Simplex 4004 Fire Alarm System
Installation/Operation Instructions
Document Number: 574-074 Rev. C
Chapter 1: 4004 System Overview
The 4004 Fire Alarm Control Panel (FACP) is a general alarm, battery-backed, electrically supervised system capable of operating two Notification Appliance Circuits (NACs) and monitoring two Initiating Device Circuits (IDCs) with expansion capability up to 8-IDCs. The 4004 FACP can automatically control auxiliary equipment such as fire doors and fans during a fire condition. It provides audible and visible indications during Fire Alarm, Supervisory, or Trouble conditions.
When a condition occurs:
- The system sounds the appropriate notification appliance(s) and flashes the applicable display (red “FIRE ALARM ZONE” for fire alarm, yellow “TROUBLE” for trouble, and yellow LED for “Supervisory”).
- Acknowledging the alarm immediately silences the panel audible and causes the display to illuminate steadily.
- Pressing the “SYSTEM RESET” key resets the system and causes the seven-segment alarm and trouble displays to indicate a dash (-) for 15-seconds. If the reset is successful, the displays go out; otherwise, they indicate any existing conditions.
The 4004 system has a “Re-sound” capability. If another circuit goes into alarm, supervisory, or trouble after an acknowledgment, the applicable display flashes, and signals operate again. The system remains in alarm until the device is restored to normal and the panel is reset.
The FACP continuously checks for electrical troubles (power loss, battery problems, wiring faults, etc.). A “Trouble” condition triggers the tone-alert and the yellow trouble display indicates the type of trouble. An active status reminder sounds the tone-alert every eight hours for five seconds if an acknowledged alarm, supervisory, or trouble condition exists.
Figure 1 illustrates the physical layout of the cards and the power-limited and non-power-limited wiring areas within the 4004. Printed circuit boards are joined by board-to-board connectors or a wiring harness.
Environmental
The 4004 operates within the following conditions:
- Temperature: 32-120° F (0-49° C)
- Humidity: UL - 85% relative humidity (non-condensing), ULC - 93% relative humidity (non-condensing)
Ground
The 4004 FACP must be properly grounded. Readings of less than 0.70 VAC must be measured between ground and neutral. A dedicated Earth connection per NFPA 70, Article 250, and NFPA 78 is required. Connect a 12 AWG copper ground wire from the safety ground (electrical distribution panel) to the green grounding screw on the FACP.
Power Input
The 4004 system is designed for 120 VAC, 60 Hz or 220/240 VAC, 50/60 Hz.
Battery Standby
The batteries mount in the 4004 control panel and provide at least 60 hours of standby operation for a fully configured system. Note: 60 hours of standby is based on 10 Ah batteries without four-wire detectors or other non-alarm loads, followed by five minutes in alarm. A fully configured system with 6.2 Ah batteries provides at least 24 hours of standby, followed by five minutes in alarm.
4004 System Features
- Expandable from two to a maximum of 8-IDCs
- 2 Notification Appliance Circuits (NACs)
- 4 Amps of Power to meet ADA Requirements
- Surface or Semi-Flush Installation
- Zone (IDC) Disconnect Switches with Abort Enable Features
- Alarm Output Disconnect Switch
- Single Piece Chassis
- One Person Walk Test
- 5-IDC Point Type Selections
- Chronological Event Display
- Indicator (Lamp) Test Feature
- Low and Depleted Battery Detection
- Active Status Reminder
- Non-volatile Memory
- Six Alarm Silence Inhibit Timer Selections
- Four Auto-Silence Timer Selections
- Four Coded Signal Selections
- Available with Optional City Circuits
- Class A (Style D/Style Z) Converters
- Full Function Remote Annunciator Interface
- Simplex 4003 Voice Control Panel and 4009 NAC Extender
4004 System Diagram
Figure 1 depicts the system wiring, including conduit entry points for power-limited and non-power-limited wiring, various circuit connections, and module placements. It details connections for the system board, IDC boards, annunciator interface, and optional modules like the City Connect or DACT boards.
