blocks - first must be set for a minimum of 3 hours and second can be set as little as 0 hours! Additionally, the turn on temperature can be adjusted for the second time block (i.e., default is 37°C) |
Option 6 | N/A | N/A | Two time-blocks - first must set for a minimum of 3 hours and second can be set for as little as 0 hours! Additionally, both turn on and turn off temperatures can be adjusted for the second time block (i.e. default is 37°C & 59°C respectively). |
Option 7 | One shot boost is activated by a dry contact signal from home management or PV inverters or dry contact smart switches. This is called "Remote" option. | Remote Control - one shot boost is activated by a dry contact/Modbus signal from home management or PV inverters or dry contact smart switches. Additionally, a time clock should be adjusted for when the signal is not received by the controller in the 18-hour cycle (i.e. this is to ensure any legionella bacterial growth is controlled in a 24-hour cycle). | Remote Control - one shot boost is activated by a dry contact/Modbus signal from home management or PV inverters or dry contact smart switches. Additionally, a time clock should be adjusted for when the signal is not received by the controller in the 18-hour cycle (i.e. this is to ensure any legionella bacterial growth is controlled in a 24-hour cycle). |
Option 8 | N/A | N/A | Holiday Mode - this option is recommended if the hot water user does not require hot water at least 7 days per week. A day and time of the week is to be selected; the heat pump will start at the specified day/time ONCE per week to meet legionella requirements by AS 3498. As per the normal operation of the heat pump, there may be additional cycles over winter for the anti-freeze function operation. (i.e. heating of the water if water in the pipes drops below approximately 3°C). |
Boost function | Available | Available | Available |
Manual Boost function | Available / Website | Available / Website | Available / Website |
Manuals | Website | Website | Website |
Figure B: Image showing a V2 controller and a smartphone displaying the Reclaim Energy mobile app interface. The app shows Wi-Fi connection status, device information, and settings like automatically setting time.
Connection to Wi-Fi and the mobile app is OPTIONAL for the end user. Full functionality of the controller can be used manually or via the FREE Reclaim Energy app, available for iOS & Android mobile phones.
The V2 system model numbers are different from previously supplied models. The following codes must be used for rebate applications such as STC, ESC, and VEECs. There has been a slight improvement of about 1-3 STCs for different model IDs between V1 and V2 models.
The latest up-to-date values should be checked at:
Item | Tank Model ID | Heat Pump Model ID (V2) | System Model Number (V2) | Heat Pump Model ID (V1) | System Model Number (V1) |
---|---|---|---|---|---|
1 | RE160AGLH | REHP-C02-160GL-V2 | REHP-C02-160GL | REHP-C02-160GL | |
2 | APS160TH | REHP-C02-160SST-V2 | REHP-C02-160SST | REHP-C02-160SST | |
3 | RE250AGLH | REHP-C02-250GL-V2 | REHP-C02-250GL | REHP-C02-250GL | |
4 | EWA-250HPT | REHP-C02-250SSEW-V2 | REHP-C02-250SSEW | REHP-C02-250SSEW | |
5 | APS250TH | REHP-C02-250SST-V2 | REHP-C02-250SST | REHP-C02-250SST | |
6 | TS300-O-E24-S2 | REHP-C02-300H-V2 | REHP-C02-300H | REHP-C02-300H | |
7 | RE315AGLH | REHP-C02-315GL-V2 | REHP-C02-315GL | REHP-C02-315GL | |
8 | EWA-315HPT | REHP-C02-315SSEW-V2 | REHP-C02-315SSEW | REHP-C02-315SSEW | |
9 | APS315SH | REHP-C02-315SSQ-V2 | REHP-C02-315SSQ | REHP-C02-315SSQ | |
10 | APS315TH | REHP-C02-315SST-V2 | REHP-C02-315SST | REHP-C02-315SST | |
11 | RE400AGLH | REHP-C02-400GL-V2 | REHP-C02-400GL | REHP-C02-400GL | |
12 | APS400TH | REHP-C02-400SST-V2 | REHP-C02-400SST | REHP-C02-400SST |
The V2 heat pump's default mode is with the V1.1 controller. If a V1.1 controller is received, it can be connected directly to the RJ45 port on the heat pump's PCB display, and the general commissioning process can be followed.
