Simplex 4004 Fire Alarm System

Installation/Operation Instructions

Document Number: 574-074 Rev. C

Chapter 1: 4004 System Overview

The 4004 Fire Alarm Control Panel (FACP) is a general alarm, battery-backed, electrically supervised system capable of operating two Notification Appliance Circuits (NACs) and monitoring two Initiating Device Circuits (IDCs) with expansion capability up to 8-IDCs. The 4004 FACP can automatically control auxiliary equipment such as fire doors and fans during a fire condition. It provides audible and visible indications during Fire Alarm, Supervisory, or Trouble conditions.

When a condition occurs:

The 4004 system has a “Re-sound” capability. If another circuit goes into alarm, supervisory, or trouble after an acknowledgment, the applicable display flashes, and signals operate again. The system remains in alarm until the device is restored to normal and the panel is reset.

The FACP continuously checks for electrical troubles (power loss, battery problems, wiring faults, etc.). A “Trouble” condition triggers the tone-alert and the yellow trouble display indicates the type of trouble. An active status reminder sounds the tone-alert every eight hours for five seconds if an acknowledged alarm, supervisory, or trouble condition exists.

Figure 1 illustrates the physical layout of the cards and the power-limited and non-power-limited wiring areas within the 4004. Printed circuit boards are joined by board-to-board connectors or a wiring harness.

Environmental

The 4004 operates within the following conditions:

Ground

The 4004 FACP must be properly grounded. Readings of less than 0.70 VAC must be measured between ground and neutral. A dedicated Earth connection per NFPA 70, Article 250, and NFPA 78 is required. Connect a 12 AWG copper ground wire from the safety ground (electrical distribution panel) to the green grounding screw on the FACP.

Power Input

The 4004 system is designed for 120 VAC, 60 Hz or 220/240 VAC, 50/60 Hz.

Battery Standby

The batteries mount in the 4004 control panel and provide at least 60 hours of standby operation for a fully configured system. Note: 60 hours of standby is based on 10 Ah batteries without four-wire detectors or other non-alarm loads, followed by five minutes in alarm. A fully configured system with 6.2 Ah batteries provides at least 24 hours of standby, followed by five minutes in alarm.

4004 System Features

4004 System Diagram

Figure 1 depicts the system wiring, including conduit entry points for power-limited and non-power-limited wiring, various circuit connections, and module placements. It details connections for the system board, IDC boards, annunciator interface, and optional modules like the City Connect or DACT boards.

Chapter 2: Requirements and Accessories

Regulatory Requirements

The 4004 Fire Alarm System is listed/approved for the following categories:

Installation Requirements

Compliance with NFPA Codes and Standards is essential. Key referenced standards include:

Optional Accessories

Chapter 3: Installation

Requirements

IMPORTANT: Notify appropriate personnel (building occupants, fire department, or monitoring facility) before installation. Ensure familiarity with these instructions and all applicable regulatory requirements.

Required tools and equipment include:

The installer is responsible for safeguarding all 4004 material. Store all items in a clean, dry, and safe place.

Back Box

  1. Remove the back box from the shipping container and lay it on a flat surface.
  2. Install the back box using Figure 2 as a reference. Refer to Figure 2 and the 841-992 Field Wiring Diagram for specific internal wiring directions.

CAUTION: Enclosure must be level and plumb when installing the back box.

Figure 2 illustrates back box mounting, including dimensions, weight, and rough opening specifications. Notes provide guidance on semi-flush mounting, conduit entry, and space for battery installation.

Wiring

Refer to Figure 3 for the interconnect wiring diagram. For detailed wiring information, including circuit loading capacities, distance specifications, and wire size, consult the 841-992 Field Wiring Diagram.

System Modules

The Base 4004 System [565-691] includes a System Board with 2-IDCs and 2-NACs. Each IDC supports up to 30 compatible two-wire detectors and can be configured for various point types: Fire Monitor, Alarm Verification, Fire/Supervisory, Trouble, and Style C. Zone disconnect switches are provided for each IDC. An “Abort Enable” feature inhibits notification circuits for 15 seconds upon zone restoration.

