Shark® 100S/200S Meter Quickstart Guide
This document provides basic installation, wiring, and programming instructions for the Shark® 100S and 200S meters.
Safety Precautions
CAUTION! Installation of the Shark® 100S/200S meter must be performed only by qualified personnel who follow standard safety precautions during all procedures. Those personnel should have appropriate training and experience with high voltage devices. Appropriate safety gloves, safety glasses and protective clothing are recommended.
WARNING! During normal operation of the Shark® meter, dangerous voltages flow through many parts of the unit, including: Terminals and any connected CTs (Current Transformers) and PTs (Potential Transformers), all I/O Modules and their circuits. All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces.
Do not use the meter or any I/O device for primary protection or in an energy-limiting capacity. The meter can only be used as secondary protection.
AVERTISSEMENT! Pendant le fonctionnement normal du compteur Shark® 100S/200S des tensions dangereuses suivant de nombreuses pièces, notamment, les bornes et tous les transformateurs de courant branchés, les transformateurs de tension, toutes les sorties, les entrées et leurs circuits. Tous les circuits secondaires et primaires peuvent parfois produire des tensions de létal et des courants. Évitez le contact avec les surfaces sous tensions. Avant de faire un travail dans le compteur, assurez-vous d'éteindre l'alimentation et de mettre tous les circuits branchés hors tension.
IMPORTANT! Refer to your meter's Installation and Operation Manual for additional safety warnings before performing installation, wiring, or maintenance of your meter. See the link to the manual, below.
Documentation and Support
NOTE: This Quickstart Guide gives basic installation, wiring, and programming instructions. For additional meter operation and programming information, refer to your meter's Installation and Operation Manual and the CommunicatorPQATM, MeterManagerPQATM, and EnergyPQA.comTM Software User Manual on EIG's website:
User Manual:
Shark® 100S Meter: https://www.electroind.com/products/shark-100s-economical-wifi-submeter/
Shark® 200S Meter: https://www.electroind.com/products/shark-200s-advanced-data-logging-wifi-submeter/
From the webpage, click Technical Documents > User Manual.
Software Manual:
https://www.electroind.com/products/communicatorpqa-software-application-5/
From the webpage, click Technical Documents > User Manual.
CommunicatorPQA™ Setup Software:
https://www.electroind.com/products/communicatorpqa-software-application-5/
From the webpage, click Download ComPQA Pro. To get a Professional license for the software, email sales@electroind.com or call 516-334-0870.
All EIG's metering and software products' literature can be accessed from: https://www.electroind.com/all-products/
Technical Support:
For software and metering integration, EIG's Technical Support Engineers are available on an hourly or daily basis to help with typical commissioning assistance, which includes:
- Verifying meter installation and wiring.
- Verifying proper system integration.
- Working with 3rd parties to ensure cross compatibility.
- Advising users on best practices for optimal implementation.
You can reach Technical Support from 8 a.m. to 8 p.m. EST, Monday-Friday, at 516-334-0870.
Electro Industries/GaugeTech™
Powered by Innovation™
Wiring and Configuration
NOTE: Jumper 2 (JP2) must be set for either RS485 or Ethernet communication. Put the jumper on positions 2 and 3 for LAN (Ethernet) communication, or on 1 and 2 for RS485 communication.
Wiring Diagrams
Select wiring diagram to meet your application. See User Manual for additional wiring diagrams.
Programming Settings Using Faceplate Buttons
Use the following buttons: MENU, ENTER, DOWN ARROW, RIGHT ARROW. See the figure below for the location of the faceplate buttons.
Access Configuration Mode
- Press the MENU button - the display will show 'rSt' blinking.
- Press the DOWN ARROW once. 'CFG' (Configuration) will move to the top of the display.
- Press the ENTER button. The Configuration menu will be shown.
Configuring CT and PT Settings
Follow these steps to configure CT and PT settings:
- Press DOWN ARROW and then ENTER to access the CT numerator setting screen (Ct-n). Adjust the value using DOWN ARROW and RIGHT ARROW to move between digits.
- Press ENTER to go to the CT denominator screen (CT-d). This setting is display only.
- Press ENTER to go to the CT Scaling setting screen (CT-S). Choose a value of 1, 10, or 100 using the DOWN ARROW.
- Press ENTER to go to the PT numerator setting screen (Pt-n). Adjust the value using DOWN ARROW and RIGHT ARROW.
- Press ENTER to go to the PT denominator screen (Pt-d). Adjust the value using DOWN ARROW and RIGHT ARROW.
- Press ENTER to go to the PT Scaling setting screen (PT-S). Choose a value of 1, 10, 100, or 1000 using the DOWN ARROW.
- Press ENTER to go to the Connection setting screen (Cnct). Choose from 3 EL (element) WYE, 2 Ct del (Delta), or 2.5 EL WYE.