If a V2 controller is received, the following steps on the heat pump are required before the V2 controller can be used:
Diagram: Illustrates how to attach/detach the piping cover using screws and tabs. Shows the heat pump power terminal and the PCB display where the RJ45 cable connects.
The smart top-down heat return system provides 50L of hot water within 20 minutes and a full tank in about 3 hours. After 15 minutes, touch the heat pump return connection to the tank; it should be hot to the touch, indicating successful installation.
Diagram: Shows the heat pump unit with labels pointing to the "Drain Plug" and "Drain Elbow".
Diagram: Shows a schematic of the heat pump unit and its connections, including the water heat exchanger, evaporator, and various ports. It also indicates the V1.1 and V2 controller connections (RJ45 and Modbus cables respectively) and the temperature sensor. A note mentions a swing check valve is recommended if the heat pump is installed more than 1m above the tank to prevent backflow.
This section provides a brief overview of the Air-Source CO2 Hot Water Pump's main components and functionality.
The system components include:
The CO2 heat pump unit draws cold water from the bottom of the tank. Using ambient air heat, it heats the CO2 refrigerant to produce hot water. The hot water (fixed at 63°C) returns to the top of the tank, ensuring fast recovery and good stratification. As the water exceeds 50°C, a tempering valve is required for delivery to bathrooms. Untempered water is permitted for kitchens and laundries per AU/NZS AS 3500 plumbing code.
The controller manages the heat pump based on a tank sensor (55-69% level). The heat pump activates if the tank temperature drops below 59°C (first cycle) or 37°C (second cycle) and runs until it reaches 59°C. System controls meet legionella requirements per Australian standards. The heat pump runs until the sensor level reaches 59°C. The turn-off logic for subsequent heating cycles is adjustable via built-in timer settings. The default setting is continuous operation, but installers can adjust it based on homeowner needs.
At ambient temperatures below 5.5°C, frosting may occur. The heat pump enters defrost mode to protect the unit, running for no more than 15 minutes. During defrost, the pump and fan stop, and refrigerant heat melts ice on the evaporator (air-CO2 heat exchanger). The evaporator temperature increases as defrost progresses.
Once a set temperature is achieved, defrost stops, and the heat pump resumes normal operation. Details are in Section 6.
The "operational window" refers to the heat pump's hot water production mode. In cold climates, operation may be extended by anti-freeze or defrost modes. The defrost cycle occurs during the operational window to clear ice from the evaporator when ambient temperature is below approximately 5°C. The frost cycle lasts about 5 minutes and can repeat, totaling up to 20 minutes. The anti-freeze cycle operates outside the operational window to protect the water circuit from freezing. If ambient and pipe temperatures drop below 3°C, the anti-freeze cycle begins. During this cycle, the heat pump operates normally (fan and pump running). It stops when water inlet temperature reaches 56°C or ambient temperature reaches 6°C.
This section covers the preparation and installation process for the Reclaim Air-Source CO2 Heat Pump system.
Installation must be performed by a licensed plumber or electrician according to local standards and regulations. Key standards include:
Installers must adhere to occupational health and safety guidelines. Thoroughly read and understand this manual before installation. For queries, contact Reclaim Energy staff at 1300 38 38 15.
This system is designed for domestic hot water applications only; other uses will void the warranty.
Recommended installation sequence:
Site Preparation Recommendations:
Figure 1: Shows concrete or heavy-duty plastic slabs for under the storage tank.