Selectable IDC Types:

Figure 3 shows the interconnect wiring diagram, detailing connections between various modules including the system board, IDC boards, City Connect, DACT, and Annunciator Interface modules.

Jumper Settings/Service Switches

Jumper settings configure NAC operation (On Until Silence/Reset) and City Circuit configuration (Local Energy/Remote Station). Table 1 details jumper settings for these configurations.

NAC Operation:

City Circuit Configuration: Refer to Table 1 for jumper settings to configure City Circuits 1 and 2.

Auxiliary Circuit Supervision: Supervise AUX Zone 1/2 alarm outputs by clipping JW1/JW2 on the System Board. Supervise AUX Alarm output by clipping JW3. For Zones 3-8 supervision, remove specific jumpers on expander modules.

Service Switches:

Programming Instructions

The 4004 system can be configured using the seven-segment displays and the “ACK” and “SYSTEM RESET” keys. Activating switch SW3 enters program mode. Alarms and troubles are not processed in program mode.

Default Conditions: System configured for 8-IDC, CITY/DACT, Annunciator Interface; all IDCs are FIRE type; NAC 1 is coded Temporal until Silence; NAC 2 is steady until Reset; Abnormal condition reminder is active.

Programming Steps:

  1. Activate SW3 to enter program mode. A tone-alert sounds until the “ACK” key is pressed. A lowercase “h” appears on the “TROUBLE” display.
  2. Use the “ACK” key to scroll through programming options and the “SYSTEM RESET” key to select configuration options. Refer to Figure 4 for programming selections.
  3. Deactivate SW3 to exit program mode. The setup is saved, and the “h” clears. Record the setup in the “CURRENT SETUP” section on the 4004 door panel label.

Figure 4 illustrates programming selections for the number of zones, initiating device point types, City/Dact module presence, Notification Appliances operation, and Annunciator interface presence.

Chapter 4: Operating Instructions

Front Panel Operation

The user interface includes controls and indicators for alarm, supervisory, trouble, power, and alarm silenced conditions (Figure 5).

Indicators and Controls:

Operator Keys:

System Initialization (Power-Up)

IMPORTANT: Notify appropriate personnel of power-up.

Normal Power-Up: Apply system power. Panel displays and indicators appear. Tone alert sounds for one second. “AC POWER” LED is ON. Program the system as needed.

Power-Up Trouble Conditions: Panel displays and indicators do not appear. Check fuses or circuit breakers. If power is removed and reapplied after checks, and the system still indicates trouble, contact Simplex.

Supervisory Conditions

A Fire/Supervisory point distinguishes between Fire Alarm and Supervisory conditions. When water is flowing in a sprinkler system, an Alarm is indicated. If a sprinkler or water pump valve is closed, a “SUPERVISORY” condition is indicated. The yellow “SUPERVISORY” LED flashes, and the tone-alert sounds until acknowledged via the “ACK” key. The “SUPERVISORY” LED remains ON steady after acknowledgment.

Walk Test

The 4004 is equipped with Walk Test, activated by SW4 on the System Board. This feature allows one person to test the system.

System Testing (Fire Drills)

Fire Drills should be conducted periodically to ensure occupant familiarity with emergency procedures and system functionality. Testing should be directed by the owner and the local Authority Having Jurisdiction (AHJ).

Considerations for testing:

For systems connected to a city circuit, notify the AHJ. The AHJ determines if the city connection should be disabled during the test. Optional city modules have disconnect switches (SW1, SW2) for disabling city circuits.

To initiate a test, activate an initiating device (pull station, smoke detector). This simulates a real alarm condition.

Emergency Operating Instructions

If the 4004 Fire Alarm System has an Alarm, Supervisory, or Trouble condition, follow these procedures:

Chapter 5: Glossary of Terms

This chapter provides definitions for key terms used in the manual.

Chapter 6: 4004 Battery Selection

Battery Selection

60 Hours of Standby Operation (with 10 Ah batteries): Fully configured 4004 system provides at least 60 hours standby, followed by 10 minutes of alarm, when no four-wire detectors or non-alarm loads are connected.