- Press ENTER to go to the meter Address setting screen (Adr). Adjust the address (001-247) using DOWN ARROW and RIGHT ARROW. Note: If using Ethernet, do NOT change this setting.
Additional Settings and Examples
Baud Rate and Protocol Settings
- Press ENTER to go to the Baud Rate setting screen (bAUd). Choose 9600 (for RS485), 19.2, 38.4, or 57.6. Note: If using Ethernet, do NOT change this setting.
- Press ENTER to go to the Protocol setting screen (Prot). Choose Mod rtU (Modbus RTU for RS485), Mod ASCI (Modbus ASCII), or dnp (DNP 3.0). Note: If using Ethernet, do NOT change this setting.
- Press ENTER to go to the Scroll setting screen (SCrL). Choose YES (scrolling) or no (no scrolling).
Saving Settings
- Press MENU twice to access the Store Settings screen (Stor ALL?).
- Press ENTER to save the settings. A confirmation screen ('Stor ALL done') will appear, and the meter will reset.
- To not save settings, press RIGHT ARROW to change YES to no, then press ENTER.
Example CT Settings:
- 200/5 Amps: set Ct-n to 200, Ct-S to 1.
- 800/5 Amps: set Ct-n to 800, Ct-S to 1.
- 2000/5 Amps: set Ct-n to 2000, Ct-S to 1.
- 10,000/5 Amps: set Ct-n to 1000, Ct-S to 10.
Example PT Settings:
- 14400/120 Volts: set Pt-n to 1440, Pt-d to 120, Pt-S to 10.
- 138000/69 Volts: set Pt-n to 1380, Pt-d to 69, Pt-S to 100.
- 345000/115 Volts: set Pt-n to 3450, Pt-d to 115, Pt-S to 100.
- 345000/69 Volts: set Pt-n to 345, Pt-d to 69, Pt-S to 1000.
For additional programming instructions, see Chapter 7 in your meter's User Manual (page QS-1).
Connecting to the Meter via IrDA Port
Follow these steps to connect to the meter:
- Connect the meter to the PC. EIG offers a USB to IrDA cable, available from EIG’s website: https://www.electroind.com/products/usb-to-irda-adapter/.
- Open CommunicatorPQATM software (see page QS-1 for download link).
- Click 'Connect' in the Icon Bar.
- The 'Connect' screen will appear. Ensure your settings match the example shown (use pull-down menus).
- Click 'Connect'. The 'Device Status' screen will open, confirming the connection. Click OK to close it.
- Click the 'Profile' icon in the Icon bar.
- The 'Device Profile' screen opens. For the 100S, settings are accessed via tabs at the top. For the 200S, a Tree menu is on the left side.
Programming CT, PT Ratios and Communications
NOTE: The screens shown are from the Shark® 100S meter. The Shark® 200S meter's screens may have additional settings. See Chapter 8 in the software user manual for details.
Program CT, PT Ratios
- This is the first Device Profile screen. To return, click the Scaling tab.
- Settings include:
- CT Numerator (Primary): Enter desired value.
- CT Denominator (Secondary): Display only.
- CT Multiplier: Choose 1, 10, or 100.
- CT Fullscale: Calculated automatically.
- PT Numerator (Primary): Enter desired value.
- PT Denominator (Secondary): Enter desired value.
- PT Multiplier: Choose 1, 10, 100, or 1000.
- PT Fullscale: Calculated automatically.
Note: Voltage Full Scale = PT Numerator x PT Multiplier. Current Full Scale = CT Numerator x CT Multiplier.
IMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOT Ratios).
You can also enter Ratios for CT/PT Numerator and Denominator, then click 'Update CT'/'Update PT' for the software to calculate the values. Clearing the Ratio fields and clicking 'Update Ratio' confirms the calculated settings.
See Chapter 8 (200S) or Chapter 9 (100S) in the software manual for additional screen settings instructions, or click Help > Contents from the CommunicatorPQATM software's Main screen.
Program Communications
- Click the 'Communication' tab.
- Default settings for IrDA (COM1) and RS485 (COM2) ports are shown. Change as needed. To revert RS485 settings, click 'Set COM2 to default' (200S does not have this option).
NOTE: If you do not have the RS485 option, ignore those settings.
Programming Meter Time and Name
Program Meter Time:
The meter is preset to Eastern time. To change the meter time:
- From the Main screen's Title bar, click Tools > Set Device Time.
- Enter time in fields or click 'Use PC Time'.
- Click 'Send'.
Program Meter Name:
To enter a name/ID for the meter:
- From the Device Profile screen, click the 'Settings' tab.
- Input a new meter designation into the 'Device/Meter Designation' field. Naming each meter individually is important as it's used for log databases.
IMPORTANT! When changes are made to the meter's Device Profile, click 'Load Profile' to send new settings to the meter. The meter will reboot. You can also click 'Save Profile' to save changes without sending them.