Chapter 2: Requirements and Accessories
Regulatory Requirements
The 4004 Fire Alarm System is listed/approved for the following categories:
- UL Standard 864 System Types: UL 864 Power-Limited Fire Alarm Control Unit, Local (NFPA 72A), Auxiliary (NFPA 72B), Remote Station (NFPA 72C), Proprietary (NFPA 72D), Central Station (NFPA 71).
- UL 864 Listings for Type of Service: Automatic, Manual, Waterflow, and Sprinkler Supervisory.
- UL 864 Listings for Type of Signaling: Coded, Non-Coded, March-Time, and DACT.
- Factory Mutual Approved: Same as UL listings, plus Intrinsically Safe (requires 2081-9036 module).
- Local/Regional Approvals: CSFM, MEA.
Installation Requirements
Compliance with NFPA Codes and Standards is essential. Key referenced standards include:
- NFPA 72 - National Fire Alarm Code
- NFPA 11, 11A, 12, 12A, 13, 15, 16, 16A, 17, 17A, 25 - Standards for various extinguishing systems and testing.
- NFPA 70 - National Electrical Code
- NFPA 80 - Standard for Fire Doors and Fire Windows
- NFPA 90A, 90B - Standards for Air Conditioning and Ventilation Systems
- NFPA 92A, 92B - Standards for Smoke-Control and Management Systems
- NFPA 101 - Life Safety Code
- NFPA 170 - Standard for Fire Safety Symbols
- NFPA 231C - Standard for Rack Storage of Materials
- NFPA 1221 - Standard for Public Fire Service Communication Systems
Optional Accessories
- 4003 Series Voice Control Panel: Provides voice communication.
- 4009 Series NAC Power Extender: Provides additional power and NACs.
- 4601 Series Annunciators: Provides remote Annunciation/Control.
Chapter 3: Installation
Requirements
IMPORTANT: Notify appropriate personnel (building occupants, fire department, or monitoring facility) before installation. Ensure familiarity with these instructions and all applicable regulatory requirements.
Required tools and equipment include:
- 1/4-inch Flat-Tip Screwdriver
- Volt-Ohmmeter
- Diagonal Cutting Pliers
- Wire Strippers
- End-of-Line Resistors (supplied by Simplex)
- The 841-992 Field Wiring Diagram
The installer is responsible for safeguarding all 4004 material. Store all items in a clean, dry, and safe place.
Back Box
- Remove the back box from the shipping container and lay it on a flat surface.
- Install the back box using Figure 2 as a reference. Refer to Figure 2 and the 841-992 Field Wiring Diagram for specific internal wiring directions.
CAUTION: Enclosure must be level and plumb when installing the back box.
Figure 2 illustrates back box mounting, including dimensions, weight, and rough opening specifications. Notes provide guidance on semi-flush mounting, conduit entry, and space for battery installation.
Wiring
Refer to Figure 3 for the interconnect wiring diagram. For detailed wiring information, including circuit loading capacities, distance specifications, and wire size, consult the 841-992 Field Wiring Diagram.
System Modules
The Base 4004 System [565-691] includes a System Board with 2-IDCs and 2-NACs. Each IDC supports up to 30 compatible two-wire detectors and can be configured for various point types: Fire Monitor, Alarm Verification, Fire/Supervisory, Trouble, and Style C. Zone disconnect switches are provided for each IDC. An “Abort Enable” feature inhibits notification circuits for 15 seconds upon zone restoration.
Selectable IDC Types:
- Fire Monitor: Alarm on short or current-limited condition; Trouble on open circuit.
- Alarm Verification: Immediate alarm on short; verification sequence for current-limited conditions; Trouble on open circuit.
- Fire/Supervisory: Supervisory on current-limited state; Alarm on short; Trouble on open circuit.
- Trouble: Trouble on short, current-limited, or open circuit conditions.
- Style C: Trouble on open or short circuit; Alarm on current-limited condition.
