MINI-RS RS485 Multiprotocol I/O Modules

Software Bundle Release Notes

Software Bundle Version 7.1 (18 Jun 2025)

Modifications and new features since software bundle version 6.5:

NAME DESCRIPTION
MINI-RS Ver. 7.1
Release date: 18 Jun 2025
New functionalities:
  • BACnet Protocol Revision 22 Update
  • New B-SS (BTL-31278) and B-SA (BTL-31262) BACnet Conformance Certificates
  • New services and objects added according to BACnet 1.22 standard:
    • Added ReinitializeDevice service
    • Added ReadRange service
    • Added Network Port object
  • Added support for custom Modbus intermessage delay for RS485 Gateway function
Improvements:
  • ASV (Application software version) value changed to 1.0
  • Send Modbus Error Codes supported and can be enabled/disabled in both IP and RS485 I/O Modules
Fixed bugs:
  • New BACnet ID not accepted after reload settings

Software Bundle Version 6.5 (13 Oct 2020)

Modifications and new features since software bundle version 6.4:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 6.5
Release date: 13 Oct 2020
Improvements:
  • Default BBMD IP address set to 0.0.0.0
  • Registering to the BBMD server is disabled if the BBMD IP address is left default
  • Added option to disable the web server access by setting the HTTP port to 0
  • For 4U4O: if the default temperature sensor is set to Fahrenheit, the default setpoint temperature is 70°F
  • BACnet stability improvement
Fixed bugs:
  • Fixed Modbus statistics on www: Modbus Received / Error / Transmitted Frames
  • Fixed BACnet ID changes to reload settings
  • Fixed loss of frames over BACnet IP
  • Fixed UI filter reset in case of short disconnection of the sensor
  • PT1000 temperature sensor fix for readings over 350°C
  • In case the temperature sensor on the UI gets disconnected, the temperature value is restored to its min/max INT value

Software Bundle Version 6.3 (3 Mar 2020)

Modifications and new features since software bundle version 6.2:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 6.3
Release date: 3 Mar 2020
New functionalities:
  • New temperature sensors implemented in Celsius and Fahrenheit degrees:
    • Celsius: NI1000 21C, NI1000 LG, 10K Type2 NTC B=3975K, 10K Type3 NTC B=3695K, 20K NTC B=4262K, 3K NTC B=3975K, PT1000
    • Fahrenheit: NI1000 32F, NI1000 70F
  • New Modbus function 0x17 Read/Write Multiple registers
  • New Modbus function 0x2B to read VENDOR_NAME, MODEL_NAME, FW_VERSION, HOMEPAGE
Improvements:
  • Improved filtering on UI
  • Device Name (Object Name) in BACnet is saved in EEPROM memory
Fixed bugs:
  • Fixed one record in sensor 30k6A1 table – resistance 60713 to 80713 (5°C)

Software Bundle Version 6.0 (7 Dec 2017)

Modifications and new features since software bundle version 5.5:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 6.0
Release date: 7 Dec 2017
New functionalities:
  • Firmware Version 6.0 released with BACnet certification
  • Added possibility to upgrade devices firmware via BACnet
Fixed bugs:
  • Fixed out of service flags in AO, BO and TO in BACnet
  • Fixed overridden flags in AO, BO and TO in BACnet
  • Fixed bug with number of counters for Binary Input object (now variable is 32-bit)
  • Changed AO-1, BO-1, TO-1 HAND_STATUS Access to read only in BACnet

Software Bundle Version 5.2 (17 Jan 2017)

Modifications and new features since software bundle version 5.1:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 5.2
Release date: 17 Jan 2017
Fixed bugs:
  • Fixed bug with RS485 communication problem after device update (in FW version 5.0 and 5.1 a power-up cycle was needed to work properly)

Software Bundle Version 5.1 (13 Jan 2017)

Modifications and new features since software bundle version 5.0:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 5.1
Release date: 13 Jan 2017
Fixed bugs:
  • Fixed bug with saving configuration to EEPROM memory (in FW version 5.0, saving to EEPROM memory could fail once for dozens of records)

Software Bundle Version 5.0 (4 Jan 2017)

Modifications and new features since software bundle version 4.3:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 5.0
Release date: 4 Jan 2017
New functionalities:
  • New HVAC functions Heating and Cooling in 4U4O based on output thermostatic control with setpoint and differential value setting
  • Added new input mode for 4I4O: Time Relay NC [ms], Time Relay NO and NC in seconds, Input Forwarding
  • Added new input mode for 4U4O: Ordinary IO, Monostable Relay, Bistable Relay, Time Relay NO and NC [ms], Time Relay NO and NC in seconds, Input Forwarding, Heating, Cooling with corresponding BACnet objects and Modbus registers
  • Added reset output to default after input mode change in 4U4O and 4I4O
Improvements:
  • Improved BACnet COV Increment, can now have values with resolution 0.1
  • Added BACnet COV Increment access (read/write) through USB
  • Added power LED flashing after IO watchdog triggered
  • Changed IO watchdog reset after read/write registers through USB
  • Added immediate detection of sensor short circuit and disconnection regardless of filter settings on universal inputs
Fixed bugs:
  • Fixed bug with Stop bits, which was always 1

