Autonics CT Series Programmable Digital Counters / Timers

Instruction Manual

Ordering Information

This is only for reference; the actual product does not support all combinations. For selecting the specified model, follow the Autonics website.

Model Structure: CT [Display Digits] [Size] - [Output Type] [Power Supply] [Communication]

Safety Considerations

Warning: Failure to follow instructions may result in serious injury or death.

Caution: Failure to follow instructions may result in injury or product damage.

Cautions during Use

Dimensions

Unit: mm

CTS (DIN W 48 × H 48 mm)

Front view: 48 mm, Side view: 45+8 mm, Depth: ≥ 65 mm

CTY (DIN W 72 × H 36 mm)

Front view: 72 mm, Side view: 45+8 mm, Depth: ≥ 40 mm

CTM (DIN W 72 × H 72 mm)

Front view: 72 mm, Side view: 68*87 mm, Depth: ≥ 91 mm

Panel Cut-out Dimensions

Unit Descriptions

CTS Series

CT6S-1P: 1-stage preset, standard model

CT6S-1PT: 1-stage preset, comm. model

CT6S-2P: 2-stage preset, standard model

CT6S-2PT: 2-stage preset, comm. model

CT6S-I: Indicator, standard model

CT6S-IT: Indicator, comm. model

CTY Series

CT6Y-1P: 1-stage preset, standard model

CT6Y-1PT: 1-stage preset, comm. model

CT6Y-2P: 2-stage preset, standard model

CT6Y-2PT: 2-stage preset, comm. model

CT6Y-I: Indicator, standard model

CT6Y-IT: Indicator, comm. model

CTM Series

CT6M-1P: 1-stage preset, standard model

CT6M-1PT: 1-stage preset, comm. model

CT6M-2P: 2-stage preset, standard model

CT6M-2PT: 2-stage preset, comm. model

CT6M-I: Indicator, standard model

CT6M-IT: Indicator, comm. model

Part Descriptions

No. Part Name Function
1 Counting value display part (red) RUN mode: Displays counting value, time progress. Parameter 1, 2 group: Displays setting item.
2 Setting value display part (green) RUN mode: Displays setting value. Parameter 1, 2 group: Displays setting content.
3 Key LOCK indicator Turns ON for key LOCK setting.
4 Counter indicator CNT: Turns ON for counter operation.
5 Timer indicator TMR: In timer operation - Flashes: time progress / turns ON: stopping time.
6 Preset value checking, changing indicator PS1, PS2: Turns ON when checking and changing preset value.
7 Output indicator OUT1, OUT2: Turns ON for the dedicated control output ON.
8 RESET key [RST]: Counting value RESET, BATCH counting value RESET.
9 MODE key [MD]: RUN mode → Parameter 1, 2 group. Move to the next when the parameter setting. Enter preset value change mode and move digits.
10 Setting key [▼], [▲]: Preset value of preset value change mode and setting content of parameter 1, 2 group. Enter function setting check mode and move check items.
11 BATCH key [BA]: Enter BATCH counter indication mode.
12 BATCH output indicator (red) BA.O: Turns ON when BATCH output ON.
13 BATCH setting value checking, changing indicator (green) BA.S: Turns ON when checking and changing BATCH setting value.

Connections

Counter operation: If INHIBIT signal is applied, count input will be prohibited. Timer operation: If INHIBIT signal is applied, time progressing will stop (HOLD).

CTS Series Connections

CT6S-1P / CT6S-1PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CT6S-2P / CT6S-2PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CT6S-I / CT6S-IT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CTY Series Connections

CT6Y-1P / CT6Y-1PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CT6Y-2P / CT6Y-2PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CT6Y-I / CT6Y-IT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2

CTM Series Connections

CT6M-1P / CT6M-1PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2, RS485 A(+), RS485 B(-)

CT6M-2P / CT6M-2PT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2, RS485 A(+), RS485 B(-)

CT6M-I / CT6M-IT: INA, INB/INH, RESET, 0 VDC=, SOURCE, OUT1, OUT2, RS485 A(+), RS485 B(-)