Figure 3 shows the interconnect wiring diagram, detailing connections between various modules including the system board, IDC boards, City Connect, DACT, and Annunciator Interface modules.
Jumper Settings/Service Switches
Jumper settings configure NAC operation (On Until Silence/Reset) and City Circuit configuration (Local Energy/Remote Station). Table 1 details jumper settings for these configurations.
NAC Operation:
- On Until Reset: Jump P2-1 to P2-2 (NAC 1) and P3-1 to P3-2 (NAC 2).
- On Until Silenced: Jump P2-2 to P2-3 (NAC 1) and P3-2 to P3-3 (NAC 2). This is required for coded operations.
City Circuit Configuration: Refer to Table 1 for jumper settings to configure City Circuits 1 and 2.
Auxiliary Circuit Supervision: Supervise AUX Zone 1/2 alarm outputs by clipping JW1/JW2 on the System Board. Supervise AUX Alarm output by clipping JW3. For Zones 3-8 supervision, remove specific jumpers on expander modules.
Service Switches:
- Zone Disconnect Switch: “ON” for normal operation, “OFF” to disconnect a zone. Allows for testing without triggering alarms.
- City Disconnect Switch: “ON” for normal operation, “OFF” to disconnect the city circuit. A trouble indication occurs when the city is disconnected.
- Alarm Output Disconnect Switch: Disables all system alarm outputs (NACs, Alarm City Circuit, Auxiliary Alarm Output, Zone Alarm Outputs).
- Walk Test Switch: “ON” places the system in Walk Test mode for single-person testing. Ignored if the system is in alarm.
- Program Switch: “ON” places the system in program mode. Ignored if the system is in alarm.
Programming Instructions
The 4004 system can be configured using the seven-segment displays and the “ACK” and “SYSTEM RESET” keys. Activating switch SW3 enters program mode. Alarms and troubles are not processed in program mode.
Default Conditions: System configured for 8-IDC, CITY/DACT, Annunciator Interface; all IDCs are FIRE type; NAC 1 is coded Temporal until Silence; NAC 2 is steady until Reset; Abnormal condition reminder is active.
Programming Steps:
- Activate SW3 to enter program mode. A tone-alert sounds until the “ACK” key is pressed. A lowercase “h” appears on the “TROUBLE” display.
- Use the “ACK” key to scroll through programming options and the “SYSTEM RESET” key to select configuration options. Refer to Figure 4 for programming selections.
- Deactivate SW3 to exit program mode. The setup is saved, and the “h” clears. Record the setup in the “CURRENT SETUP” section on the 4004 door panel label.
Figure 4 illustrates programming selections for the number of zones, initiating device point types, City/Dact module presence, Notification Appliances operation, and Annunciator interface presence.
Chapter 4: Operating Instructions
Front Panel Operation
The user interface includes controls and indicators for alarm, supervisory, trouble, power, and alarm silenced conditions (Figure 5).
Indicators and Controls:
- Supervisory LED (Yellow): Indicates a zone programmed as Fire/Supervisory is in a current-limited state (not an alarm). Press “ACK” to view the zone number on the red, seven-segment display.
- Alarm Silenced LED (Yellow): Indicates notification appliances configured “On Until Silence” are off, and an alarm remains in the system.
- AC Power LED (Green): Indicates AC power is applied to the panel.
- Fire Alarm Zone Display (Red, 7-segment): Indicates alarms and supervisories. Displays the zone number for a single zone alarm. For multiple alarms, it scrolls through the zones. A decimal point indicates the start/end of an alarm list. IDCs in alarm are illuminated ('1'-'8'); IDCs in supervisory are illuminated with a dot ('1.'-'8.').
- Trouble Display (Yellow, 7-segment): Indicates IDC, NAC, City Circuit, Power Supply, AUX output, and system trouble conditions. Displays numerals 1-8 for IDC troubles and alphabetically for other troubles (Table 2).