Software Bundle Version 4.3 (28 Sep 2016)

Modifications and new features since software bundle version 4.2:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 4.3
Release date: 28 Sep 2016
Improvements:
  • UI filter improved (better signal stability at a lower filter time constant)
Fixed bugs:
  • Fixed a physical output state when the priority table is null in BACnet Binary/Analog/Triac Output object (when priority table is null, physical output is set to relinquish default value)

Software Bundle Version 4.2 (22 Apr 2016)

Modifications and new features since software bundle version 4.0:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 4.2
Release date: 22 Apr 2016
Improvements:
  • Added new module 4TO-H
  • Added possibility to set COV Increment via USB by iSMA-Configurator
Fixed bugs:
  • Fixed LED flashing in module 4U4A when AO_VALUE > 0 in 0-10V mode

Software Bundle Version 4.0 (18 Jan 2016)

Modifications and new features since software bundle version 1.0:

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 4.0
Release date: 18 Jan 2016
New functionalities:
  • New BACnet objects for configuration (detail in manual)
  • Added BACnet device property (Active COV Subscriptions)
  • Added BACnet objects for additional modes in 4I4O
Improvements:
  • Improved configuration of flag Out Of Service and Override in digital outputs and analog outputs
  • Added COV Increment for universal inputs and analog outputs
  • BACnet Out Of Service for UI and BI with the possibility of overwriting present value
  • BACnet Analog Output and Binary Output priority table reset after watchdog was triggered
  • Improved Resistance measurement on universal input for increased accuracy of PT1000 and NI1000
  • Improved counter of TX and RX frames in MS/TP BACnet
  • Improved additional modes in 4I4O
Fixed bugs:
  • Fixed LED flashing in module 4U4A when AO_VALUE > 0 in 0-10V mode

Software Bundle Version 1.0 (13 Jul 2015)

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 1.0
Release date: 13 Jul 2015
Improvements:
  • Improved stability and speed in BACnet MS/TP
  • Default settings after reset for Analog Outputs
  • Changed Firmware Version and Application Software Version in BACnet
  • Changed saving counters via USB and Modbus (regular verification of changing settings)
  • Improved reading structure of bits in Modbus (reset irrelevant bits)

Software Bundle Version 0.8 (12 Jun 2015)

NAME DESCRIPTION
iSMA-B-MINI-RS Ver. 0.8
Release date: 12 Jun 2015
First release.

PDF preview unavailable. Download the PDF instead.

iC MINI RS Series FW Release Notes V7.1 Microsoft Word for Microsoft 365

Related Documents

Preview iSMA-B-24I Digital Input Module: Specifications and Installation Guide
Detailed technical specifications and installation guidelines for the iSMA-B-24I digital input module from iSMA CONTROLLI, featuring RS485 communication and 24 dry contact inputs.
Preview iSMA-B-4I4O-H-IP Installation Guide and Specifications
Detailed installation guide and technical specifications for the iSMA-B-4I4O-H-IP industrial automation controller, covering its features, wiring, safety considerations, and compliance.
Preview ISMA-D-PA15C-B1 15.6" Industrial PC Panel Datasheet
Datasheet for the ISMA-D-PA15C-B1, a 15.6" Industrial PC Panel with Android 7.1 OS, capacitive touch screen, and the dedicated ISMA Android Application for building automation.
Preview SFAR-S-16DI Installation Guideline and Specifications | iSMA CONTROLLI
Comprehensive installation guidelines, technical specifications, and Modbus register map for the iSMA CONTROLLI SFAR-S-16DI digital input module. Includes safety warnings and setup details for industrial automation.
Preview iSMA-D-PA15C-B1 Installation and Guidelines
Installation instructions and guidelines for the iSMA-D-PA15C-B1, a 15.6-inch capacitive touch screen industrial panel computer running Android 7.1.
Preview SFAR-1M-4DI-M Digital Input Module - ISMACONTROLLI Installation & Specifications
Detailed installation guide, specifications, and Modbus register map for the ISMACONTROLLI SFAR-1M-4DI-M digital input module. Learn about power supply, digital inputs, connections, and safety precautions.
Preview ISMACONTROLLI SfAR-S-6RO User Manual: Expansion Module - 6 Relay Outputs
Comprehensive user manual for the ISMACONTROLLI SfAR-S-6RO, a 6-relay output expansion module designed for RS485 Modbus networks. Details include technical specifications, electrical connections, communication settings, DIP switch configuration, module registers, and safety guidelines.
Preview iSMA CONTROLLI MVE5xx-65 IP65 Globe Valve Actuators: Technical Specification and Operation
Detailed technical specifications, operation guide, and compatibility information for the iSMA CONTROLLI MVE5xx-65 series IP65 Globe Valve Actuators, designed for HVAC and industrial temperature control systems.