Figure 2: Required space for heat pump installation. Shows dimensions A (clearance in front), B (clearance on sides), and C (clearance at back). Note 1: PCB must be accessible. Note 2: Installation next to AC unit is approved if exhausts don't interfere.
Reclaim Energy ASHP units MUST be installed on the ground using supplied mounting frames OR on the wall with brackets. A plumber needs access underneath for servicing and purge protocols.
Figure 4: Shows ground mounting frames. Figure 5: Shows wall mounting brackets. Figure 6: Shows a heat pump drain elbow plug supplied with the unit.
A drain plug is supplied in the heat pump unit's packaging. Safely connect the drain elbow and guide the drain hose to a ditch if required.
Figure 7: Illustrates how to attach the drain elbow to the bottom panel of the heat pump, connecting to the drain hose.
Removal: 1. Remove the screw. 2. Slide the piping cover downwards.
Attachment: 1. Fit the piping cover by aligning 5 tabs. 2. Slide the cover upward and secure with the screw.
Figure 8: Shows the process of removing and attaching the piping cover, indicating screw and tab locations.
After removing the right-side piping cover, the heat pump's cold (inlet) and hot (outlet) pipes are accessible.
Figure 9: Plumbing diagram of the Reclaim Energy ASHP hot water system. Shows connections between the Heat Pump Unit, Storage Tank, PTRV, Thermistor, and LOAD. Includes pressure ratings (PLV, ECV, PTRV) and notes on distance limits, bends, valves, and sensors.
NOTE:
A licensed electrician must install the system according to the wiring diagram (Figure 10) and local/national codes. The power cord must comply with AS/NZS 3191, with a nominal cross-sectional area of 1.5 mm² or more.
The heat pump requires its own circuit (15 A) and must be hard-wired to a 15 A ISOLATOR SWITCH. The controller has its own plug and requires a separate power point, which can be fed from the heat pump circuit.
Figure 10: Wiring diagram of the Reclaim Energy ASHP hot water system. Shows connections between the Heat Pump Unit, Controller, Storage Tank, and power supply via a 15A AC isolator switch. Includes labels for temperature sensor cable, RJ45 cable (V1.1), and Modbus cable (V2).
The communication protocol differs between V1.1 and V2 controllers:
Images show V1.1 controller connecting to the RJ45 terminal on the PCB display, and V2 controller connecting to the Modbus terminal block. Instructions for wiring Modbus cables are provided.
Regardless of controller version, installers must ensure:
A licensed installer should check the following before leaving the installation site:
General:
Heat Pump:
Tank:
Piping/Wiring:
Controller:
End users should check that the heat pump operation matches the selected options at least monthly. If the heat pump operates outside these settings, escalate to a local service agent or Reclaim Energy representative. Potential causes for deviation include: loose tank sensor, winter freeze/frost protection cycles, or accidental activation of Boost function.
Check the heat pump's drain tray for blockages at least annually. Ensure the surrounding area is clear of plant growth to allow for natural ventilation.
If the heat pump or controller encounters an issue, an error code will be generated. Each error code on the controller corresponds to a label on the heat pump PCB display. If a controller error appears but not on the PCB, it may indicate a damaged or faulty communication cable.