Operator Keys:
- ACK: Acknowledges alarm, supervisory, and trouble conditions. Silences the tone-alert. Performs a lamp test when pressed for 5 seconds (all LEDs and displays turn ON).
- ALARM SILENCE: De-energizes NACs configured as “On Until Silence.” The “ALARM SILENCED” LED turns ON until all alarms are cleared.
- SYSTEM RESET: Removes IDC loop power for 5 seconds. Turns OFF “On Until Silence” and “On Until Reset” signals if all zones are clear. Turns OFF the “Alarm Silenced” LED and annunciator alarm outputs. Displays dashes (-) during reset.
System Initialization (Power-Up)
IMPORTANT: Notify appropriate personnel of power-up.
Normal Power-Up: Apply system power. Panel displays and indicators appear. Tone alert sounds for one second. “AC POWER” LED is ON. Program the system as needed.
Power-Up Trouble Conditions: Panel displays and indicators do not appear. Check fuses or circuit breakers. If power is removed and reapplied after checks, and the system still indicates trouble, contact Simplex.
Supervisory Conditions
A Fire/Supervisory point distinguishes between Fire Alarm and Supervisory conditions. When water is flowing in a sprinkler system, an Alarm is indicated. If a sprinkler or water pump valve is closed, a “SUPERVISORY” condition is indicated. The yellow “SUPERVISORY” LED flashes, and the tone-alert sounds until acknowledged via the “ACK” key. The “SUPERVISORY” LED remains ON steady after acknowledgment.
Walk Test
The 4004 is equipped with Walk Test, activated by SW4 on the System Board. This feature allows one person to test the system.
- Alarm: Indicated with zone code notification over both NACs. Strobes may not indicate zone code if connected.
- Trouble: Indicated by activating NACs for four seconds.
- Walk Test switch is ignored if there is an alarm.
- An upper case “H” on the yellow “TROUBLE” display indicates Walk Test trouble.
- City Circuit activation is not inhibited; disconnect via Disconnect Switches if needed.
- Display and tone-alert function normally.
- Automatic system reset occurs within 30 seconds after Walk Test alarm.
- Subsequent alarms on the same zone cause another zone code.
- A “SYSTEM RESET” is required when exiting Walk Test.
System Testing (Fire Drills)
Fire Drills should be conducted periodically to ensure occupant familiarity with emergency procedures and system functionality. Testing should be directed by the owner and the local Authority Having Jurisdiction (AHJ).
Considerations for testing:
- How the owner and AHJ want the drill performed.
- Whether the building is occupied.
- Which system features are in use.
For systems connected to a city circuit, notify the AHJ. The AHJ determines if the city connection should be disabled during the test. Optional city modules have disconnect switches (SW1, SW2) for disabling city circuits.
To initiate a test, activate an initiating device (pull station, smoke detector). This simulates a real alarm condition.
Emergency Operating Instructions
If the 4004 Fire Alarm System has an Alarm, Supervisory, or Trouble condition, follow these procedures:
- Alarm-Supervisory-Trouble Condition: System indicator flashing, tone ON.
- To Acknowledge: Press “ACK” until tone alert is silenced. Review indicators and summon personnel to investigate.
- To Silence Alarm Signals: Press “ALARM SILENCE”.
- To Restore System to Normal: Press “SYSTEM RESET” within 15 seconds. Dashes appear while reset is in progress.
- Lamp Test: Press “ACK” for 5 seconds.
Chapter 5: Glossary of Terms
This chapter provides definitions for key terms used in the manual.
- Alarm: A warning of fire danger.
- Alarm Signal: A signal indicating an emergency requiring immediate action.
- Alarm Verification: A feature to reduce unwanted alarms by requiring smoke detectors to report alarm conditions for a minimum period.
- Annunciator: A unit providing status information about a circuit or location via lamps or displays.
- Authority Having Jurisdiction (AHJ): The organization responsible for approving equipment, installations, or procedures.
- Class A: A four-wire method of connecting IDC or NAC that guarantees operation with a single open conductor.