Specifications

Model CTS□-□□□ CTY□-□□□ CTM□-□□□
Display digits 4-digit 6-digit 6-digit
Display method 7-segment (counting value: red, setting value: green) LED
Character size (W × H, mm) Counting value: 6.5 × 10, Setting value: 4.5 × 8 Counting value: 4.5 × 10, Setting value: 3.5 × 7 Counting value: 4.2 × 9.5, Setting value: 3.5 × 7
Counter Count up, count down, count up / down
Counting range 01) -999 to 9999 -99999 to 999999
Timer Count up, count down
Error Repeat / SET / voltage / Temp.
Input logic Voltage input (PNP) / No-voltage input (NPN)
One-shot output time 0.01 to 99.99 s
Product components Product, instruction manual, Bracket (x2)
Unit weight (packaged) ≈ 159 g (≈ 212 g) ≈ 140 g (≈ 228 g) ≈ 252 g (≈ 322 g)
Approval CE, UL, RoHS
Contact control output (Relay) Type (1-stage): SPDT (1c) × 1
Type (2-stage): SPST (1a) × 2
Type (1-stage): SPDT (1c) × 1
Type (2-stage): SPST (1a) × 1, SPDT (1c) × 1
Type (1-stage): SPDT (1c) × 1
Type (2-stage): SPST (1a) × 1, SPDT (1c) × 1
Capacity 250 VAC~ 5 A, 30 VDC~ 5 A (resistive load) 250 VAC~ 3 A, 30 VDC~ 3 A (resistive load) 250 VAC~ 5 A, 30 VDC~ 5 A (resistive load)
Solid-state control output (NPN open collector) Type (1-stage): Standard × 1
Type (2-stage): Standard × 1
Type (1-stage): Standard × 1
Type (2-stage): Standard × 1
Type (1-stage): Standard × 2
Type (2-stage): Standard × 3
Capacity ≤ 30 VDC~, 100 mA
Power supply 100 - 240 VAC~ ±10% 50 / 60 Hz 24 VAC~ ±10% 50 / 60 Hz, 24 - 48 VDC~ ±10%
Power consumption ≤ 12 VA AC: ≤ 10 VA, DC: ≤ 8 W ≤ 12 VA
External power supply ≤ 12 VDC~ ±10% 100 mA
Memory retention ≈ 10 years (non-volatile semiconductor memory)
Insulation resistance ≥ 100 MΩ (500 VDC~ megger)
Dielectric strength 2,000 VAC~ 50 / 60 Hz for 1 minute
Noise immunity ± 2 kV square wave noise (pulse width: 1 ㎲) by noise simulator
Vibration 0.75 mm double amplitude at 10-55 Hz (1 min) in each X, Y, Z direction for 1 hour
Vibration (malfunction) 0.5 mm double amplitude at 10-55 Hz (1 min) in each X, Y, Z direction for 10 min
Shock 300 m/s² (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction) 100 m/s² (≈ 10 G) in each X, Y, Z direction for 3 times
Relay life cycle Mechanical: ≥ 1,000,000 operations, Electrical: ≥ 100,000 operations
Ambient temperature -10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Protection rating IP65 (front part, IEC standard)

Error Display and Output Operation

Error Display

Display Description Troubleshooting
ERR0 Preset value = 0 Change the preset value to anything other than 0.

Reset

In RUN mode, pressing the [RST] key or applying a signal to the RESET terminal on the back side will reset the present value. The output maintains the OFF state.

Model No-voltage (NPN) Voltage (PNP)
CTS Short no. 9, 10 terminals Short no. 8, 10 terminals
CTY Short no. 4, 5 terminals Short no. 3, 5 terminals
CTM Short no. 11, 12 terminals Short no. 10, 12 terminals

Preset Value Change Mode

Even in preset value change mode, input operation and output control will continue. The preset value can be set to 0, and the output for a 0 preset value will occur. However, the preset value cannot be set to 0 depending on the output operation mode (the value flashes 3 times when setting to 0). If no key is touched for 60 seconds, the product returns to RUN mode without saving.

Example: To set 1-stage preset value = 180, 2-stage preset value = 200

  1. Press [◀] key to enter preset value change mode. The PS1 indicator turns ON, and the first digit of the preset value flashes.
  2. Use [◀], [▲], [▼] keys to set the 1-stage preset value to 180.
  3. Press [MD] key to enter 2-stage preset value change mode.
  4. Use [◀], [▲], [▼] keys to set the 2-stage preset value to 200.
  5. Press [MD] key to return to RUN mode.

Select Input Logic

For CTS and CTY models, detach the case to proceed with settings. The position of the internal switch varies by model.