The following tables summarize error codes and troubleshooting steps:
Error Codes | Remote Control | PCB | Appearance, Portion, Parts Seemed Wrong | Method of Check | Troubleshooting | Error Reset |
---|---|---|---|---|---|---|
H9 | PCB(Main) | Outdoor temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
HC | PCB(Main) | Outgoing water temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
J3 | PCB(Main) | Discharge temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
J5 | PCB(Main) | Suction temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
J6 | PCB(Main) | Defrost temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
J8 | PCB(Main) | Return water temp. sensor error | Check resistance value. | Sensor replacement if broken. PCB replacement if needed. | Auto | |
E6 | Start-up failure of compressor | PCB or HP unit | Compressor connector | Check connection. Restart HP unit. | Replace PCB or HP unit if problem persists. | Power OFF |
H6 | Abnormal revolution of compressor | PCB or HP unit | Drop of power voltage, Heating water circulation circuit, Heating pump error, Expansion valve coil | Check power voltage. Check for water flow blockages. Check sensor resistance. Check pump operation. Check valve coil. | Replace PCB or HP unit if problem persists. Replace sensor, pump, or valve coil as needed. | Power OFF |
U0 | Stop by detecting gas leakage | PCB (Main) or HP unit | Discharge temp. sensor, Expansion valve coil | Check resistance value. Check disconnection/short circuit. | Replace sensor or valve coil. Replace PCB or HP unit if problem persists. | Power OFF |
E1 | PCB failure | PCB | Drop of power voltage, Installation condition | Check power voltage. Check installation condition (e.g., blocked air inlet). | Replace PCB or HP unit if problem persists. Adjust installation if needed. | Power OFF |
E8 | Stop by detecting input overcurrent | PCB (Main) or HP unit | Heating pump error, Expansion valve coil | Check pump operation. Check valve coil. | Replace pump or valve coil. Replace PCB or HP unit if problem persists. | Power OFF |
Error Codes | Remote Control | PCB | Appearance, Portion, Parts Seemed Wrong | Method of Check | Troubleshooting | Error Reset |
---|---|---|---|---|---|---|
H8 | PCB(Main) | Current detection error | Reset power supply. | Replace PCB if problem persists. | Power OFF | |
L4 | PCB(Main) | Module temperature error (90°C or higher) | Check fin condition. | Restart HP unit after checking. | Power OFF | |
L5 | PCB(Main) | Detecting output overcurrent | Check for foreign substances blocking fan motor. | Replace fan motor if needed. | Power OFF | |
P4 | PCB(Main) | Module sensor error | Reset power supply. | Replace PCB if problem persists. | Auto | |
U2 | Power voltage error | PCB(Main) | Drop of power voltage | Check power voltage. Reset power supply. | Replace PCB if problem persists. | Power OFF |
HJ | Water Circulation system failure | Each sensor | Heating water circulation circuit | Check for water flow blockages. Check sensor resistance. | Replace sensor or PCB/HP unit if needed. | Power OFF |
EC | Stop by outgoing water temperature error | PCB (Main) or HP unit | Outgoing water temp. sensor, Heating pump, Expansion valve coil | Check sensor resistance. Check pump operation. Check valve coil. | Replace sensor, pump, or valve coil. Replace PCB or HP unit if problem persists. | Power OFF |
E9 | Heating pump error | PCB(Main) | Heating pump error | Check pump rotation on PCB display. | Replace heating pump or PCB/HP unit as needed. | Power OFF |
E7 | Outdoor fan lock | PCB(Main) | Fan motor | Check for fan motor clogging or connector issues. | Improve cause. Replace fan motor if needed. | Power OFF |
F3 | Stop by Discharge temperature error | PCB (Main) or HP unit | Discharge temp. sensor, Expansion valve coil | Check sensor resistance. Check valve coil. | Replace sensor or valve coil. Replace PCB or HP unit if problem persists. | Power OFF |
Eg-8 | No detection of tank sensor | Tank sensor | Tank sensor | Contact Reclaim Energy Support. | Improve cause, then restart HP unit. | Auto |
Eg-9 | Tank sensor failure | Tank sensor | Tank sensor | Contact Reclaim Energy Support. | Replace sensor. | Auto |
Error Codes | Remote Control | PCB | Appearance, Portion, Parts Seemed Wrong | Method of Check | Troubleshooting | Error Reset |
---|---|---|---|---|---|---|
Eg-10 | Loose tank sensor issue | Check if probe is fully inserted. Contact Reclaim Energy Support. | Push sensor fully in. Check controller/sensor. Contact Support. | Auto | ||
Eg-11 | Modbus sensor | Contact Reclaim Energy Support. | Fix or replace Modbus cable or V2 controller. Contact Support. | Auto | ||
Eg-20 - 23 | Wi-Fi errors | V2 controller Wi-Fi connection issue. Contact Reclaim Energy Support. | Wi-Fi connection issue may be due to poor network. Disable Wi-Fi and use controller manually. Contact Support. | Auto |
The system requires a PTRV for pressure release (max 850kPa). It must have a downward copper pipe to a safe drainage location. The PTRV may discharge small amounts of water (1L per 50L heated). If installed indoors, a safe tray is mandatory. Check the PTRV every 6 months by lifting the lever; water should discharge. Operate the manual relief every 6 months to clear deposits.
