American Standard Submittal
4 Ton Split System Cooling — 1 Ph
Model: 4A7A7048B
Document Date: May 2020
Document ID: 4A7A7048B-SUB-1D-EN
Note: Graphics in this document are for representation only. Actual model may differ in appearance.
Product Specifications
NOTE: All dimensions are in mm/inches.
Product Specifications | 4A7A7048B1000A |
---|---|
POWER CONNS. -- V/PH/HZ | 208/230/1/60 |
MIN. BRCH. CIR. AMPACITY | 28 |
BR. CIR. PROT. RTG. – MAX. (AMPS) | 45 |
COMPRESSOR NO. USED - NO. STAGES | 1 - 2 |
VOLTS/PH/HZ | 230/1/60 |
R.L. AMPS - L.R. AMPS | 20.4 - 122 |
FACTORY INSTALLED START COMPONENTS | NO |
INSULATION/SOUND BLANKET | NO |
COMPRESSOR HEAT | NO |
OUTDOOR FAN DIA. (IN.) - NO. USED | PROPELLER 27.6 - 1 |
TYPE DRIVE - NO. SPEEDS | DIRECT - 1 |
CFM @ 0.0 IN. W.G. | 4400 |
NO. MOTORS - HP | 1 - 1/3 |
MOTOR SPEED R.P.M. | 825 |
VOLTS/PH/HZ | 208/230/1/60 |
F.L. AMPS | 2.8 |
OUTDOOR COIL -- TYPE | SPINE FINTM |
ROWS - F.P.I. | 1 - 24 |
FACE AREA (SQ. FT.) | 30.79 |
TUBE SIZE (IN.) | 3/8 |
REFRIGERANT LBS. -- R-410A (O.D. UNIT) | R-410A 13 LBS.- 3 OZ. |
FACTORY SUPPLIED | YES |
LINE SIZE - IN. O.D. GAS | 7/8 |
LINE SIZE - IN. O.D. LIQ. | 3/8 |
CHARGING SPECIFICATION SUBCOOLING | 10°F |
DIMENSIONS CRATED (IN.) | H X W X D 51 X 35.1 X 38.7 |
WEIGHT SHIPPING (LBS.) | 296 |
NET (LBS.) | 259 |
Notes on Specifications:
- Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program (AHRI standard 210/240). Indoor fan time delay on the comfort control must be enabled for AHRI standard rating.
- Rated in accordance with ARI standard 270.
- Calculated in accordance with National Electric Codes. Use only HACR circuit breakers or fuses.
- Standard Air — Dry Coil — Outdoor. Value is approximate; see unit nameplate for precise value. Max linear length 60 ft; Max lift (Suction) 25 ft; Max lift (Liquid) 25 ft. Consult refrigerant piping software for greater lengths.
- Compressor RLA value shown is used for computing minimum branch circuit ampacity and max fuse size, representing the branch circuit selection current.
- "No" indicates no start components. "Yes" indicates quick start kit components. "PTC" indicates positive temperature coefficient starter.
Diagram and Dimensional Data (Fig. 1)
Figure 1 illustrates the outdoor unit with various dimensions and connection points labeled A through K. It also details required clearances. The diagram shows an outdoor condensing unit with labels indicating:
- Model: 4A7A7048B
- Base: 4
- A (Width): 1147 mm (45-1/8 inches)
- B (Depth): 946 mm (37-1/4 inches)
- C (Height): 870 mm (34-1/4 inches)
- D (Gas Line Valve Size): 7/8 inches
- E (Liquid Line Valve Size): 3/8 inches
- F (Clearance): 152 mm (6 inches)
- G (Clearance): 98 mm (3-7/8 inches)
- H (Clearance): 219 mm (8-5/8 inches)
- J (Clearance): 86 mm (3-3/8 inches)
- K (Clearance): 813 mm (32 inches)
Required clearances include: top discharge area unrestricted for at least 1524 mm (5 feet), unit placement to avoid roof run-off, and at least 305 mm (12 inches) from walls and shrubbery on two sides, with the other two sides unrestricted. Electrical service panel locations are also indicated.
Sound Power Level Data
Model | A-Weighted Sound Power Level [dB(A)] | Full Octave Sound Power [dB] | |||||||
---|---|---|---|---|---|---|---|---|---|
63 Hz | 125 Hz | 250 Hz | 500 Hz | 1000 Hz | 2000 Hz | 4000 Hz | 8000 Hz | ||
4A7A7048B | 73 | 70 | 67 | 68 | 66 | 63 | 56 | 53 | 49 |
Note: Rated in accordance with AHRI Standard 270-2008.
Mechanical Specification Options
General
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit shall be certified to UL 1995. Exterior is designed for outdoor application.
Casing
Unit casing is constructed of heavy gauge, G60 galvanized steel and painted with a weather-resistant powder paint on all louvers and panels. It features a corrosion and weatherproof CMBP-G30 DuraBase™ base.
Refrigerant Controls
Refrigeration system controls include condenser fan, compressor contactor, and high pressure switch. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard.
Compressor
The Duration® 2-stage compressor features internal over temperature and pressure protection and a hermetic motor. Other features include roto lock suction and discharge refrigerant connections, a centrifugal oil pump, and modular plugs for electrical connections.
Condenser Coil
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.
Low Ambient Cooling
As manufactured, this unit has a cooling capability down to 55°F. For low ambient cooling below 55°F, refer to Application Guide APP-APG014-EN.
About American Standard Heating and Air Conditioning
American Standard has been creating comfortable and affordable living environments for more than a century. For more information, please visit www.americanstandardair.com.
Certifications and Disclaimers
The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, visit ahridirectory.org.
The manufacturer has a policy of continuous data improvement and reserves the right to change design and specifications without notice. The company is committed to using environmentally conscious print practices.
Document Version: 4A7A7048B-SUB-1D-EN (May 2020), Supersedes 4A7A7048B-SUB-1C-EN (February 2020).