Finder 072.11 Floor Probe for Water Presence Control
Ideal for controlling water presence on floors.
Product Image and Dimensions:
A Finder 072.11 unit is shown. Dimensions are indicated: 44mm, 32mm, 28.5mm, 13mm.
Installation Diagrams:
Diagrams illustrate the connection of cables with specified stripping lengths (9mm) and wire cross-sections (up to 6 mm²). Another diagram shows the probe installation with a screw (max Ø 5 mm) and the probe tip clearance from the floor (1 mm). A separate view shows the maximum cable diameter (10 mm) and the maximum cable length between probe and relay (200 m).
Wiring Diagram:
A schematic shows the wiring connections for the 072.11 probe to a relay (e.g., 72.x1). Terminals are labeled L/+, N/-, A1, A2, 12, 11, 14, B1, B2, B3. The diagram indicates a maximum cable length of 200m and a maximum liquid temperature of 100°C.
Technical Specifications
- Cable stripping length: 9 mm
- Distance between floor and electrodes: 1 mm
- Screw diameter for floor fixing: Max M5
- Maximum cable diameter: 10 mm
- Maximum cable length (probe to relay): 200 m (100nF/Km)
- Maximum liquid temperature: +100°C
ATTENTION: The anti-flooding sensor must be connected to terminals (B1 and B3) of control relays such as the 72.x1, setting the emptying function (ES or E) respectively. For applications in refrigeration units, the 72.01.8.230.0002 type is recommended (adjustable sensitivity 5...450 kOhm).