- Class B: A two-wire method of connecting IDC or NAC that causes a trouble indication with an open circuit.
- Current-Limited IDC State: Exists when an initiating device shunts a resistor (400-820 ohms for the 4004) across the IDC.
- Digital Alarm Communicator Transmitter (DACT): Transmits alarm status changes to a Digital Alarm Communicator Receiver via telephone line.
- Display: Visual representation of output data.
- Evacuation: Withdrawal of occupants from a building.
- Evacuation Signal: A distinctive signal requiring evacuation.
- FACP (Fire Alarm Control Panel): Receives input from fire alarm devices and may supply power to detection devices.
- Fire/Supervisory: An IDC point type that initiates a “Supervisory Abnormal” condition if a current-limited state is detected.
- Heat Detector: Detects abnormally high temperature or rate of temperature rise.
- Initiating Device: Component that originates a change of state condition (e.g., smoke detector, manual fire alarm box).
- Initiating Device Circuit (IDC): Circuit to which initiating devices are connected.
- Labeled: Equipment or materials with an identifying mark from an acceptable organization.
- Listed: Equipment or materials included in a list published by an acceptable organization, indicating compliance with standards or suitability for use.
- March Time Code: A notification code with a 50% duty cycle pulse train.
- Municipal Master Box: An indicating device that sends an alarm to the public fire service communication center.
- Normal State (IDC): End-of-line resistor in place with full range of line resistance and detector load.
- Notification Appliance: Fire alarm system component providing audible or visible output (e.g., bell, horn, strobe).
- Notification Appliance Circuit (NAC): Circuit connected to notification appliances.
- Open Circuit State (IDC): Absence of the end-of-line resistor.
- Protected Premises: The physical location protected by the fire alarm system.
- Remote Station Circuit: Circuit sending alarm, supervisory, or trouble signals to a remote location.
- Short Circuit IDC State: Initiating device shunts a low resistance contact across the IDC (0-200 ohms).
- Simple Code: Distinct number of pulses indicating which zone is in alarm.
- Smoke Detector: Detects visible or invisible particles of combustion.
- States (IDC): Four states associated with an IDC: Short, Current-limited, Normal, and Open circuit.
- Style B: IDC connection method providing a trouble indication on an open circuit.
- Style C/Style E: IDC point type; trouble on short/open, alarm on current-limited.
- Style D: IDC connection method providing multiple signal paths for circuit operation with a single open circuit.
- Style Y: NAC connection method providing a trouble indication on an open circuit.
- Style Z: NAC connection method providing multiple signal paths for circuit operation with a single open circuit.
- Supervisory Signal: Signal indicating the need for action related to fire suppression systems or equipment.
- Temporal Code: A three-pulse pattern adopted by NFPA as a standard evacuation pattern.
- VSMOKE: An IDC point type initiating immediate alarm on pull station/heat detector activation, or verification sequence for current-limited alarms from smoke detectors.
- Zone: A defined area within the protected premises for signal reception, transmission, or control.
Chapter 6: 4004 Battery Selection
Battery Selection
60 Hours of Standby Operation (with 10 Ah batteries): Fully configured 4004 system provides at least 60 hours standby, followed by 10 minutes of alarm, when no four-wire detectors or non-alarm loads are connected.
24 Hours of Standby Operation (with 6.2 Ah batteries): Fully configured 4004 system provides at least 24 hours standby, followed by 10 minutes of alarm, when no four-wire detectors or non-alarm loads are connected.
4004 Fire Alarm System with 4-Wire Detectors or Non-Alarm Loads: For systems requiring four-wire detectors or non-alarm loads, use the battery calculation equation in Table 4.