24 Hours of Standby Operation (with 6.2 Ah batteries): Fully configured 4004 system provides at least 24 hours standby, followed by 10 minutes of alarm, when no four-wire detectors or non-alarm loads are connected.

4004 Fire Alarm System with 4-Wire Detectors or Non-Alarm Loads: For systems requiring four-wire detectors or non-alarm loads, use the battery calculation equation in Table 4.

Table 3 provides the Supervisory Current requirements for various modules:

Module Supervisory Current
Standard Panel 52 mA
4004-9802, 2 Pt. IDC, Low Current 7 mA
4004-9804, 4 Pt., Low Current 14 mA
4004-9822, 2 Pt. IDC, High Current 14 mA
4004-9824, 4 Pt. IDC, High Current 27 mA
4004-9806, Class A Adapter N.A.
4004-9808, Annunciator Interface Module 4 mA
4004-9809, 2 Circuit Remote Station/City Connect 12 mA
2080-9045 DACT 35 mA

Note: Add all NAC Appliances and IDC Devices for total.

Battery Selection Calculation

Table 4 provides a step-by-step calculation for determining battery requirements:

  1. Enter total supervisory current from all cards.
  2. Enter total Auxiliary power current draw in standby.
  3. Enter total two-wire detector current draw in standby.
  4. Sum lines 1, 2, and 3 for total standby current.
  5. Enter the required hours of standby.
  6. Multiply line 4 by line 5 for total standby Ah requirement.
  7. Enter the total NAC/AUX alarm current.
  8. Multiply line 7 by 0.083 for five minutes of alarm, or by 0.167 for ten minutes of alarm.
  9. Add lines 6 and 8.

Battery Sizing Guidelines:

Notes:

Models: 4004 Fire Alarm Control Panel, 4004, Fire Alarm Control Panel, Alarm Control Panel, Control Panel

File Info : application/pdf, 36 Pages, 206.13KB

PDF preview unavailable. Download the PDF instead.

4004

Related Documents

Preview Simplex 4010ES Fire Alarm Control Panel Operator's Manual
This manual provides comprehensive instructions for operating the Simplex 4010ES Fire Alarm Control Panel (FACP). It covers basic concepts, alarm conditions, trouble conditions, supervisory conditions, advanced functions, and system test procedures. Learn how to acknowledge alarms, silence alarms, reset the system, and manage various system events.
Preview Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide
Comprehensive guide for installing, operating, and programming the Simplex 4010 Fire Alarm system. Covers system overview, wiring, configuration, diagnostics, and troubleshooting.
Preview Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide
Comprehensive guide for the Simplex 4010 Fire Alarm system, covering installation, operation, and programming instructions. Includes system overview, wiring, configuration, diagnostics, and troubleshooting.
Preview Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide
Comprehensive guide for installing, operating, and programming the Simplex 4010 Fire Alarm system. Covers system components, wiring, configuration, diagnostics, and troubleshooting.
Preview Simplex 4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming Guide
Comprehensive guide for wiring and programming the Simplex 4098-9019 IDNet Addressable Beam Detector system with Simplex Fire Alarm Control Panels (FACPs). Covers compatibility, electrical specifications, addressing, and panel operations.
Preview Simplex 4007ES Color Touchscreen LCD Annunciator Installation Manual
Installation guide for the Simplex 4007ES Color Touchscreen LCD Annunciator, detailing wiring, mounting, and address setting procedures for fire alarm systems.
Preview Simplex 4098 Detectors, Sensors, and Bases Application Manual
This application manual provides comprehensive information on the proper use and installation of Simplex 4098 series detectors, sensors, and bases within fire alarm systems. It covers principles of operation, placement guidelines, compatibility, testing procedures, and troubleshooting for these critical fire safety components.
Preview Simplex 4100ES Service Parts List
Official service parts list for the Simplex 4100ES fire alarm system, detailing replacement components, modules, and accessories for maintenance and repair.