How to change settings: Power OFF → Change settings → Power ON → Press [RESET] key or input RESET signal (≥ 20 ms) to the external terminal.

CTS, CTY

Internal switch SW1: NPN / PNP

CTM

Internal switch SW1: NPN / PNP

Detach the Case

CTS, CTY: Press in direction ① and pull toward direction ② for detaching the case and contents. Caution: Turn OFF the power before detaching the case.

Mode Setting

01) Use [▲], [▼] keys to check parameter settings. In 2-stage preset models, 1-stage and 2-stage preset values are displayed by pressing [MD] key. For timers, this is available for output operation modes: OND, OND.1, OND.2.

02) For CT6M-1P / 2P models only. Press [◀] key to set BATCH counter setting value.

Parameter Setting

Some parameters are activated/deactivated depending on the model or other parameter settings. Refer to the description of each parameter.

[MD] key: Saves current setting and moves to the next parameter.

[◀] key: Checks fixed value / Changes setting digits.

[▲], [▼] key: Changes setting values.

Parameter 1 group (counter)

Parameter Mark Defaults Setting range Display condition
Counter / timer C-T COUN COUN: counter, TIME: timer -
Input operation mode IN UD-C UD-C: phase different input, UD-A: command input, UD-B: individual input, UP, UP-1, UP-2, DN, DN-1, DN-2 -
Output operation mode OUtM F F, N, C, R, K, P, Q, A, S*, T*, D* (*C1-2 input operation mode: UD-A, UD-B, UD-C) [Preset setting model]
Indication mode DspM TOTAL HOLD, TOTAL ([Indicator model]) [Indicator model]
Max. counting speed CPS 30 30, 1K, 5K, 10K, 1 cps Max. counting speed is when duty ratio of INA or INB input signal is 1:1. It is applied for INA, or INB input as same.
OUT2 output time OUT2 HOLD 0.01 to 99.99 sec, Hold [2-stage preset setting model]
OUT1 output time OUT1 10 0.01 to 99.99 sec, Hold [2-stage preset setting model]
OUT output time OUtT HOLD 0.01 to 99.99 sec, Hold [1-stage preset setting model]
Counting value / preset value decimal point DP ------ ------, -----.-, ----.--, ---.---, --.----, -.----- ([6 digit model])
----, ---.-, --.--, -.--- ([4 digit model])
-
Min. RESET time RST 20 1, 20 ms -
Input logic SIG NPN NPN, PNP Set the same as settings of input logic selection switch.
Prescale decimal point ScDP -.----- -.----- , -----.-, ----.--, ---.---, --.---- ([6 digit model])
-.---, ---.-, --.-- ([4 digit model])
-
Prescale value SCL !00000 0.00001 to 99999.9 ([6 digit model])
0.001 to 999.9 ([4 digit model])
-
Start Point value STRT 000000 0.00000 to 999999 ([6 digit model])
0.000 to 9999 ([4 digit model])
[C1-2 input operation mode: UD-C, UP, UP-1, UP 2, UD-A, UD-B]
Memorize counting value DATA CLR CLR: Resets counting value when power is off.
REC: Memorizes counting value at the moment of power off. (memory retention)
-
Key lock LOCK L.OFF L.OFF: Unlock key LOCK, key LOCK indicator OFF
LOC.1: Locks [RST] key, key LOCK indicator ON
LOC.2: Locks [◀], [▼], [▲] key, key LOCK indicator ON
LOC.3: Locks [RST], [◀], [▼], [▲] key, key LOCK indicator ON
-

Parameter 1 group (timer)