Table 3 provides the Supervisory Current requirements for various modules:
Module | Supervisory Current |
---|---|
Standard Panel | 52 mA |
4004-9802, 2 Pt. IDC, Low Current | 7 mA |
4004-9804, 4 Pt., Low Current | 14 mA |
4004-9822, 2 Pt. IDC, High Current | 14 mA |
4004-9824, 4 Pt. IDC, High Current | 27 mA |
4004-9806, Class A Adapter | N.A. |
4004-9808, Annunciator Interface Module | 4 mA |
4004-9809, 2 Circuit Remote Station/City Connect | 12 mA |
2080-9045 DACT | 35 mA |
Note: Add all NAC Appliances and IDC Devices for total.
Battery Selection Calculation
Table 4 provides a step-by-step calculation for determining battery requirements:
- Enter total supervisory current from all cards.
- Enter total Auxiliary power current draw in standby.
- Enter total two-wire detector current draw in standby.
- Sum lines 1, 2, and 3 for total standby current.
- Enter the required hours of standby.
- Multiply line 4 by line 5 for total standby Ah requirement.
- Enter the total NAC/AUX alarm current.
- Multiply line 7 by 0.083 for five minutes of alarm, or by 0.167 for ten minutes of alarm.
- Add lines 6 and 8.
Battery Sizing Guidelines:
- If total in line 9 is ≤ 5.1 Ah, use 2081-9272 6.2 Ah batteries.
- If total in line 9 is > 5.1 Ah and ≤ 8.3 Ah, use 2081-9274 10 Ah batteries.
- If total in line 9 is > 8.3 Ah, the 4004 charger cannot charge larger batteries. Consider using the 4004 with a 4009 NAC Power Extender or a 4005 Fire Alarm Control Panel.
Notes:
- Auxiliary loads subtract from the total 4.0 Amps of power available on the 4004.
- Standby current for detectors is listed on their data sheets. Maximum standby current draw for “low current” IDC is 2 mA per zone; for “high current” IDC is 3 mA per zone.
File Info : application/pdf, 36 Pages, 206.13KB
DocumentDocumentRelated Documents
![]() |
Simplex 4010ES Fire Alarm Control Panel Operator's Manual This manual provides comprehensive instructions for operating the Simplex 4010ES Fire Alarm Control Panel (FACP). It covers basic concepts, alarm conditions, trouble conditions, supervisory conditions, advanced functions, and system test procedures. Learn how to acknowledge alarms, silence alarms, reset the system, and manage various system events. |
![]() |
Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide Comprehensive guide for installing, operating, and programming the Simplex 4010 Fire Alarm system. Covers system overview, wiring, configuration, diagnostics, and troubleshooting. |
![]() |
Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide Comprehensive guide for the Simplex 4010 Fire Alarm system, covering installation, operation, and programming instructions. Includes system overview, wiring, configuration, diagnostics, and troubleshooting. |
![]() |
Simplex 4010 Fire Alarm: Installation, Operation, and Programming Guide Comprehensive guide for installing, operating, and programming the Simplex 4010 Fire Alarm system. Covers system components, wiring, configuration, diagnostics, and troubleshooting. |
![]() |
Simplex 4098-9019 IDNet Addressable Beam Detector Wiring and FACP Programming Guide Comprehensive guide for wiring and programming the Simplex 4098-9019 IDNet Addressable Beam Detector system with Simplex Fire Alarm Control Panels (FACPs). Covers compatibility, electrical specifications, addressing, and panel operations. |
![]() |
Simplex 4007ES Color Touchscreen LCD Annunciator Installation Manual Installation guide for the Simplex 4007ES Color Touchscreen LCD Annunciator, detailing wiring, mounting, and address setting procedures for fire alarm systems. |
![]() |
Simplex 4098 Detectors, Sensors, and Bases Application Manual This application manual provides comprehensive information on the proper use and installation of Simplex 4098 series detectors, sensors, and bases within fire alarm systems. It covers principles of operation, placement guidelines, compatibility, testing procedures, and troubleshooting for these critical fire safety components. |
![]() |
Simplex 4100ES Service Parts List Official service parts list for the Simplex 4100ES fire alarm system, detailing replacement components, modules, and accessories for maintenance and repair. |