The sacrificial anode in glass-lined tanks protects the vitreous enamel for approximately five years. It should be replaced as part of an annual service thereafter. Water supplies with high Total Dissolved Solids (TDS) (>600mg/L or <40mg/L) may require a different anode. Warranty is void if TDS exceeds 2500 mg/L. Check the tank anode initially after 5 years, then every 3 years.
The Magnesium anode can release small quantities of hydrogen gas, usually dissolved and flushed away. If the water heater is unused for two or more weeks, or water appears milky, hydrogen build-up may occur. To resolve this, "purge" the tank for approximately 30 seconds using the PTRV lever. Stand clear of the discharge piping.
Drainage is only required if the system is left without power or for holidays/maintenance. Follow these steps:
![]() |
Reclaim Energy Air-Source CO2 Heat Pump Quick Start/Install Manual This manual provides quick start and installation instructions for the Reclaim Energy Air-Source CO2 Heat Pump Hot Water System, covering system description, installation details, operation, and maintenance. |
![]() |
Reclaim Energy V2 Release Quick Start/Install Manual for Air-Source CO2 Heat Pump Hot Water System This document provides a quick start and installation guide for the Reclaim Energy V2 Air-Source CO2 Heat Pump Hot Water System. It details product updates, system components, installation procedures, operational guidelines, and troubleshooting steps. |
![]() |
Reclaim Energy Heat Pump Hot Water System Warranty Terms and Conditions Detailed warranty terms and conditions for Reclaim Energy's Air-Source CO2 Heat Pump Hot Water Systems, covering product registration, claim procedures, and component coverage. |
![]() |
Reclaim Energy CO2 Heat Pump Hot Water System: Quick Start/Install Manual Comprehensive quick start and installation manual for the Reclaim Energy CO2 Heat Pump Hot Water System, covering model numbers REHP-KY-CO2-160GL through REHP-KY-CO2-315DX and HE-UM60AR. Includes system overview, installation procedures, safety warnings, and maintenance checks. |
![]() |
Reclaim Energy Duplex Tank Specifications: 315L CO2 Heat Pump Hot Water System Detailed specifications for the Reclaim Energy 315L Duplex Stainless Steel CO2 Heat Pump Hot Water System, including dimensions, technical data, features, and contact information. Learn about its efficient, reliable, and Australian-designed performance. |
![]() |
Reclaim Energy Heat Pump Controller V2 Manual Comprehensive manual for the Reclaim Energy Heat Pump Controller V2, covering product updates, installation, operation, commissioning, setup procedures, Wi-Fi connectivity, mobile app usage, status display, fault diagnosis, and cable extension. |
![]() |
Reclaim Energy Commercial CO2 Heat Pump Hot Water System Tank Specifications Detailed specifications for Reclaim Energy's Commercial CO2 Heat Pump Hot Water Systems with Stainless Steel Tanks, including dimensions, product codes, tank capacities, and materials. |
![]() |
Reclaim Energy Heat Pump Controller V1.1 Manual: Installation, Operation, and Maintenance This manual provides comprehensive guidance for the Reclaim Energy Heat Pump Controller V1.1, covering installation procedures, operational modes, user access, troubleshooting fault codes, and technical specifications for optimal heat pump performance. |