Parameter Mark Defaults Setting range Display condition
Counter / timer C-T TIME COUN: counter, TIME: timer -
Time range SEC Refer to the table below. 02) -
UP / DOWN mode U-D UP UP: 0 → setting time, DN: setting time → 0 -
Indication mode DspM TOTAL HOLD, TOTAL, ONT.D: On time display ([Indicator model]) [Indicator model]
Memorize counting value DATA CLR CLR: Resets counting value when power is off.
REC: Memorizes counting value at the moment of power off. (memory retention)
[Indicator model]
Output operation mode OUtM OND OND, OND.1, OND.2, FLK, FLK.1, FLK.2, INT, INT.1, INT.2 03), OFD, NFD, NFD.1, INTG -
OUT2 output time OUT2 HOLD 0.01 to 99.99 sec, Hold [2-stage preset setting model]
OUT1 output time OUT1 10 0.01 to 99.99 sec, Hold [2-stage preset setting model]
OUT output time OUtT HOLD 0.01 to 99.99 sec, Hold [1-stage preset setting model]
Input logic SIG NPN NPN, PNP Set the same as settings of input logic selection switch.
Input signal time InT 20 1, 20 ms CTS / CTY: min. signal width of INA, INH, RESET signal
CTM: min. signal width of INA, RESET, INHIBIT, BATCH RESET signal
Key lock LOCK L.OFF L.OFF: Unlock key LOCK, key LOCK indicator OFF
LOC.1: Locks [RST] key, key LOCK indicator ON
LOC.2: Locks [◀], [▼], [▲] key, key LOCK indicator ON
LOC.3: Locks [RST], [◀], [▼], [▲] key, key LOCK indicator ON
-

Parameter 2 group (communication)

Only for RS485 communication models.

Parameter Mark Defaults Setting range Display condition
Comm. address ADDR 001 1 to 127 Do not set the same address during multi-comm.
Comm. speed BPS 96 24: 2,400, 48: 4,800, 96: 9,600, 192: 19,200, 384: 38,400 bps -
Parity bit PRTY NONE NONE, EVEN, ODD -
Stop bit STP 2 1, 2 bit -
Response waiting time RSwT 20 16 to 99 ms (Comm. speed: 24)
8 to 99 ms (Comm. speed: 48)
5 to 99 ms (Comm. speed: 96, 192, 384)
-
Comm. write COMw ENA ENA: enable, DISA: disable -

Communication Interface

RS485

Software

Download the installation file and manuals from the Autonics website.

DAQMaster

This is a comprehensive device management program for Autonics products, providing parameter setting, monitoring, and data management.

Models: CT6Y-2P2T, CT Series Programmable Digital Counter, Programmable Digital Counter, Digital Counter, Digital Timer

File Info : application/pdf, 2 Pages, 987.06KB

PDF preview unavailable. Download the PDF instead.

tyBgwGAFY2VzIsvlVrx4rLqXK7Rpz23lFAYkK645

References

Adobe PDF Library 16.0.3 Adobe InDesign 17.0 (Windows)

Related Documents

Preview Autonics CT Series Programmable Digital Counters and Timers Product Manual
This product manual provides detailed information on Autonics' CT Series programmable digital counters and timers, covering features, specifications, safety considerations, and operational guidance for models like CT6S, CT6Y, and CT6M.
Preview Autonics CX Series LCD Display Counter/Timer Instruction Manual
Instruction manual for Autonics CX Series LCD Display Counter/Timer, covering models CX6S and CX6M. Provides details on specifications, connections, operations, function settings, and safety considerations.
Preview Autonics LE3S Series LCD Digital Thumbwheel Switch Timers Instruction Manual
Instruction manual for Autonics LE3S Series LCD Digital Thumbwheel Switch Timers, covering ordering information, product components, dimensions, safety considerations, cautions during use, specifications, output operation modes, time ranges, connections, and UP/DOWN mode.
Preview Autonics ATM Series Analog Timers Catalog
Comprehensive catalog detailing the Autonics ATM Series of miniature analog timers. Includes specifications, ordering information, features, dimensions, and pin arrangements for models ATM4-2, ATM4-5, and ATM4-6.
Preview Autonics MT4W Series 4-Digit Multi Panel Meters Instruction Manual
Instruction manual for Autonics MT4W Series 4-Digit Multi Panel Meters, covering specifications, connections, parameter settings, and troubleshooting.
Preview Autonics BS5 Series Groove-Depth 9 mm Photomicro Sensors Instruction Manual
Instruction manual for the Autonics BS5 Series groove-depth 9 mm photomicro sensors, covering ordering information, connections, specifications, circuit diagrams, operation timing, safety considerations, and installation cautions.
Preview Autonics TCN4 Series Dual Indicator Temperature Controller Instruction Manual
Instruction manual for the Autonics TCN4 Series Dual Indicator Temperature Controller, covering specifications, dimensions, connections, parameter groups, functions, and safety considerations.
Preview Autonics TX Series LCD PID Temperature Controllers Instruction Manual
Instruction manual for Autonics TX Series LCD PID Temperature Controllers, covering safety considerations, specifications, ordering information, connections, and parameter settings.