American Standard
HEATING & AIR CONDITIONING
Specification
Variable Speed AccuLink™ Air Conditioner
Model: 4A7V8036A1000A
⚠ SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Date: September 2013
Document ID: 4A7V8036A-SPEC-1
Manufacturer: Ingersoll Rand
Unit Diagrams and Dimensions
Figure 1: Unit Layout and Dimensions
This diagram illustrates the overall unit dimensions and key features. It shows the top discharge area clearance requirement (unrestricted for at least 1524 mm / 5 feet above the unit). The unit placement should prevent roof run-off water from directly hitting it and maintain at least 305 mm (12 inches) clearance from walls and shrubbery on two sides, with the other two sides unrestricted. It indicates service valves for gas line (Type D, 1/4 turn ball, female brazed connection with 1/4" SAE flare pressure tap fitting) and liquid line (Type E, female brazed connection with 1/4" SAE flare pressure tap fitting). Electrical service panel access and low voltage/power supply knockouts (K.O.) are also shown.
Figure 2 & 3: Service Valve and Clearance Details
These figures provide detailed views of the liquid line service valve (Type E, I.D. female brazed connection with 1/4" SAE flare pressure tap fitting) and gas line service valve (Type D, I.D. female brazed connection with 1/4" SAE flare pressure tap fitting). They also illustrate electrical and refrigerant component clearances required by prevailing codes.
Dimensional Data
Model | Base | A | B | C | D | E | F | G | H | J | K |
---|---|---|---|---|---|---|---|---|---|---|---|
4A7V8036A | 3 | 1035 (40-3/4) | 829 (32-5/8) | 756 (29-3/4) | 19-3/4 | 10-3/8 | 127 (5) | 76 (3) | 197 (7-3/4) | 57 (2-1/4) | 813 (32) |
Sound Power Level Data
Sound Power Level
Model | Mode | Speed | A-Weighted Sound Power Level [dB(A)] | Full Octave Sound Power [dB] | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
63 Hz | 125 Hz | 250 Hz | 500 Hz | 1000 Hz | 2000 Hz | 4000 Hz | 8000 Hz | ||||
4A7V8036A | Cool | Min | 55 | 71.0 | 53.4 | 51.2 | 53.5 | 51.5 | 44.6 | 40.3 | 41.0 |
4A7V8036A | Cool | Max | 70 | 73.1 | 70.5 | 65.8 | 67.3 | 66.0 | 60.9 | 54.1 | 50.0 |
Note: Rated in accordance with AHRI Standard 270-2008.
Mechanical Specifications
Outdoor Unit Specifications (Model: 4A7V8036A1000A)
OUTDOOR UNIT | 4A7V8036A1000A |
POWER CONNS. -- V/PH/HZ | 208/230/1/60 |
MIN. BRCH. CIR. AMPACITY | 18.0 |
BR. CIR. PROT. RTG. -- MAX. (AMPS) | 25 |
COMPRESSOR | SCROLL |
NO. USED -- NO. SPEEDS | 1 -- VARIABLE |
R.L. AMPS -- L.R. AMPS | 12.4 -- 10.2 |
FACTORY INSTALLED START COMPONENTS | NA |
INSULATION/SOUND BLANKET | YES |
COMPRESSOR HEAT | YES |
OUTDOOR FAN DIA. (IN.) -- NO. USED | 23 -- 1 |
TYPE DRIVE -- NO. SPEEDS | DIRECT -- VARIABLE |
CFM @ 0.0 IN. W.G. | 2850 |
NO. MOTORS -- HP | 1 -- 1/3 |
MOTOR SPEED R.P.M. | 200 -- 1200 |
VOLTS/PH/HZ | 208/230/1/60 |
F.L. AMPS | 2.8 |
OUTDOOR COIL -- TYPE | SPINE FINTM |
ROWS -- F.P.I. | 1 -- 24 |
FACE AREA (SQ. FT.) | 23.75 |
TUBE SIZE (IN.) | 3/8 |
REFRIGERANT LBS. -- R-410A (O.D. UNIT) | R410A, 7 lb -- 14 oz |
FACTORY SUPPLIED | YES |
LINE SIZE -- IN. O.D. GAS | 3/4 |
LINE SIZE -- IN. O.D. LIQ. | 3/8 |
CHARGING SPECIFICATIONS SUBCOOLING | 10° |
DIMENSIONS HXWXD | 46 X 30.1 X 33 |
CRATED (IN.) | 46 X 30.1 X 33 |
WEIGHT SHIPPING (LBS.) | 228 |
WEIGHT NET (LBS.) | 207 |
Mechanical Specification Options
General
The Outdoor Units are charged from the factory for matched indoor section and up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures from 55° F to 120° F in cooling and from -10° F to 66° F in heating. Only AHRI approved indoor matches are approved for use with these models.
AccuLink™
This outdoor unit contains the AccuLink™ digital communication with 2 wire connection to outdoor and Plug-n-Play setup.
Casing
Unit casing is constructed of heavy gauge G60 galvanized steel and painted with a weather-resistant powder paint on all louvers, panels, and prepaint on all other panels. Features a Corrosion and weatherproof CMBP-G30 DuraBase™ base.
Refrigerant Controls
Refrigeration system controls include condenser fan, compressor contactor, and high and low pressure switches. A factory supplied, field installed filter is standard.
Compressor
Inverter driven scroll compressor with 25 to 100% output capacity on heat pumps and 30 to 100% output capacity on air conditioners. Noise enclosure minimizes sound levels, and built-in compressor protection reduces operating speed and current draw to maintain operation while protecting the compressor.
Condenser Coil
The Spine Fin™ outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.
Low Ambient Cooling
As manufactured, this system has built-in freeze protection that allows cooling operation below 55°F but will reduce capacity or shut down completely to prevent operation under adverse conditions.
Comfort Control
The 950/850 Control is required and provides Plug-n-Play setup and 3 wire connection.
Notes and Certifications
Explanations of Specification Notations:
- (a) Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on AHRI standard 210/240.
- (b) Rated in accordance with AHRI standard 270.
- (c) Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses.
- (d) This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current.
- (e) No means no start components. Yes means quick start kit components. PTC means positive temperature coefficient starter.
- (f) Standard Air -- Dry Coil -- Outdoor
- (g) This value approximate. For more precise value see unit nameplate.
- (h) Max. linear length 150 ft.; Max. lift -- Suction 50 ft.; Max. lift -- Liquid 50 ft.
Company Information and Certifications:
American Standard optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, American Standard offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.americanstandardair.com.
American Standard has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2013 American Standard Heating & Air Conditioning
Document ID: 4A7V8036A-SPEC-1, Revision: 13 Sep 2013
Certifications: AHRI Certified (Unitary Small AC, AHRI Standard 210/240), ETL Listed (US).